Section 1 - General Information

Carrier Liquid-cooled 15 kW Generators

1.1GENERATOR

This equipment is a liquid-cooled, engine-driven gen- erator set. The generator is designed to supply elec- trical power that operates critical electrical loads during utility power failure. The unit has been facto- ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only. Use this generator as a source of electrical power for the oper- ation of 120 and/or 240 volts, single phase loads.

These models are available. They are rated as follows:

Model ASPAS1CCL015: Provides 15,000 watts (15 kW) of single phase power.

If this generator is used to power electrical

!load circuits normally powered by a utility power source, it is required by code to install a transfer switch. The transfer switch must effectively isolate the electric system from the utility distribution system when the generator is operating (NEC 701). Failure to isolate an electrical system by such means results in damage to the generator and may also result in injury or even death to utility power work- ers due to backfeed of electrical energy.

1.2TRANSFER SWITCH

This generator system includes a matched automatic transfer switch which is intended to be used in con- junction with the generator. It is supplied with a NEMA 3R enclosure. The NEMA 3R enclosure is weather proof and can be used indoors or outdoors. Follow these rules:

Install the transfer switch on a firm, sturdy sup- porting structure.

To prevent switch distortion, level the switch if nec- essary. This can be done by placing washers between the switch enclosure and the mounting surface.

Never install the switch where water or any corro- sive substance might drip onto the enclosure.

Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor- rosive vapors.

Failure to utilize a Carrier transfer switch with this generator will void the warranty.

1.3AUTOMATIC SYSTEM OPERATION

When this generator, along with its transfer switch, has been installed and interconnected, a circuit board in the generator panel constantly monitors utility power source voltage. Should that voltage drop below a pre- set value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the generator starts, the transfer switch transfers load circuits so the generator can power them.

When utility source voltage has been restored, the switch re-transfers back to the utility source voltage and the generator then shuts down.

Please reference the transfer switch manual for spe- cific information.

1.4GENERATOR AC CONNECTION

SYSTEMS

The generator was shipped from the factory with its stator AC output leads connected in a single-phase, three-wire generator AC connection system (Figure 1.1). The stator assembly in this system consists of a pair of stationary windings, with two leads brought out of each winding. Each single winding can supply 120 volts AC, 60 Hertz. When the two windings are connected in series, a 240 volts, 60 Hertz AC output results. Typically the two “hot” leads in the circuit are Wires No. 11 and 44. The “Neutral” leads are the junction of Wires 22 and 33.

Figure 1.1 - Generator AC Connection System

1.5MAIN CIRCUIT BREAKER

The generator’s main circuit breaker is included with the unit as shipped from the factory. The breaker for each unit is described in Figure 1.2.

Figure 1.2 - Main Circuit Breaker

Model

Rating

Phase

Actual Current

C/B Rating*

% over rating

Circuit Breaker

ASPAS1CCL015

15,000

1

62.5

70

112%

70A BQ2

* Amp Rating of CB structured under model.

4 Carrier

Image 6
Contents Liquid-cooled, Prepackaged Standby Generators Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Your Carrier Dealer isIntroduction IFC Safety Rules General Hazards Fire Hazards ‹ Standards IndexAutomatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Generator Fuel SystemSpecifications UnpackingLifting the Generator ‹ 1.10.2 Engine Specifications Reconfiguring the Fuel SystemTorque Specifications Fuel ConsumptionCoolant Recommendations Before InstallationEngine OIL Recommendations ‹ 2.1.1 Nfpa StandardsGenerator Location Generator Mounting SupportBasic Standby Electric System ‹ 2.1.2 Other Published StandardsTotal Circuit Isolation Method Transfer Switch Signal ConnectionsEmergency Circuit Isolation Method Generator AC Neutral Connections‹ 2.10.1 Vented Batteries Battery InstallationPreparation Before START-UP ‹ 2.11.1 Prior to Initial START-UPControl Console Components Manual Transfer START-UP Automatic Operation ‹ 3.1.2 Fault Indicator Lamp‹ 3.1.5 SET Exercise Time Switch Weekly Exercise CycleOverload Protection for Engine DC Electrical System Cooling SystemChecking Fluid Levels ‹ 4.4.3 Engine Coolant ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System‹ 4.5.2 Check Battery ‹ 4.5.1 Check Engine OIL Level‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.12 Spark Plugs‹ 4.6.2 Battery ‹ 4.6.3 Battery Maintenance‹ 4.6.4 Battery Replacement Scheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionCarrier Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Cover Connector Housing Housing Governor ConnectorConnector Interface Assembly ASM Motor StepperDampener Vibration Base Mounting 1.5L Stnrd & AcstcWasher Shakeproof EXT 5/16 STL Washer Flat 5/16 ZincPanel for Access Assembly Cover Access Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Roof ACSTC&STND Cmprtmnt 1.5LATO Panel Back & Bottom Switch ROC Dpdt ON-OFF-ONWire Assembly Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware Ground Wire Starter Switch OIL PressureARM Adjust Alternator ENGINE-1.5L14 21 Venturi 1.5L Modine Tank Coolant RecoveryRadiator 1.5L Guard FAN 1.5L ModineVapor Weldment Mounting Base Cover AIR CleanerGasket AIR Cleaner Adapter Flange Fuel InletOTH Blowgousin re Assy Rotor 15KW Housing BlowerAssy Rotor 10KW Assy Rotor 20KWBRACKET, Battery Hold Down ASSY,WIRE#16 REDBOOT, Battery Cable Battery Post Cover RED+Saddle 2 Inch Manifold Exhaust 1.5LNipple TOE 1.5NPTX5.5 BLK Iron PIPE,EXHAUST 1.5L STNDRD&ACSTCYour Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

ASPAS1CCL015 specifications

The Generac ASPAS1CCL015 is a cutting-edge automatic standby generator that provides reliable backup power in the event of an electrical outage. Designed with innovative technology and robust features, it ensures that homes and businesses can maintain essential operations without interruptions, enhancing peace of mind and safety during unforeseen power disruptions.

One of the standout features of the Generac ASPAS1CCL015 is its powerful engine, designed to produce up to 15 kilowatts of electricity. This makes it suitable for a wide range of applications, from residential homes to small commercial establishments. The generator operates on propane or natural gas, providing flexibility in fuel options based on user preferences or availability in their region.

Incorporating advanced technologies, the ASPAS1CCL015 is equipped with an automatic transfer switch (ATS). This feature allows the generator to automatically detect power outages and start up within seconds, ensuring that homes remain powered without a manual start. The ATS also reassesses whether the utility power has restored, allowing for a smooth transition back to grid power when available.

The unit is designed to be both quiet and efficient, featuring a low-emission engine that meets stringent environmental standards. This is an increasingly important consideration for many users concerned about eco-friendliness. Its noise-reduction technology ensures that operation is not disruptive, allowing users to run the generator during night hours without disturbing the peace.

In terms of user-friendly features, the Generac ASPAS1CCL015 is equipped with an intuitive digital control panel. Users can easily monitor the generator's status, run diagnostic checks, and access maintenance reminders. This enhances the overall user experience and promotes proactive care of the equipment.

Durability is another hallmark of the ASPAS1CCL015. Constructed with corrosion-resistant materials, the generator can withstand various weather conditions, making it a reliable option for outdoor settings. Its compact design allows for easy installation, whether in a garage, basement, or an external concrete pad.

Overall, the Generac ASPAS1CCL015 combines reliability, advanced technology, and user-friendly features to deliver a dependable electricity solution. Its capability to seamlessly transition between power sources, coupled with the sustainable operation, positions it as an excellent choice for those looking to safeguard their homes or businesses against power outages.