42 Chapter 2 Nortel VPN Router 1750 chassis
Installing the chassis in an equipment rack
To mount the VPN Router 1750 in an equipment rack, you need the following equipment:
•standard
•four screws (supplied with the chassis)
•four cage nuts (supplied with the chassis) if the rack does not have threaded rail holes
•a #2 Phillips screwdriver
Rack-mount recommendations
When you mount the chassis in the equipment rack, observe the following standard recommendations:
•The maximum recommended ambient temperature is 40oC (104oF). Ensure that the internal temperature of the rack does not exceed 40oC (104oF).
•Do not block the power supply vents or otherwise restrict air flow when you install the chassis in the rack.
•Stabilize the rack so that it does not tip over under the weight of the gateway and other devices.
•Before you install and turn on the gateway, ensure that the electrical branch circuits can handle the VPN Router 1750 and other units in the rack.
•Maintain a reliable
Attaching the shelf in the equipment rack
The VPN Router 1750 ships with a
To attach the shelf to the inside of the equipment rack, perform the following steps: