Briggs & Stratton 30208 owner manual Troubleshooting, Problem Cause Correction

Page 15

3500W Portable Generator

TROUBLESHOOTING

Problem

Cause

Correction

 

 

 

 

 

 

1.

One of the circuit breakers is

1.

Reset circuit breaker.

 

 

open.

 

 

No AC output is available, but

2.

Fault in generator.

2.

Contact Authorized service facility.

3.

Poor connection or defective cord

3.

Check and repair.

generator is running.

 

set.

 

 

 

 

 

 

 

4.

Connected device is bad.

4.

Connect another device that is in

 

 

 

 

good condition.

 

 

 

 

 

Generator runs good at no-load

1.

Short circuit in a connected load.

1.

Disconnect shorted electrical load.

 

 

 

 

but "bogs" down" when loads are

2.

Generator is overloaded.

2.

See "Don't Overload Generator".

connected.

3.

Shorted generator circuit.

3.

Contact Authorized service facility.

 

 

 

 

Generator will not start; or starts

Low oil level.

Fill crankcase to proper level or place

and runs rough.

 

 

generator on level surface.

 

 

 

 

 

Generator shuts down during

1.

Out of gasoline.

1.

Fill fuel tank.

2.

Low oil level.

2.

Fill crankcase to proper level or

operation.

 

 

 

place generator on level surface.

 

 

 

 

 

 

 

Generator lacks power.

Load is too high.

See "Don't Overload Generator".

 

 

 

 

 

15

Image 15
Contents 030208 3500W Table of Contents Safety RulesEquipment Description When Transporting or Repairing Equipment When Adding or Draining FuelWhen Starting Equipment When Operating EquipmentWhen Testing for Engine Spark When Adjusting or Making Repairs to Your GeneratorKnow Your Generator Remove Generator From Carton AssemblyInstall Wheel KIT Carton ContentsAdd Engine Oil When Adding FuelInstall fuel cap and wipe up any spilled fuel Before Starting EngineGenerator Location Using the GeneratorConnecting to a Building’s Electrical System System GroundDo not Overload the GENERATOR. See Don’t Overload Generator Connecting Electrical LoadsOperating Generator Starting the Engine120/240 Volt AC, 20 Amp, Locking Receptacle ReceptaclesCold Weather Operation Stopping the EnginePermanent Cold Weather Shelter Remove shelter when temperatures are above 40F 4CExample Power ManagementDont Overload Generator CapacityGenerator Maintenance SpecificationsGeneral Maintenance Recommendations Engine MaintenanceStorage Generator StorageEngine Storage Other Storage Tips Problem Cause Correction Troubleshooting3500W Portable Generator Year Consumer Use Years Years orAdvertencia Conserve Estas Instrucciones Tabla DE ContenidosDescripción DEL Equipo Reglas DE SeguridadCuando Transporte O Repare EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Opere EL EquipoPrecaución Cuando Ajuste O Haga Reparaciones a SU GeneradorCuando Pruebe LA Bujía DEL Motor Tomacorriente con Dispositivo de Seguridad de Conozca SU GeneradorTapa del Depósito del Aceite Llene el motor con aceite Tomacorriente Dobles de 120 Voltios AC, 20 AmpContenido de la Caja MontajeInstale el Juego de Ruedas Para Retirar El Generador De La CajaColoque la generador sobre una superficie nivelada Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Agregue CombustibleConexión al Sistema Eléctrico de un Edificio USO DEL GeneradorTierra del Sistema Ubicación del GeneradorNo Sobrecargue EL GENERADOR.Vea No Sobrecargue Generador Operando EL GeneradorEncienda el Motor Conexion De Cargas ElectricasVoltios AC, 20 Amperios, Receptáculos Dobles Receptáculos PrecauciónOperación Durante UN Clima Frío Parado Del MotorFigura 15 Refugio Frío Permanente del Tiempo Ejemplo No Sobrecargue GeneradorCapacidad Control de la EnergíaMantenimiento del Generador EspecificacionesRecomendaciones Generales DE Mantenimiento Mantenimiento del MotorOtras Sugerencias Para el Almacenando AlmacenamientoAlmacenando el Generador Almacenando el MotorDiagnositicos DE Averías Problemo Accion CausaGarantía Limitada