Contents
Multiranger
Instrumentation described, variations
Technical data subject to change
This document is available in bound version
Manual for agreement with
Table of Contents
Dolphin Plus Toolbar Buttons
Starting Pumps by Rate of Level Change MR
Iii
Set Relays to First in First OUT Fifo Assist MR
Open Channel Monitoring OCM
100
Communication Appendix a Single Parameter Access SPA
Vii
Coaxial Transducer Extention
Connecting a transducer with RG62 coaxial extension cable
Viii
Set the MultiRanger to Ignore the Bad Echo
MultiRanger 100/200
MultiRanger 100
Manual
MultiRanger
Configuration Examples
Manual Symbols
Mounting
Specifications
Power
Specifications
Accuracy
Resolution
Temperature Compensation
Temperature Error
Outputs
Approvals
Weight
Inputs
Enclosure
Maximum
Cable
Recommended
Installation
Mounting
Mounting Locations
Mounting the Enclosure
Enclosure Dimensions
Mounting Instructions
Wall Mount
Tighten the glands to form a good seal
Cable routed through a conduit
Cable exposed and entering through the cable glands
Unscrew the glands and attach them loosely to the enclosure
Cutout Instructions
Cutout Dimensions
Panel Mount
Helpful hint
Panel Mount Dimensions
Mounting the Enclosure
Close and secure enclosure lid
Installing the Battery
MultiRanger Board
Open the enclosure lid
Installing SmartLinx Card
MultiRanger
Wiring
Wiring
Connection Cable Type
Terminal Board
Cables
Please do not overtighten the screws
Relay Ratings
Power Failure
Transducers
Relays
Sensor only. Leave
Temperature Sensor
MA Input MR 200 only
MA Output
Level System Synchronization
Power
RS-485 Serial Connection
Digital Communications
RS-232 Serial Connection
Discrete Inputs
Operation
RUN Mode
RUN Mode
Operating the MultiRanger
Operation Key
Readings in RUN Mode
Icons indicating index type Item 1 edited in Program mode
Icon Index Type
Values
Status Parameters
Action
Adjusting the primary reading for four-digit LCD readout
Controlling the Display
Auxiliary Reading
Changing Number Scrolling Speed
Setting the Default Auxiliary Reading
Multiple Readings MR 200 only
Parameter Index Value Description
To activate Program from RUN mode, press Program and then
Program Mode
Starting Program Mode
Hand Programmer
Digit Totalizer toggle MR 200 only
Operation Keys Programming Mode
Programmer Keys
Compatible with product software versions 1.06 and earlier1
Dolphin Plus
Button Action
Dolphin Plus Toolbar Buttons
See P900 for Software Revision Number 7ML19981FB06
Simatic Process Device Manager PDM
Device Description
Compatible with product software versions 1.07 and later1
Helpful Hints
Activating the MultiRanger
Changing Parameters
Maximum
Using Units or Percent %
Security
Parameters Types
Display Readout
Parameter Reset
Default Values
Master Reset P999
Changing ParametersDolphin Plus
Index Number
Accessing a Parameter Index
Parameter Indexing
MultiRanger Display
Primary Index
Accessing a Secondary Index
Example Setting P1113 =
Primary and Secondary Indexes
Parameter
Starting Measurement
Single Point Models
Example MR 200 only
Index Value Description
Dual Point Models
Average or Differential MR 200 only
Operation Index Description
Failsafe
Dimensions MR 200 only
Measurement Conditions
Response Rate
Relay Function
Alarm
Relays
General Introduction
Miscellaneous
Pump
Relay Types
Relay States
Relay Related Parameters
Relay Status Non Run Modes
Relay Activation
Relay Wiring Test
Energizes the relay
Relay Failsafe
Relay Logic is Modified
HOLd Keeps the relay in the current state
Value Parameters Affected
Preset Applications
Backup Level Override
Backup Level Override
Backup Level Override Parameters
Programming the Discrete Input Logic
Wiring the Discrete Inputs
Discrete Inputs
MA I/O
MA I/O
MA Input MR
Level Reading Parameters
Verifying the mA Range
MA LI/O
Calibrating 4 mA Output
Calibrating 20 mA Output
Readings
Volume MR
Tank Shape and Dimensions
Volume
Level P054
Characterization Chart MR
Example Chart
P051
All level readings
Which the volumes are known
Determines the volumes which
MultiRanger 200 only
Set the Common Parameters
Alarms
Alarms
Level
Rate MR
Setting Simple Level Alarms
Alarm Designation
Setting a Filling Rate Alarm
Parameter Index Value
Cable Fault
Temperature MR
Bounds/ Out of Bounds Range MR
Loss of Echo LOE
This shows a high alarm
Example Sewage Wet Well
Setting a Pump Down Group
Setting a group of three pumps to pump down a wet well
Pump Control
Set the on Setpoints
Setting a Pump Up Reservoir Group
Set Relays to Alternate Duty Assist
4m Sets the three setpoints for the pump relays
3m By using index 0 all six relays are set at
Set the Relay OFF Setpoints
Sample values
Set the Relay OFF Setpoints MR
Other Pump Control Algorithms
Set Relays to Fixed Duty Assist
Set the Relay on Setpoints MR
Ever run at one time
Set Relays to Fixed Duty Backup MR
Set Relays to Alternate Duty Service MR
Fixed Duty BACKUP. Only one pump will
P112 P113 P121 P132
Optional Pump Controls
Starting Pumps by Rate of Level Change MR
Pump Control Parameter
Time
Rotating Pumps by Service Ratio MR
Single and Dual Point MR
Set in RUN Mode
Totalizing Pumped Volume MR
Setting Independent Failsafe Controls
Reducing Wall Cling MR
Setting a Pump to Run On MR
Setting the Pump Start Delays MR
Groups Pumps Three and Four
Setting a Flush Valve MR
Grouping Pumps MR
Groups Pumps One and Two
Relay Controlled by Communications
Information Available Parameter Access
Tracking Pump Usage
Point Three Level Distance = h1 -h2
Setting a Rake Control
Rake Screen Control MR
Screen Control
Setting the Common Parameters
Set Relays 2 to 4 Level Alarms
Set Relay 1 Operate Rake
Counter Formula
External Totalizers and Flow Samplers MR
Relay Contacts
Totalizer
Operation Units Source Parameter
Based on Volume and Time
Flow Sampler
Source of units depends on the operation
Exponential P600 =
Dimensional P600 = 2,3,6,7
Open Channel Monitoring OCM MR
Common Parameters
P603 P006 P007 P605
Setting Zero Head
Channel Monitoring
Examples on the following pages show both methods
BS-3680 / ISO 1438/1 Thin plate V notch weir
Setting Totalized Volume
Applications Supported by MultiRanger
P605 P608
BS-3680 / ISO 4359 Rectangular Flume
Plan View 4 to 5 x hmax hmax = P007
P600 P602
Application Information
Palmer Bowlus Flume
Flume height D
Flume
Flume Size Diameter in feet Point of Measurement Cminches
Flume
Weir Profile
Applicable Weir Profiles
Standard Weirs
P600 Exponential Function P601
Transducer P006
Non-Applicable Weir Profiles
Parshall Flume
Sized by throat width Set on solid foundation
Leopold Lagco Flume
Maximum Head preset P007
Leopold Lagco Flume
Cut Throat Flume
Cut Throat Flume
Zero Flow
Universal Calculation Support
Typical Flow Characterization
P611 Linear Flow Curved Head P610
These weirs could require universal calculation
Example Flumes
Example Weirs
Trapezoidal Dual Range nested Parshall
Simulating a Single Measurement
Testing the Configuration
Testing the Configuration
Simulation
No effect
Checking Volume Characterization MR
Checking OCM Flow Characterization MR
Press
Application Test
Checkout
Testing the Configuration
Communications
MultiRanger Communications
MultiRanger Communication Systems
Optional SmartLinxCards
Port Connection Location Interface
Communication Systems
Communication Ports
Modbus
Data rate of 115.2 Kilo baud
SmartLinx
P770 Modbus RTU slave P771
P770 Dolphin P772
Ports 1
Communications Installation
Wiring Guidelines
Comms Installation
Computer DB-9 male RJ-11 to DB 9 converter
To connect the unit to a modem using an RS-232 jack
Port 1 RS-232 RJ-11 Jack
Port 2 RS-485
P771 Network Address
Configuring Communication Ports Parameters
To connect the unit to a modem using an RS-485 port
P770 Port Protocol
P775 Stop Bits
P772 Baud Rate
P773 Parity
P774 Data Bits
Hanging Up
P779 Modem Inactivity Timeout
P778 Modem Available
P782 Parameter Index Location
Modbus Register Types
Modbus Register Map
Register Map for Most Common Data
Type Description Start Data Type Read
Modbus Register Types Description Start
Word Order R40,062
Map ID R40,063
Input/Output R41,070 R41,143
Product ID R40,064
Point Data R41,010 R41,031
Totalizer R41,040 R41,043
MA Output R41,110-41,111
Discrete Inputs R41,070
Relay Outputs R41,080
MA Input R41,090 MR
Pump Starts R41,470 R41,475
Pumped Volume R41,440 R41,443 MR
Pump OFF Setpoint R41,430 R41,435
Pump Hours R41,450 R41,461
Usually, the parameters are all read / write
Parameter Access R43,998 R46,999
Indexing the Parameter Access Area
Format Register # Parameter #
Examples are
Reading Parameters
Global Index Method P782 =
Parameter Specific Index Method P782 =
Writing Parameters
Format Registers
Format Words R46,000 to R46,999
Global Index Method P782 =
Parameter-Specific Index Method P782 =
Decimal
Decimal Offset Example
Format
Unsigned Double Precision Integer UINT32
Data Types
Numeric Values
Bit Values
Two registers are read as a 32-bit integer
Yy = value % 256 128 where % is the modulus operator
Split Values
One example is P807, Transducer Noise, where
Number Text Message as displayed on LCD
Text Messages
Control Relay Function Code Number P111
Relay Function Codes P111 Only
MultiRanger
Modbus Responses
Error Handling
Error Handling
Error Handling
Error Handling
Specifically
Communication Troubleshooting
Generally
Address Description
Mapping
Reading Parameters
Communication Appendix a
Bits Values Description
Writing Parameters
Format Register
Currently the MultiRanger has two error codes available
Error Codes
Parameters
Parameter Reference
MultiRanger 100 and MultiRanger
Helpful Hints
Up to 7 2
Index types
# of indexes
Transducer2
Single Point Model Dual Point Model
Quick Start P001 to P007
P000 Lock
P001 Operation
Dual Point Model Use
P002 Material
For DPD and DPA Programming MR
Single Point Model Use
Determines level change reaction
P003 Maximum Process Speed
P004 Transducer
P006 Empty
Specifies measurement units used for dimensional values
P005 Units
Sets the range levels to be measured
Volume P050 to P055 MR
P007 Span
Parabola Bottom
Volume calculation not required
Preset Flat Level Bottom
P050 Tank Shape MR
Examples
P051 Maximum Volume MR
Entering a Level Breakpoint
P052 Tank Dimension a MR
P053 Tank Dimension L MR
P054 Level Breakpoints Universal Volume Calculation MR
P060 Decimal Position
Typical volume calculations
Entering a Volume Breakpoint
Display and Reading P060 to P062
Range -999 to
P061 Convert Reading MR
P062 Offset Reading
P607 Flowrate Decimal
P065 Reading Override Value
Backup Level Override
P064 Reading Override Enable
P069 Password
P066 Override Time Delay
P071 Failsafe Material Level
P070 Failsafe Timer
Material level reported when a Failsafe State is initiated
Failsafe P070 to P072
P072 Failsafe Level Advance
Relays P100 to P119
Setpoints P112, P113
P100 Preset Applications MR
Six preset applications to configure or bench test the unit
Control Functions P111
P111 Relay Control Function
Single Point Mode standard
Dual Point Mode optional
P110 Level Source
Values For P111 Control Type Relay Control
P112 Relay on Setpoint
P116 Dead Band MR
Distance above and below the bound alarm setpoints
P113 Relay OFF Setpoint
P115 Relay Interval Setpoint MR
Relay States
Value Logic Alarm
Power Failure
P118 Relay Output Logic
Positive Logic
P118 is preset to 2 which is positive logic
P119 Relay Logic Test
P121 Pump by Rate MR
This parameter only relates to relays with P111 = 54 or
P122 Pump Service Ratio MR
Independent Relay Failsafe P129
P129 Relay Failsafe
To select an independent Relay Failsafe value
Relay Function P111 Preset P129
Advanced Pump Control Modifiers P130 to P137 MR
P130 Pump Run-On Interval MR
P131 Pump Run-On Duration MR
P132 Pump Start Delay MR
P133 Pump Power Resumption Delay MR
Sets the minimum delay in seconds between pump starts
P137 Pump Group MR
P136 Wall Cling Reduction MR
P170 Flush Pump MR
Single Point Mode
Dual Point Mode
Flush Systems P170 to P173 MR
Sets the number of pump cycles requiring flush control
P171 Flush Cycles MR
P172 Flush Interval MR
P173 Flush Duration MR
Determines the mA output range
MA Output P200 to P219
P200 mA Output Range
P201 mA Output Function
P202 mA Output Allocation
Displays current mA output value for the Point Number
P203 mA Output Value / Transducer
P210 0/4 mA Output Setpoint
P201-mA Function Action Settings
Independent mA Setpoints P210 and P211
MA Output Limits P212 and P213
P214 4 mA Output Trim
MA Output Trim P214 to P215
P212 mA Output Min Limit
P213 mA Output Max Limit
P219 mA Output Failsafe MR
MA Output Failsafe P219 MR
MA Input P250 to P260 MR
P215 20 mA Output Trim
Shows the mA input range of the connected mA device
P250 mA Input Range MR
P251 0 or 4 mA Input Level MR
P252 20 mA Input Level MR
P260 mA Raw Input MR
Discrete Input Functions P270 to P275
P253 Input Filter Time Constant MR
P254 Scaled mA Input Value MR
P275 Scaled Discrete Input Value
Record Temperatures P300 to P303
Standard Data Logging P300 to P321
P270 Discrete Input Function
P302 Temperature, Sensor Maximum
P300 Temperature, Transducer Maximum
P301 Temperature, Transducer Minimum
P304 Reading Max
P303 Temperature, Sensor Minimum
Record Readings P304 and P305
Pump Records P309 to P312
P312 Pump Run Ons MR
P309 Pump RUN Time
P310 Pump Hours
P311 Pump Starts
P321 Flow Min MR
Flow Records P320 and P321 MR
LCD Totalizer P322 and P323 MR
P320 Flow Max MR
P323 LCD Total High MR
Profile Records P330 to P337
P322 LCD Total Low MR
Code Description
P330 Profile Record
P333 Auto Record Interval
P331 Auto Record Enable
Use to enable/disable the Auto Profile Record function
P332 Auto Record Transducer
P335 Auto Record OFF Setpoint
Auto Record on and OFF Setpoints P334 to P337
P334 Auto Record on Setpoint
P337 Auto Record LOE Time
P336 Auto Record Filling / Emptying
P342 Start Ups
Installation Records P340 to P342
P340 Date of Manufacture
P341 RUN Time
Type of primary measuring device PMD used
Open Channel Monitoring P600 to P621 MR
P600 Primary Measuring Device MR
Single Point Model Dual
Exponent for the flow calculation formula
P601 Flow Exponent MR
Word on Exponents
PMD Type Exponent sample only
Dimensions of the Primary Measuring Device PMD
Example Exponents
Maximum flowrate associated with Maximum Head P603
P603 Maximum Head MR
P604 Maximum Flow MR
Level value associated with Maximum Flow, in Units P005
Conditions Enter
P605 Zero Head MR
Maximum number of decimal places to be displayed
P606 Time Units MR
P607 Flowrate Decimal MR
Million gallons / day Imperial
Volume units used to display total flow
P608 Flowrate Units MR
Cubic metres / hour Cubic metres / day Cubic feet / second
Flowrate corresponding to each Head Breakpoint entered
P610 Head Breakpoints MR
P611 Breakpoint Flowrates MR
Head vs. Flowrate P610 and P611
Calibrates Zero Head P605 based on actual head measurements
Procedure, with head steady
P620 Low Flow Cutoff MR
P621 Auto Zero Head MR
Or discharge
Pumped Volume Totalizer P622 MR
P622 Inflow / Discharge Adjust MR
P630 LCD Totalized Multiplier MR
Totalizer features apply to MultiRanger 200 only
Totalizer P630 to P645 MR
100 1000
P633 LCD Totalized Decimal Position MR
P640 Remote Totalized Multiplier MR
Enter the maximum number of decimal places to be displayed
Enter the mantissa Y for the exponent Z in the formula
P641 Flow Sampler Mantissa MR
P642 Flow Sampler Exponent MR
Enter the exponent Z for the mantissa Y in the formula
Offset Adjusts the measurements by a fixed amount
Range Calibration P650 to P654
P645 Relay Duration MR
Offset Calibration
Condition for use of this feature
P650 Offset Calibration
P651 Sound Velocity Calibration
P653 Velocity
Using Sound Velocity Calibration
Value altered when an Offset Calibration is performed
P652 Offset Correction
P660 Temp Source
Temperature Compensation P660 to P664
P654 Velocity at 20C
P660 Temp Source
P663 Temperature Transducer Allocation
Range -199 to 199 preset = 20 C
P661 Temp Fixed
P700 Max Fill Rate
P664 Temperature
View the transducer temperature in C
Rate P700 to P708
P003 Value Meters / Minute
P702 Filling Indicator
Fill rate required to activate the LCD Filling indicator
P701 Max Empty Rate
Damps Rate Value P707 fluctuations
P703 Emptying Indicator
Empty rate required to activate the LCD Emptying indicator
P704 Rate Filter
P005 Units P007 Span
P705 Rate Update Time
P706 Rate Update Distance
P707 Rate Value
P710 Fuzz Filter
P708 Volume Rate Display MR
Press Reading to toggle between percent and volume
Measurement Verification P710 to P713
P713 Echo Lock Window P820 Algorithm
P711 Echo Lock
Global Transducer Off
P713 Echo Lock Window
P711 value P712 preset value
Adjusts the size of the Echo Lock Window
P712 Echo Lock Sampling
P726 Level System Sync
P727 Scan Delay
Enables the System Sync on the terminal block
Transducer Scanning P726 to P729
P730 Auxiliary Reading
P728 Shot Delay
Display P730 to P739
P729 Scan Time
P731 Auxiliary Reading Key
P732 Display Delay
P733 Scroll Access
Adjusts the Point Number display scroll speed
Controls the LCD backlighting
P741 Communications Timeout
P735 Backlight
P737 Primary Reading MR
P771 Network Address
SmartLinx Reserved P750 to P769
Communications P770 to P782
P770 Port Protocol
P774 Data Bits
P772 Baud Rate
P773 Parity
P778 Modem Available
P779 Modem Inactivity Timeout
P775 Stop Bits
Global
SmartLinx Hardware Testing P790 to P795
P790 Hardware Error
P782 Parameter Index Location
P794 SmartLinx Module Type P795 SmartLinx Protocol
P791 Hardware Error Code
P792 Hardware Error Count
Space near the transducer face which cannot be measured
Echo Processing P800 to P807
P799 Communications Control
P800 Near Blanking
P802 Transducer with Submergence Shield
P801 Range Extension
Determines which echoes are evaluated by software
P803 Shot / Pulse Mode
P804 Confidence Threshold
Determines what type of ultrasonic shots are fired
Display Description
P805 Echo Confidence
P806 Echo Strength
P807 Noise
Time in ms from the transmit pulse to the processed echo
Advanced Echo Processing P815 to P825
P815 Echo Time Filtered
P816 Echo Time Raw
P820 Algorithm
Filters out echoes of a specific width
P821 Spike Filter
P822 Narrow Echo Filter
Dampens spikes in the echo profile to reduce false readings
Smoothes jagged peaks in the echo profile
P823 Reform Echo
P825 Echo Marker Trigger
Selects the TVT Curve used
Advanced TVT Adjustment P830 to P835
P830 TVT Type
P831 TVT Shaper
P833 TVT Start Min
P832 TVT Shaper Adjust
P833 TVT Start Min P835 TVT Slope Min
P834 TVT Start Duration
P835 TVT Slope Min
Values
Display before Auto False Echo Suppression Or when P837 =
P837 Auto False-Echo Suppression
Display after Auto False Echo Suppression
Set Up
P838 Auto False-Echo Suppression Distance
P839 TVT Hover Level
P841 Long Shot Number
Advanced Shot Adjustment P840 to P852
P840 Short Shot Number
P844 Short Shot Width
P842 Short Shot Frequency
P843 Long Shot Frequency
P850 Short Shot Bias
Adjust the width in ms of the long shot transmit pulse
Range 30 to Preset P840 Short Shot Number
P845 Long Shot Width
P901 Memory
Test P900 to P913
P852 Short Shot Range
P900 Software Revision Number
P905 Transmit Pulse
P902 Watchdog
P903 Display
P904 Keypad
P911 mA Output Value
P912 Transducer Temperature
P908 Scanner
P910 Toggle Relays
P914 mA Input MR
P913 Sensor Temperature
To Access in RUN Mode
Measurement P920 to P927
P001 P050 = P050 ≠
P921 Material Measurement
P922 Space Measurement
P923 Distance Measurement
Calculated flowrate in Max Flow P604 units or % of Max Flow
P924 Volume Measurement MR
P925 Flow Measurement MR
P926 Head Measurement MR
Pressing the Clear keys 7ML19981FB06
Master Reset P999
This feature resets all parameters to original values
P927 Distance Measurement
Parameters
Parameter depen Dent up to 7 2 Or 3
Appendix a Index Types
Global View only Breakpoint
Cursor
Transmit Pulse
Echo Processing
Dolphin Plus Display
Auto False-Echo Suppression
TVT Time Varying Threshold curves
Sound Velocity
Distance Calculation
Universal, Linear P050 =
Volume Calculation MR
Scanning
MultiRanger 100/200
Set P050 =
Flow Calculation
Universal, Curved MR
See also Typical Flow Characterization on
Universal, Linear MR
Fast
Maximum Process Speed
Parameter Units
Values Dependent on Maximum Process
Symptom Cause Action
Appendix C Troubleshooting
Common Problems Chart
Acoustical Noise
Noise Problems
Determine the Noise Source
Removed + removed Go to
Reducing Acoustical Noise
Common Wiring Problems
Non-Transducer Noise Sources
Reducing Electrical Noise
Flashing LOE Display
Adjust Transducer Aiming
Measurement Difficulties
Nozzle Mountings
Fixed Reading
Obstructions in the Sound Beam
Types of Wrong Readings
Adjust the Echo Algorithm
Wrong Reading
Set the MultiRanger to Ignore the Bad Echo
Ring Down TVT curve
Transducer Ringing
Normal Ring Down
Poor Ring Down
Unit Repair and Excluded Liability
Pump by Rate MR
Pump Control Options
Pump Control Algorithms
Pump Groups
Fixed Duty Assist P111 =
Fixed Duty Backup P111 = 51 MR
Cycle Relays
Alternate Duty Backup P111 = 53 MR
Alternate Duty Assist P111 =
Index Relays
Relay Operation for P118 = 2 MR
Service Ratio Duty Assist P111 = 54 MR
Pump by Rate P121 MR
Service Ratio Duty Backup P111 = 55 MR
Other Pump Controls MR
First In First Out Fifo P111 = 56 MR
Flush Device P170 to P173
Updating Software
Appendix E Updating Software
Coaxial Transducer Extention
Connecting the Transducer
Appendix F Upgrading
Mounting a MultiRanger 100/200
Existing installation
Connecting a transducer with RG62 coaxial extension cable
On setpoint
Alarm
MultiRanger Plus
Relay Parameter Value
7ML19981FBO6
Appendix G Conduit Entry for Class 1, Div 2 Applications
Appendix G
23650314
Changes
MultiRanger
Soft
Soft Ware Date Changes Rev
Improvement to prevent it from going
Systems testing
Property no Reset
Simatic PDM related TVT display
Changed P132 to global
Eliminated rogue watchdog resets when
Improved Preset Application values
Using Dolphin+
DDs required 7ML19981FB06
OCM Time Units improvement
From Modbus map reg
Now being protected from other units’ Transmit pulse
Reading some floats as decimal shifted
Property noReset
Improved volume calculation for 3rd point
Volume
P000 Lock G
Programming Charts
Parameter Charts
P210 0/4 mA Output Setpoint P211 20 mA Output Setpoint
P121 Pump by Rate MR P122 Pump Service Ratio MR
P113 Relay OFF Setpoint P115
P116 Deadband P118 Relay Output Logic P119 Relay Logic Test
P322 LCD Total Low MR P323 LCD Total High MR
P219 mA Output FailsafeMR
P304 Reading Max P305 Reading Min
P320 Flow Max MR P321 Flow Min MR
Open Channel Monitoring
P340 Date of Manufacture P341 RUN Time P342 Start Ups
Temperature Compensation
SmartLinx Reserved Communications
P737 Primary Reading MR P741 Communications Timeout
Reserved
Parameter
Index
103
Parameter access
105
153
162
203
212
207
242
Service ratio
Testing
110
233
Characterization chart
Weir
167
Page
Page
7ml19981FB06