Siemens 200 P838 Auto False-Echo Suppression Distance, P839 TVT Hover Level, Set Up

Page 221

P838 Auto False-Echo Suppression Distance

Defines the range of Auto False-Echo Suppression (P837) to use for ignoring false echoes. (Units are defined in P005.)

Values

Range

Maximum range:

(depends on model)

0.000 to 15 m (50 ft)

 

Default

1.000 m (3.28 ft)

 

 

 

Determine the actual distance from the transducer face to the material surface. Subtract 0.5 m from this distance, and enter the result.

Set Up:

1.Perform this function when the vessel is empty or nearly empty.

2.Determine actual distance from transducer face to material level.

3.Select P838 and key in [distance to material level minus 0.5 m].

4.Press ENTER .

5.Select P837.

6.Press 2 and then press ENTER . P837 will revert to 1 (use Learned TVT) automatically after a few seconds.

Display after Auto False Echo Suppression

 

 

 

TVT curve

 

 

 

material

(learned)

 

 

level

 

 

 

 

 

 

(db)

 

Level

false

echo

 

 

 

Distance (meters)

P839 TVT Hover Level

Defines (in percent) how high the TVT curve is placed above the profile, relative to the largest echo. When MultiRanger 100/200 is located in the center of the vessel, lower this parameter to prevent multiple echo detections.

Values

Range

0 to 100%

 

 

Default

33 (%)

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 211

Parameters

Image 221
Contents Multiranger This document is available in bound version Technical data subject to changeManual for agreement with Instrumentation described, variationsTable of Contents Dolphin Plus Toolbar Buttons Starting Pumps by Rate of Level Change MR IiiSet Relays to First in First OUT Fifo Assist MR Open Channel Monitoring OCM 100 Communication Appendix a Single Parameter Access SPA Vii Viii Connecting a transducer with RG62 coaxial extension cableSet the MultiRanger to Ignore the Bad Echo Coaxial Transducer ExtentionManual MultiRanger 100MultiRanger MultiRanger 100/200Configuration Examples Manual SymbolsPower SpecificationsSpecifications MountingTemperature Compensation ResolutionTemperature Error AccuracyOutputs Inputs WeightEnclosure ApprovalsMaximum CableMounting InstallationMounting Locations RecommendedMounting Instructions Enclosure DimensionsWall Mount Mounting the EnclosureCable exposed and entering through the cable glands Cable routed through a conduitUnscrew the glands and attach them loosely to the enclosure Tighten the glands to form a good sealCutout Instructions Cutout DimensionsPanel Mount Helpful hint Panel Mount DimensionsMounting the Enclosure MultiRanger Board Installing the BatteryOpen the enclosure lid Close and secure enclosure lidInstalling SmartLinx Card MultiRanger WiringWiring Cables Terminal BoardPlease do not overtighten the screws Connection Cable TypeTransducers Power FailureRelays Relay RatingsMA Input MR 200 only Temperature SensorMA Output Sensor only. LeaveLevel System Synchronization PowerRS-485 Serial Connection Digital CommunicationsRS-232 Serial Connection Discrete Inputs RUN Mode RUN ModeOperating the MultiRanger OperationIcons indicating index type Item 1 edited in Program mode Readings in RUN ModeIcon Index Type Operation KeyValues Status ParametersControlling the Display Adjusting the primary reading for four-digit LCD readoutAuxiliary Reading ActionMultiple Readings MR 200 only Setting the Default Auxiliary ReadingParameter Index Value Description Changing Number Scrolling SpeedStarting Program Mode Program ModeHand Programmer To activate Program from RUN mode, press Program and thenDigit Totalizer toggle MR 200 only Operation Keys Programming ModeProgrammer Keys Compatible with product software versions 1.06 and earlier1 Dolphin PlusButton Action Dolphin Plus Toolbar ButtonsDevice Description Simatic Process Device Manager PDMCompatible with product software versions 1.07 and later1 See P900 for Software Revision Number 7ML19981FB06Helpful Hints Activating the MultiRangerChanging Parameters Security Using Units or Percent %Parameters Types MaximumDefault Values Parameter ResetMaster Reset P999 Display ReadoutChanging ParametersDolphin Plus Parameter Indexing Accessing a Parameter IndexMultiRanger Display Index NumberExample Setting P1113 = Accessing a Secondary IndexPrimary and Secondary Indexes Primary IndexSingle Point Models Starting MeasurementExample MR 200 only ParameterAverage or Differential MR 200 only Dual Point ModelsOperation Index Description Index Value DescriptionMeasurement Conditions Dimensions MR 200 onlyResponse Rate FailsafeRelays AlarmGeneral Introduction Relay FunctionMiscellaneous PumpRelay Related Parameters Relay StatesRelay Status Non Run Modes Relay TypesRelay Activation Relay Wiring TestRelay Logic is Modified Relay FailsafeHOLd Keeps the relay in the current state Energizes the relayValue Parameters Affected Preset ApplicationsBackup Level Override Backup Level OverrideBackup Level Override Parameters Programming the Discrete Input Logic Wiring the Discrete InputsDiscrete Inputs MA Input MR MA I/OLevel Reading Parameters MA I/OCalibrating 4 mA Output MA LI/OCalibrating 20 mA Output Verifying the mA RangeTank Shape and Dimensions Volume MRVolume ReadingsExample Chart Characterization Chart MRP051 Level P054Determines the volumes which Which the volumes are knownMultiRanger 200 only All level readingsAlarms AlarmsLevel Set the Common ParametersAlarm Designation Setting Simple Level AlarmsSetting a Filling Rate Alarm Rate MRTemperature MR Cable FaultBounds/ Out of Bounds Range MR Parameter Index ValueLoss of Echo LOE This shows a high alarmSetting a group of three pumps to pump down a wet well Setting a Pump Down GroupPump Control Example Sewage Wet WellSet the on Setpoints Setting a Pump Up Reservoir GroupSet Relays to Alternate Duty Assist Set the Relay OFF Setpoints 3m By using index 0 all six relays are set atSample values 4m Sets the three setpoints for the pump relaysSet Relays to Fixed Duty Assist Other Pump Control AlgorithmsSet the Relay on Setpoints MR Set the Relay OFF Setpoints MRSet Relays to Alternate Duty Service MR Set Relays to Fixed Duty Backup MRFixed Duty BACKUP. Only one pump will Ever run at one timeStarting Pumps by Rate of Level Change MR Optional Pump ControlsPump Control Parameter P112 P113 P121 P132Time Rotating Pumps by Service Ratio MRSingle and Dual Point MR Set in RUN Mode Totalizing Pumped Volume MRSetting Independent Failsafe Controls Reducing Wall Cling MR Setting a Pump to Run On MRSetting the Pump Start Delays MR Grouping Pumps MR Setting a Flush Valve MRGroups Pumps One and Two Groups Pumps Three and FourRelay Controlled by Communications Information Available Parameter AccessTracking Pump Usage Point Three Level Distance = h1 -h2 Setting a Rake ControlRake Screen Control MR Set Relays 2 to 4 Level Alarms Setting the Common ParametersSet Relay 1 Operate Rake Screen ControlRelay Contacts External Totalizers and Flow Samplers MRTotalizer Counter FormulaFlow Sampler Based on Volume and TimeSource of units depends on the operation Operation Units Source ParameterOpen Channel Monitoring OCM MR Dimensional P600 = 2,3,6,7Common Parameters Exponential P600 =Channel Monitoring Setting Zero HeadExamples on the following pages show both methods P603 P006 P007 P605BS-3680 / ISO 1438/1 Thin plate V notch weir Setting Totalized VolumeApplications Supported by MultiRanger Plan View 4 to 5 x hmax hmax = P007 BS-3680 / ISO 4359 Rectangular FlumeP600 P602 P605 P608Application Information Palmer Bowlus FlumeFlume Size Diameter in feet Point of Measurement Cminches FlumeFlume Flume height DStandard Weirs Applicable Weir ProfilesP600 Exponential Function P601 Weir ProfileParshall Flume Non-Applicable Weir ProfilesSized by throat width Set on solid foundation Transducer P006Leopold Lagco Flume Maximum Head preset P007Leopold Lagco Flume Cut Throat Flume Cut Throat FlumeTypical Flow Characterization Universal Calculation SupportP611 Linear Flow Curved Head P610 Zero FlowExample Weirs Example FlumesTrapezoidal Dual Range nested Parshall These weirs could require universal calculationTesting the Configuration Testing the ConfigurationSimulation Simulating a Single MeasurementChecking OCM Flow Characterization MR Checking Volume Characterization MRPress No effectApplication Test CheckoutTesting the Configuration MultiRanger Communication Systems MultiRanger CommunicationsOptional SmartLinxCards CommunicationsCommunication Ports Communication SystemsModbus Port Connection Location InterfaceP770 Modbus RTU slave P771 SmartLinxP770 Dolphin P772 Data rate of 115.2 Kilo baudWiring Guidelines Communications InstallationComms Installation Ports 1Port 1 RS-232 RJ-11 Jack To connect the unit to a modem using an RS-232 jackPort 2 RS-485 Computer DB-9 male RJ-11 to DB 9 converterTo connect the unit to a modem using an RS-485 port Configuring Communication Ports ParametersP770 Port Protocol P771 Network AddressP773 Parity P772 Baud RateP774 Data Bits P775 Stop BitsP778 Modem Available P779 Modem Inactivity TimeoutP782 Parameter Index Location Hanging UpRegister Map for Most Common Data Modbus Register MapType Description Start Data Type Read Modbus Register TypesModbus Register Types Description Start Word Order R40,062Map ID R40,063 Point Data R41,010 R41,031 Product ID R40,064Totalizer R41,040 R41,043 Input/Output R41,070 R41,143Relay Outputs R41,080 Discrete Inputs R41,070MA Input R41,090 MR MA Output R41,110-41,111Pump OFF Setpoint R41,430 R41,435 Pumped Volume R41,440 R41,443 MRPump Hours R41,450 R41,461 Pump Starts R41,470 R41,475Indexing the Parameter Access Area Parameter Access R43,998 R46,999Format Register # Parameter # Usually, the parameters are all read / writeGlobal Index Method P782 = Reading ParametersParameter Specific Index Method P782 = Examples areWriting Parameters Global Index Method P782 = Format Words R46,000 to R46,999Parameter-Specific Index Method P782 = Format RegistersDecimal Decimal Offset ExampleFormat Numeric Values Data TypesBit Values Unsigned Double Precision Integer UINT32Split Values Yy = value % 256 128 where % is the modulus operatorOne example is P807, Transducer Noise, where Two registers are read as a 32-bit integerNumber Text Message as displayed on LCD Text MessagesControl Relay Function Code Number P111 Relay Function Codes P111 OnlyMultiRanger Error Handling Error HandlingError Handling Modbus ResponsesError Handling Specifically Communication TroubleshootingGenerally Reading Parameters MappingCommunication Appendix a Address DescriptionBits Values Description Writing ParametersFormat Register Currently the MultiRanger has two error codes available Error CodesMultiRanger 100 and MultiRanger Parameter ReferenceHelpful Hints Parameters# of indexes Index typesTransducer2 Up to 7 2P000 Lock Quick Start P001 to P007P001 Operation Single Point Model Dual Point ModelFor DPD and DPA Programming MR P002 MaterialSingle Point Model Use Dual Point Model UseDetermines level change reaction P003 Maximum Process SpeedP004 Transducer P006 Empty Specifies measurement units used for dimensional valuesP005 Units Sets the range levels to be measured Volume P050 to P055 MRP007 Span Preset Flat Level Bottom Volume calculation not requiredP050 Tank Shape MR Parabola BottomExamples P051 Maximum Volume MRP053 Tank Dimension L MR P052 Tank Dimension a MRP054 Level Breakpoints Universal Volume Calculation MR Entering a Level BreakpointEntering a Volume Breakpoint Typical volume calculationsDisplay and Reading P060 to P062 P060 Decimal PositionP062 Offset Reading P061 Convert Reading MRP607 Flowrate Decimal Range -999 toP065 Reading Override Value Backup Level OverrideP064 Reading Override Enable P069 Password P066 Override Time DelayMaterial level reported when a Failsafe State is initiated P070 Failsafe TimerFailsafe P070 to P072 P071 Failsafe Material LevelP072 Failsafe Level Advance Relays P100 to P119Six preset applications to configure or bench test the unit P100 Preset Applications MRControl Functions P111 Setpoints P112, P113Dual Point Mode optional Single Point Mode standardP110 Level Source P111 Relay Control FunctionValues For P111 Control Type Relay Control P112 Relay on Setpoint P113 Relay OFF Setpoint Distance above and below the bound alarm setpointsP115 Relay Interval Setpoint MR P116 Dead Band MRPower Failure Value Logic AlarmP118 Relay Output Logic Relay StatesP119 Relay Logic Test P118 is preset to 2 which is positive logicP121 Pump by Rate MR Positive LogicIndependent Relay Failsafe P129 P122 Pump Service Ratio MRP129 Relay Failsafe This parameter only relates to relays with P111 = 54 orAdvanced Pump Control Modifiers P130 to P137 MR Relay Function P111 Preset P129P130 Pump Run-On Interval MR To select an independent Relay Failsafe valueP133 Pump Power Resumption Delay MR P132 Pump Start Delay MRSets the minimum delay in seconds between pump starts P131 Pump Run-On Duration MRP137 Pump Group MR P136 Wall Cling Reduction MRDual Point Mode Single Point ModeFlush Systems P170 to P173 MR P170 Flush Pump MRP172 Flush Interval MR P171 Flush Cycles MRP173 Flush Duration MR Sets the number of pump cycles requiring flush controlP200 mA Output Range MA Output P200 to P219P201 mA Output Function Determines the mA output rangeP202 mA Output Allocation Displays current mA output value for the Point Number P203 mA Output Value / TransducerIndependent mA Setpoints P210 and P211 P201-mA Function Action SettingsMA Output Limits P212 and P213 P210 0/4 mA Output SetpointP212 mA Output Min Limit MA Output Trim P214 to P215P213 mA Output Max Limit P214 4 mA Output TrimMA Input P250 to P260 MR MA Output Failsafe P219 MRP215 20 mA Output Trim P219 mA Output Failsafe MRP251 0 or 4 mA Input Level MR P250 mA Input Range MRP252 20 mA Input Level MR Shows the mA input range of the connected mA deviceP253 Input Filter Time Constant MR Discrete Input Functions P270 to P275P254 Scaled mA Input Value MR P260 mA Raw Input MRStandard Data Logging P300 to P321 Record Temperatures P300 to P303P270 Discrete Input Function P275 Scaled Discrete Input ValueP302 Temperature, Sensor Maximum P300 Temperature, Transducer MaximumP301 Temperature, Transducer Minimum Record Readings P304 and P305 P303 Temperature, Sensor MinimumPump Records P309 to P312 P304 Reading MaxP310 Pump Hours P309 Pump RUN TimeP311 Pump Starts P312 Pump Run Ons MRLCD Totalizer P322 and P323 MR Flow Records P320 and P321 MRP320 Flow Max MR P321 Flow Min MRP323 LCD Total High MR Profile Records P330 to P337P322 LCD Total Low MR Code Description P330 Profile RecordUse to enable/disable the Auto Profile Record function P331 Auto Record EnableP332 Auto Record Transducer P333 Auto Record IntervalP335 Auto Record OFF Setpoint Auto Record on and OFF Setpoints P334 to P337P334 Auto Record on Setpoint P337 Auto Record LOE Time P336 Auto Record Filling / EmptyingP340 Date of Manufacture Installation Records P340 to P342P341 RUN Time P342 Start UpsP600 Primary Measuring Device MR Open Channel Monitoring P600 to P621 MRSingle Point Model Dual Type of primary measuring device PMD usedExponent for the flow calculation formula P601 Flow Exponent MRWord on Exponents PMD Type Exponent sample only Dimensions of the Primary Measuring Device PMDExample Exponents P604 Maximum Flow MR P603 Maximum Head MRLevel value associated with Maximum Flow, in Units P005 Maximum flowrate associated with Maximum Head P603Conditions Enter P605 Zero Head MRMaximum number of decimal places to be displayed P606 Time Units MRP607 Flowrate Decimal MR P608 Flowrate Units MR Volume units used to display total flowCubic metres / hour Cubic metres / day Cubic feet / second Million gallons / day ImperialP611 Breakpoint Flowrates MR P610 Head Breakpoints MRHead vs. Flowrate P610 and P611 Flowrate corresponding to each Head Breakpoint enteredP620 Low Flow Cutoff MR Procedure, with head steadyP621 Auto Zero Head MR Calibrates Zero Head P605 based on actual head measurementsOr discharge Pumped Volume Totalizer P622 MRP622 Inflow / Discharge Adjust MR P630 LCD Totalized Multiplier MR Totalizer features apply to MultiRanger 200 onlyTotalizer P630 to P645 MR P640 Remote Totalized Multiplier MR P633 LCD Totalized Decimal Position MREnter the maximum number of decimal places to be displayed 100 1000Enter the mantissa Y for the exponent Z in the formula P641 Flow Sampler Mantissa MRP642 Flow Sampler Exponent MR Range Calibration P650 to P654 Offset Adjusts the measurements by a fixed amountP645 Relay Duration MR Enter the exponent Z for the mantissa Y in the formulaP650 Offset Calibration Condition for use of this featureP651 Sound Velocity Calibration Offset CalibrationValue altered when an Offset Calibration is performed Using Sound Velocity CalibrationP652 Offset Correction P653 VelocityP660 Temp Source Temperature Compensation P660 to P664P654 Velocity at 20C Range -199 to 199 preset = 20 C P663 Temperature Transducer AllocationP661 Temp Fixed P660 Temp SourceView the transducer temperature in C P664 TemperatureRate P700 to P708 P700 Max Fill RateFill rate required to activate the LCD Filling indicator P702 Filling IndicatorP701 Max Empty Rate P003 Value Meters / MinuteEmpty rate required to activate the LCD Emptying indicator P703 Emptying IndicatorP704 Rate Filter Damps Rate Value P707 fluctuationsP706 Rate Update Distance P705 Rate Update TimeP707 Rate Value P005 Units P007 SpanPress Reading to toggle between percent and volume P708 Volume Rate Display MRMeasurement Verification P710 to P713 P710 Fuzz FilterP713 Echo Lock Window P820 Algorithm P711 Echo LockGlobal Transducer Off Adjusts the size of the Echo Lock Window P711 value P712 preset valueP712 Echo Lock Sampling P713 Echo Lock WindowEnables the System Sync on the terminal block P727 Scan DelayTransducer Scanning P726 to P729 P726 Level System SyncDisplay P730 to P739 P728 Shot DelayP729 Scan Time P730 Auxiliary ReadingP733 Scroll Access P732 Display DelayAdjusts the Point Number display scroll speed P731 Auxiliary Reading KeyP735 Backlight P741 Communications TimeoutP737 Primary Reading MR Controls the LCD backlightingCommunications P770 to P782 SmartLinx Reserved P750 to P769P770 Port Protocol P771 Network AddressP774 Data Bits P772 Baud RateP773 Parity P778 Modem Available P779 Modem Inactivity TimeoutP775 Stop Bits P790 Hardware Error SmartLinx Hardware Testing P790 to P795P782 Parameter Index Location GlobalP794 SmartLinx Module Type P795 SmartLinx Protocol P791 Hardware Error CodeP792 Hardware Error Count P799 Communications Control Echo Processing P800 to P807P800 Near Blanking Space near the transducer face which cannot be measuredP802 Transducer with Submergence Shield P801 Range ExtensionP804 Confidence Threshold P803 Shot / Pulse ModeDetermines what type of ultrasonic shots are fired Determines which echoes are evaluated by softwareP806 Echo Strength P805 Echo ConfidenceP807 Noise Display DescriptionP815 Echo Time Filtered Advanced Echo Processing P815 to P825P816 Echo Time Raw Time in ms from the transmit pulse to the processed echoP820 Algorithm P822 Narrow Echo Filter P821 Spike FilterDampens spikes in the echo profile to reduce false readings Filters out echoes of a specific widthSmoothes jagged peaks in the echo profile P823 Reform EchoP825 Echo Marker Trigger P830 TVT Type Advanced TVT Adjustment P830 to P835P831 TVT Shaper Selects the TVT Curve usedP833 TVT Start Min P832 TVT Shaper AdjustP833 TVT Start Min P835 TVT Slope Min P834 TVT Start DurationP835 TVT Slope Min Values Display before Auto False Echo Suppression Or when P837 =P837 Auto False-Echo Suppression P838 Auto False-Echo Suppression Distance Set UpP839 TVT Hover Level Display after Auto False Echo SuppressionP841 Long Shot Number Advanced Shot Adjustment P840 to P852P840 Short Shot Number P844 Short Shot Width P842 Short Shot FrequencyP843 Long Shot Frequency Range 30 to Preset P840 Short Shot Number Adjust the width in ms of the long shot transmit pulseP845 Long Shot Width P850 Short Shot BiasP852 Short Shot Range Test P900 to P913P900 Software Revision Number P901 MemoryP903 Display P902 WatchdogP904 Keypad P905 Transmit PulseP908 Scanner P912 Transducer TemperatureP910 Toggle Relays P911 mA Output ValueTo Access in RUN Mode P913 Sensor TemperatureMeasurement P920 to P927 P914 mA Input MRP922 Space Measurement P921 Material MeasurementP923 Distance Measurement P001 P050 = P050 ≠P925 Flow Measurement MR P924 Volume Measurement MRP926 Head Measurement MR Calculated flowrate in Max Flow P604 units or % of Max FlowThis feature resets all parameters to original values Master Reset P999P927 Distance Measurement Pressing the Clear keys 7ML19981FB06Parameters Parameter depen Dent up to 7 2 Or 3 Appendix a Index TypesGlobal View only Breakpoint Echo Processing Transmit PulseDolphin Plus Display CursorAuto False-Echo Suppression TVT Time Varying Threshold curvesSound Velocity Distance CalculationScanning Volume Calculation MRMultiRanger 100/200 Universal, Linear P050 =Set P050 = Flow CalculationUniversal, Curved MR See also Typical Flow Characterization on Universal, Linear MRParameter Units Maximum Process SpeedValues Dependent on Maximum Process FastSymptom Cause Action Appendix C TroubleshootingCommon Problems Chart Determine the Noise Source Noise ProblemsRemoved + removed Go to Acoustical NoiseNon-Transducer Noise Sources Common Wiring ProblemsReducing Electrical Noise Reducing Acoustical NoiseFlashing LOE Display Adjust Transducer AimingMeasurement Difficulties Nozzle Mountings Fixed ReadingObstructions in the Sound Beam Wrong Reading Adjust the Echo AlgorithmSet the MultiRanger to Ignore the Bad Echo Types of Wrong ReadingsNormal Ring Down Transducer RingingPoor Ring Down Ring Down TVT curveUnit Repair and Excluded Liability Pump Control Algorithms Pump Control OptionsPump Groups Pump by Rate MRFixed Duty Assist P111 = Fixed Duty Backup P111 = 51 MRAlternate Duty Assist P111 = Alternate Duty Backup P111 = 53 MRIndex Relays Cycle RelaysRelay Operation for P118 = 2 MR Service Ratio Duty Assist P111 = 54 MROther Pump Controls MR Service Ratio Duty Backup P111 = 55 MRFirst In First Out Fifo P111 = 56 MR Pump by Rate P121 MRFlush Device P170 to P173 Updating Software Appendix E Updating SoftwareAppendix F Upgrading Connecting the TransducerMounting a MultiRanger 100/200 Coaxial Transducer ExtentionExisting installation Connecting a transducer with RG62 coaxial extension cableMultiRanger Plus AlarmRelay Parameter Value On setpoint7ML19981FBO6 Appendix G Conduit Entry for Class 1, Div 2 ApplicationsAppendix G 23650314 Changes MultiRangerSoft Soft Ware Date Changes Rev Property no Reset Systems testingSimatic PDM related TVT display Improvement to prevent it from goingImproved Preset Application values Eliminated rogue watchdog resets whenUsing Dolphin+ Changed P132 to globalFrom Modbus map reg OCM Time Units improvementNow being protected from other units’ Transmit pulse DDs required 7ML19981FB06Improved volume calculation for 3rd point Property noResetVolume Reading some floats as decimal shiftedP000 Lock G Programming ChartsParameter Charts P113 Relay OFF Setpoint P115 P121 Pump by Rate MR P122 Pump Service Ratio MRP116 Deadband P118 Relay Output Logic P119 Relay Logic Test P210 0/4 mA Output Setpoint P211 20 mA Output SetpointP304 Reading Max P305 Reading Min P219 mA Output FailsafeMRP320 Flow Max MR P321 Flow Min MR P322 LCD Total Low MR P323 LCD Total High MROpen Channel Monitoring P340 Date of Manufacture P341 RUN Time P342 Start UpsTemperature Compensation SmartLinx Reserved Communications P737 Primary Reading MR P741 Communications TimeoutReserved Parameter Index 105 Parameter access153 103212 203207 162Testing Service ratio110 242Weir Characterization chart167 233Page Page 7ml19981FB06