Briggs & Stratton 030209-1 Stopping the Engine, Volt AC, 20 Amp, Duplex Receptacles

Page 10

5500W Portable Generator

Stopping the Engine

1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to instructions given in the engine operator’s manual.

4.Move fuel valve to “Off” position.

RECEPTACLES

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 5).You can use the same 4–wire cord if you plan to run a 120 Volt load.

Figure 5 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 5,500 watts of power (5.5 kW) at 22.9 Amps for 240 Volts or two independent 120 Volt loads at 20 Amps each.The outlet is protected by push–to–reset circuit breakers.

120 Volt AC, 20 Amp, Duplex Receptacles

Each duplex receptacle (Figure 6) is protected against overload by a push–to–reset circuit breaker.

Figure 6 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

10

Image 10
Contents 030209-1 5500W Safety Rules Table of ContentsEquipment Description When Operating Equipment When Adding or Draining FuelWhen Starting Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Install Wheel Kit AssemblyCarton Contents Refer to and install the wheel kit as followsAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelSystem Ground Using the GeneratorConnecting to a Building’s Electrical System Generator LocationStarting the Engine Connecting Electrical LoadsOperating Generator Do not Overload the GENERATOR. See Don’t Overload Generator120/240 Volt AC, 30 Amp, Locking Receptacle ReceptaclesStopping the Engine Volt AC, 20 Amp, Duplex ReceptaclesCapacity Power ManagementDont Overload Generator ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Generator MaintenanceEngine Storage StorageGenerator Storage Other Storage TipsTroubleshooting Problem Cause CorrectionLimited Warranty Reglas DE Seguridad Tabla DE ContenidosDescripción DEL Equipo AdvertenciaCuando Opere EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Transporte O Repare EL EquipoCuando Ajuste O Haga Reparaciones a SU Generador PrecauciónCuando Pruebe LA Bujía DEL Motor Conozca SU Generador Tapa del Depósito del Aceite Llene el motor con aceiteInstale el Juego de Ruedas MontajeDesembalaje del Generador Contenido de la CajaAgregar Aceite al Motor Antes DE Darle Arranque AL MotorAgregue Combustible Cuando Añada CombustibleConexión al Sistema Eléctrico de un Edificio USO DEL GeneradorTierra del Sistema Ubicación del GeneradorConexion De Cargas Electricas Operando EL GeneradorEncienda el Motor No Sobrecargue EL GENERADOR.Vea No Sobrecargue Generador120/240 Voltios AC, 30 Amp, Receptáculo de Seguridad Receptáculos PrecauciónParado Del Motor Volt AC, 20 Amp, Receptáculos DoblesControl de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Para Limpiar el GeneradorAlmacenando el Generador Diagnositicos DE AveríasAlmacenamiento Almacenando el MotorGarantía Limitada