Baldor MN2410 manual Receptacle Connections, Frame Ground Connection

Page 15

Electrical Connections Continued

Table 3-1 Single Phase Power Receptacle Description

Model

 

Electrical Connection Information (Receptacle Provided at Panel)

 

 

 

 

 

 

 

 

Straight 120VAC

Twist Lock 120VAC

Twist Lock 120/240VAC

Twist Lock 120/240VAC

Rated Watts/

 

(20Amp)

(30Amp)

(30Amp)

(50Amp)

(Full load Amps 120/240)

 

 

 

 

 

 

K3000

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

 

 

2500 / (20.8)

K5000

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

4500 / (37.5/18.7)

K5000E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

4500 / (37.5/18.7)

K6500

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

6000 / (50.0/25.0)

K6500E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

6000 / (50.0/25.0)

R30

4- 5-20R GFCI 120VAC

 

 

 

2500 / (20.8)

R45/R45E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

4000 / (33.3/16.7)

R60/R60E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

5000 / (41.6/20.8)

OHV30

4- 5-20R GFCI 120VAC

 

 

 

2500 / (20.8)

OHV50H

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

4000 / (33.3/16.7)

OHV60/OHV60E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

5000 / (41.6/20.8)

OHV85E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

 

10000 / (83.3/41.6)

OHV100E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

1- CS6369 120/240VAC

8000 / (66.7/33.4)

OHV110E

4- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

1- CS6369 120/240VAC

9500 / (79.2/39.6)

Note: GFCI is Ground Fault Protected power.

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3-2 Receptacle Connections

 

W

 

(GOLD)

 

 

(GOLD)

 

(SILVER)

 

 

 

 

G

X

 

 

X

 

 

 

 

 

 

 

 

 

X

 

 

NEMA

 

NEMA

CS6369

 

L5-30R

 

L14-30R

125/250V

 

125V

125/250V

Y

50A

W

 

30A

 

30A

 

G

X

Y

W

(GOLD)

 

W

NEMA 5-20R

(GOLD)

(GOLD)

(SILVER)

Y

 

(SILVER)

125V 20A

 

 

 

 

 

 

Frame Ground Connection

WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be connected to an approved earth ground. Local codes may also require proper grounding of generator systems.

The NEC requires that the frame and exposed metal surfaces be at local ground reference potential to avoid electrical shock hazard. A local ground reference may require a driven earth ground conductor at the generator installation site. Make the ground connection as shown in Figure 3-3. Use the appropriate size wire (normally 6 AWG) as required by NEC and local codes. The local reference ground is normally a copper clad earth ground rod driven into the earth at least 8 feet.

WARNING: Do not connect the generator output neutral to the frame or local ground. The generator output is isolated from ground. NEC and local codes require that the generator output remain isolated from local ground reference.

MN2410

Receiving & Installation 3-3

Image 15
Contents Premier POW’R Products Generator California Proposition 65 Warning Table of Contents Appendix C Appendix DAppendix E Read This Manual Thoroughly Section Product Safety InformationPrecaution Statements Used In This Manual PropertyOperation Operation Warning Statements Burn Installation Maintenance Product Safety Information MN2410 Section General Information Limited WarrantyOwner’s Responsibilities Premier Generators Storage Section Receiving & InstallationPhysical Location Frame Ground Connection Receptacle ConnectionsEngine Oil Use of Electric Motor Loads Battery ConnectionsSeries K Recommended Engine Oil and Battery TypeAC Voltmeter Section OperationOperator Control Panel Elapsed TimeStart-Up Procedure Electric Start Stopping ProcedureRecoil Start Section Troubleshooting and Maintenance GeneralEngine Problems and Solutions Troubleshooting GuideService Figure A-1 K3000 Operator Panel Appendix a Premier K SeriesTable A-1 Generator Set Parts List Replacement PartsControl Box Operator Panel Figure A-5 K3000 Wiring Diagram Figure A-6 K5000 Wiring Diagram Figure A-7 K5000E Wiring Diagram Figure A-8 K6500 Wiring Diagram Figure A-9 K6500E Wiring Diagram R30, R45, R45E, R60, R60E Appendix B Premier R SeriesFigure B-3 Alternator Assembly Bearing included with rotor Figure B-5 R30 Wiring Diagram Figure B-6 R45/45E Wiring Diagram Figure B-7 R60 Wiring Diagram Figure B-8 R60E Wiring Diagram Premier R Series MN2410 Figure C-1 OHV30 Operator Panel Appendix C Premier OHV SeriesTable C-1 Generator Set Parts List Figure C-4 Alternator AssemblyOHV30 Figure C-6 OHV30 Wiring Diagram Figure C-7 OHV40 / OHV50 / OHV60 Wiring Diagram Figure C-8 OHV60E Wiring Diagram Figure C-9 OHV 85E Wiring Diagram Premier OHV Series MN2410 Figure D-1 OHV100E Operator Panel Appendix D Premier OHV100E SeriesFigure D-2 Alternator Assembly Table D-1 Generator Set Parts List Figure D-4 OHV100E Wiring Diagram Figure D-5 OHV100E Generator Output Wiring Diagram Figure D-6 OHV100E DC Wiring Diagram Figure E-1 OHV110E Operator Panel Appendix E Premier OHV110E SeriesFigure E-2 Alternator Assembly Table E-1 Generator Set Parts List Figure E-4 OHV110E Wiring Diagram Figure E-5 OHV100E Generator Output Wiring Diagram Figure E-6 OHV110E DC Wiring Diagram Baldor District Offices Baldor Generators