Generac ASPAS1CCL015 Engine OIL Recommendations, Coolant Recommendations, Before Installation

Page 10

Section 2 — Installation

Carrier Liquid-cooled 15 kW Generators

1.14 ENGINE OIL RECOMMENDATIONS

The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service SJ or latest available.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:

 

Temperature

Oil Grade (Recommended)

 

 

Above 80° F (27° C)

SAE 30W or 15W-40

 

 

32° to 80° F (-1° to 27° C)

SAE 20W-20 or 15W-40

 

 

Below 32° F (0° C)

SAE 10W or 15W-40

 

NOTE:

Synthetic oil is highly recommended when the generator will be operating in ambient tempera- tures which regularly exceed 90° F and/or fall below 30° F.

Any attempt to crank or start the engine before

!it has been properly serviced with the recom- mended oil may result in an engine failure.

1.15 COOLANT RECOMMENDATIONS

Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is about 8 U.S. quarts (7.6 liters). Use only deionized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the rec- ommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.

Do not use any chromate base rust inhibitor

!with ethylene glycol base anti-freeze or chromi- umhydroxide (“green slime”) forms and will cause overheating. Engines that have been operated with a chromate base rust inhibitor must be chemically cleaned before adding eth- ylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. It is also recommended that any soluble oil inhibitor is NOT used for this equipment.

1.16 BEFORE INSTALLATION

Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Isolation Method” and “Total Circuit Isolation Method” in Sections 2.5 and 2.6.

The generator’s rated wattage/amperage capacity must be adequate to handle all electrical loads that the unit will power. The critical (essential) loads may need to be grouped together and wired into a sepa- rate “emergency” distribution panel.

The standard transfer switch has no sensing or con- trolling circuit boards. Instead, the generator control console houses a “Printed Circuit Board Assembly”, which controls all phases of operation, including engine start up and load transfer.

2.1STANDBY GENERATOR INSTALLATION

DANGER

Connecting this generator to an electrical sys- tem normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distri- bution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

If an open bottom is used, the engine-genera- tor is to be installed over non-combustible materials and should be located such that com- bustible materials are not capable of accumu- lating under the generator set.

Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula- tions pertaining to the installation.

This genset must be installed on a level surface. The base frame must be level within 1/2 inch all around.

After the system has been installed, do nothing

!that might render the installation in noncompli- ance with such codes, standards and regulations.

‹2.1.1 NFPA STANDARDS

The following published standards booklets pertain- ing to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:

8 Carrier

Image 10
Contents Liquid-cooled, Prepackaged Standby Generators Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Your Carrier Dealer isIntroduction IFC Safety Rules General Hazards Fire Hazards ‹ Standards IndexAutomatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Generator Fuel SystemUnpacking SpecificationsLifting the Generator ‹ 1.10.2 Engine Specifications Reconfiguring the Fuel SystemTorque Specifications Fuel ConsumptionCoolant Recommendations Before InstallationEngine OIL Recommendations ‹ 2.1.1 Nfpa StandardsGenerator Location Generator Mounting SupportBasic Standby Electric System ‹ 2.1.2 Other Published StandardsTotal Circuit Isolation Method Transfer Switch Signal ConnectionsEmergency Circuit Isolation Method Generator AC Neutral Connections‹ 2.10.1 Vented Batteries Battery InstallationPreparation Before START-UP ‹ 2.11.1 Prior to Initial START-UPControl Console Components Manual Transfer START-UP Automatic Operation ‹ 3.1.2 Fault Indicator Lamp‹ 3.1.5 SET Exercise Time Switch Weekly Exercise CycleCooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.4.3 Engine Coolant ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System‹ 4.5.2 Check Battery ‹ 4.5.1 Check Engine OIL Level‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.12 Spark Plugs‹ 4.6.3 Battery Maintenance ‹ 4.6.2 Battery‹ 4.6.4 Battery Replacement Scheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionCarrier Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Cover Connector Housing Housing Governor ConnectorConnector Interface Assembly ASM Motor StepperDampener Vibration Base Mounting 1.5L Stnrd & AcstcWasher Shakeproof EXT 5/16 STL Washer Flat 5/16 ZincPanel for Access Assembly Cover Access Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Roof ACSTC&STND Cmprtmnt 1.5LATO Panel Back & Bottom Switch ROC Dpdt ON-OFF-ONWire Assembly Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware Ground Wire Starter Switch OIL PressureARM Adjust Alternator ENGINE-1.5L14 21 Venturi 1.5L Modine Tank Coolant RecoveryRadiator 1.5L Guard FAN 1.5L ModineVapor Weldment Mounting Base Cover AIR CleanerGasket AIR Cleaner Adapter Flange Fuel InletOTH Blowgousin re Assy Rotor 15KW Housing BlowerAssy Rotor 10KW Assy Rotor 20KWBRACKET, Battery Hold Down ASSY,WIRE#16 REDBOOT, Battery Cable Battery Post Cover RED+Saddle 2 Inch Manifold Exhaust 1.5LNipple TOE 1.5NPTX5.5 BLK Iron PIPE,EXHAUST 1.5L STNDRD&ACSTCMANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

ASPAS1CCL015 specifications

The Generac ASPAS1CCL015 is a cutting-edge automatic standby generator that provides reliable backup power in the event of an electrical outage. Designed with innovative technology and robust features, it ensures that homes and businesses can maintain essential operations without interruptions, enhancing peace of mind and safety during unforeseen power disruptions.

One of the standout features of the Generac ASPAS1CCL015 is its powerful engine, designed to produce up to 15 kilowatts of electricity. This makes it suitable for a wide range of applications, from residential homes to small commercial establishments. The generator operates on propane or natural gas, providing flexibility in fuel options based on user preferences or availability in their region.

Incorporating advanced technologies, the ASPAS1CCL015 is equipped with an automatic transfer switch (ATS). This feature allows the generator to automatically detect power outages and start up within seconds, ensuring that homes remain powered without a manual start. The ATS also reassesses whether the utility power has restored, allowing for a smooth transition back to grid power when available.

The unit is designed to be both quiet and efficient, featuring a low-emission engine that meets stringent environmental standards. This is an increasingly important consideration for many users concerned about eco-friendliness. Its noise-reduction technology ensures that operation is not disruptive, allowing users to run the generator during night hours without disturbing the peace.

In terms of user-friendly features, the Generac ASPAS1CCL015 is equipped with an intuitive digital control panel. Users can easily monitor the generator's status, run diagnostic checks, and access maintenance reminders. This enhances the overall user experience and promotes proactive care of the equipment.

Durability is another hallmark of the ASPAS1CCL015. Constructed with corrosion-resistant materials, the generator can withstand various weather conditions, making it a reliable option for outdoor settings. Its compact design allows for easy installation, whether in a garage, basement, or an external concrete pad.

Overall, the Generac ASPAS1CCL015 combines reliability, advanced technology, and user-friendly features to deliver a dependable electricity solution. Its capability to seamlessly transition between power sources, coupled with the sustainable operation, positions it as an excellent choice for those looking to safeguard their homes or businesses against power outages.