GAS VALVE REMOVAL

1.Shut off gas supply to the heater. Remove gas piping to gas valve inlet.

2.Disconnect wires, pilot tubing and bleed line, if required.

3.Turn vertical gas pipe from manifold slightly and unscrew gas valve.

4.Reverse above procedure to re-install.

MAIN BURNER AND ORIFICE REMOVAL

1.Remove burner drawer. See burner drawer removal procedure.

2.Remove screws and burner hold down bracket.

NOTE: If the heat exchanger is sooted badly, the burner hold down bracket and spacer can become distorted from direct flame impingement and this usually neces- sitates replacement of these parts.

3.Lift burners from slotted spacers and slide from orifices. Clean with a non-sparking wire brush.

4.Orifices usually do not need to be replaced. To clean, run either copper wire or wood toothpick through orifice. Do not enlarge hole. To remove orifice, use a socket wrench and re- move from manifold. DO NOT over tighten when reinstalling.

PILOT REMOVAL AND CLEANING

1.Remove burner drawer. (See burner drawer removal procedure).

2.Disconnect pilot tubing, disconnect wires from gas valve.

3.Disconnect pilot bracket from burner shield.

4.Remove pilot from bracket.

5.Remove pilot orifice and air opening, and clean with wire or small brush. CAUTION! DO NOT enlarge hole in pilot orifice.

6.Reverse above procedure to re-install.

HEAT EXCHANGER REMOVAL

1.Shut water, gas and electricity off, close valves and relieve pressure, remove relief valve.

Remove side inspections panels.

2.Remove top holding screws.

3.Remove draft diverter, lift and remove top and flue collector. Remove inspection panels.

4.Loosen bolts and disconnect flange nuts on inlet-outlet header, loosen union(s) at gas pipe and slide heater away from piping until stud clear the header.

5.Remove heat exchanger corner brackets.

6.Remove combustion chamber clips at the four corners of the heat exchanger.

7.Lift heat exchanger straight up using caution not to damage refractory.

8.Reverse above procedure to reinstall.

TUBE CLEANING PROCEDURE

Establish a regular inspection schedule frequency, depending on local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16” in thickness.

The heater may be cleaned from the right side, without breaking pipe connections. It is preferable, however, to remove both headers for better visibility through the tubes and to be sure the ground-up lime dust does not get into the system.

Note that you do not remove the top panel or the heat exchanger, generally.

After reaming, mount the wire brush in place of the auger and clean out debris remaining in the tubes.

Another method is to remove the heat exchanger, ream tubes and immerse heat exchanger in non-inhibited de-scale solvent for severe scale build up.

TUBEREPLACEMENTPROCEDURE

On Raypak units, tube replacement may be effected without rolling as a temporary means or repair, providing there are two or more tubes rolled in to act as stays on the left and right side. The “O” rings should provide a seal up to 120 PSI working pressure.

Use 3/8” heavy duty reversible drill motor or larger to power the tube roller. If a reversible drill is not available, after rolling the tube in, remove the drill motor and wrench out the roller. A tube roller is available from the factory.

RAYPAK TUBE CLEANING KIT

Extension Pieces (5)

Auger with Carbide Tip

Wire Brush

 

 

 

 

 

Fig. # 8154.0

21

Image 21
Contents What to do if YOU Smell GAS Installation Operating Instructions CommercialWaterchemistry Contents For Your Safety Read Before Operating START-UP Procedures Before START-UPBurners WaterTo Turn OFF GAS to Appliance Operating InstructionsWater Pressure Switch Maintenance and Care ProceduresAfter START-UP Visual InspectionPool & SPA Water Chemistry Basic Tips if Heater will not FireCalifornia Proposition 65 Warning Important NoticeClearances Base InstallationStep #2 Indoor HeaterVenting Connections Vent Piping223.1/NFPA GAS Pressure Regulator GAS Supply ConnectionsPlumbing for Water Connections Location Pipe Sizing for GAS ConnectionsFlow Rates Model Pipe Size MIN. GPM MAX. GPM CompanionflangeconnectionsPressure Relief Valve Installation Auxiliary Bypass Valve AdjustmentAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS UnithermgovernoroperationS8600 Ignition Control Electrical WiringPage Page Page Page Typical Comfortable SPA Temperature Range CONTROLS/ADJUSTMENTS/REPLACEMENTSKnobstopadjustment Servicing InsructionsPressure Switch Adjustment Pressure SwitchPressure Switch Adjustment Range Pilot SafetyRaypak Tube Cleaning KIT Desootingprocedure UNITHERMGOVERNORU.G.REPLACEMENTCombustionchamberremoval Importantnotice Liming Troubleshooting Honeywell S8600 ElectricalHighvoltage Raypak, Inc Eastman Ave Oxnard, CA Replacement Parts ListThis page is empty Pilot ASSEMBLY- Electronic Ignition Page Page
Related manuals
Manual 32 pages 11.75 Kb

514-824 specifications

The Raypak 514-824 is a leading model in the realm of heating solutions, specifically designed for outdoor residential and commercial applications. Known for its efficiency and durability, the Raypak 514-824 has gained popularity among users looking for reliable heating systems.

One of the standout features of the Raypak 514-824 is its advanced design that incorporates high-quality materials ensuring longevity. This model is constructed with a robust heat exchanger, typically made of copper or bronze, which promotes better thermal conductivity while resisting corrosion. This ensures that the unit maintains a high performance level even after prolonged use, making it an excellent choice for areas with varying weather conditions.

The technological aspects of the Raypak 514-824 are also impressive. It is equipped with an intuitive digital control system that allows for precise temperature adjustments. Users can easily set their desired temperature, which is maintained automatically, providing comfort with minimal manual control. The digital display is user-friendly, making it simple to monitor system performance and adjust settings as needed.

Efficiency is a critical characteristic of the Raypak 514-824. With a focus on energy-saving capabilities, this heater exceeds industry standards, often achieving efficiency ratings that minimize energy consumption. This not only results in cost savings on utility bills but also contributes to environmental sustainability, making it a more responsible choice for heating needs.

Safety features are paramount in the design of the Raypak 514-824. It includes various protections such as high-limit switches and pressure regulators that help prevent overheating and maintain optimal operating conditions. These safety measures ensure that the unit operates reliably and minimizes risks associated with traditional heating systems.

Furthermore, installation versatility sets the Raypak 514-824 apart. It is designed for straightforward installation, suitable for various setups whether it's integrated with a swimming pool or spa heating system. This adaptability makes it an ideal selection for anyone looking to enhance their outdoor space with effective heating solutions.

In summary, the Raypak 514-824 is a high-performing, efficient, and versatile heating model that combines modern technology with significant safety features. Its emphasis on user-friendly operation and long-lasting materials makes it a top contender in the heating market, catering to both residential and commercial applications. The Raypak 514-824 exemplifies a commitment to quality, efficiency, and reliability.