BECKETT CLEANCUT INSTALLATION INFORMATION

SINGLE STAGE FUEL UNIT

Part No. 21844

GENERATION INFORMATION - ALL SYSTEMS

IMPORTANT INFORMATION Long or oversized inlet lines may require the pump to operate dry during initial bleeding period. In such cases, the priming may be assisted by injecting fuel oil in the pump gearset. Under lift conditions, lines and fittings must be air tight. To assure this, oil-resistant pipe joint compound may be applied to both the used and unused inlet and both return fittings.

! WARNING Professionalquired Service Re-

Incorrect installation, adjustment, or mis- use of this burner could result in severe personal injury, death, or substantial prop- erty damage from fire, carbon monoxide poisoning, soot or explosion.

Please read and understand the manual supplied with this equip- ment. This equipment must be installed, adjusted and put into operation only by a qualified individual or service agency that is:

yLicensed or certified to install and provide technical service to oil heating systems.

yExperienced with all applicable codes, standards and ordi- nances.

yResponsible for the correct installation and commission of this equipment.

ySkilled in the adjustment of oil burners using combustion test instruments.

The installation must strictly comply with all applicable codes, authorities having jurisdiction and the latest revision of the Na- tional Fire Protection Association Standard for the installation of Oil-burning Equipment, NFPA 31 (or CSA-B139 and CSA-B140 in Canada).

Regulation by these authorities take precedence over the general instructions provided in this installation manual.

!WARNING Oil Leak & Fire Hazard

yThe inlet and return line pressures must not exceed 3 psig, or pump seal damage and oil leaks could result! See NFPA 31-25, 8.6.3.

yDo not use a check valve in the inlet line of a 1-pipe system (with or w/o a boost pump), or in the return line of a 2-pipe system.

yNFPA 31-25, 8.5 states that ‘A return line from a burner or pump to a supply line shall have no valves or obstructions and shall enter the top of the same tank.’

yCheck valve flow restriction in a return line can elevate pressures and damage the fuel unit seals.

yDangerous thermal expansion of oil trapped by an inlet line check valve can create extreme pressures that damage fuel unit seals, line fittings, inlet filters, gauges and other components. A properly installed vacuum safety valve, such as Suntec PRV-38, having accumulator effect and pressure relief to tank is acceptable in the inlet line.

yDo not use teflon tape or compression fittings.

2-STAGE FUEL UNIT Part No. 21941

 

This pump must be used with

! CAUTION

 

a controlling device that pro-

 

vides a valve on delay (pre-purge).

Beckett

INLET

USE ONLY WITH

VALVE ON DELAY

A2EA-6520

4 GPH 100-150 PSI 3450 RPM

NO. 2 & LIGHTER FUEL

3 GPH 150-200 PSI 3450 RPM

NO. 2 FUEL

INLET

BY-PASS

Made by Suntec

Exclusively for Beckett

FigureFIGURE1 1

MOUNTING POSITION Beckett CleanCut fuel unit may be mounted in any position (except upside-down during single pipe installation).

VACUUM CHECK A Vacuum Gauge may be installed in either of the 1/4” NPT inlet ports. The Beckett CleanCut pump should be used where the vacuum does not exceed 6” hg. single pipe and 12” hg. two pipe. The Beckett CleanCut XL pump should be used where the vacuum is less than 17” hg. Remember, running vacuum is the total of all pressure drops (eP) in the system from tank to inlet of pump.

PRESSURE CHECK When a pressure check is made use either the BLEED PORT OR NOZZLE PORT.

CUTOFF CHECK To check cutoff pressure, dead head a pres- sure gauge in nozzle port. Run burner for short period of time. Shut burner off. The pressure will drop and hold above zero.

MOUNTING PUMP (If the shutter screw interferes with the solenoid on the fuel unit)

To install a CleanCut fuel unit on chassis with existing shutter tab see Figure 2 and follow these steps:

Remove existing fuel unit and solenoid valves, if applicable, and appropriately dispose of them.

Note the air setting of the shutter, then remove the air shutter, set the shutter aside to be reinstalled.

DO NOT INSTALL

THE TOP SHUTTER

SCREW IF IT INTER-

FERES WITH THEO O

SOLENOID ON THE

FUEL UNIT.

LOWER SHUT-

TER SCREW

R.W. BECKETT CORPORATION