VS375C/VS575C | 13 |
4. SPECIFICATIONS
4.1 Electrical Specifications
|
| Product Name |
|
| Frequency (Hz) |
|
| Voltage (V) | Capacity VA / W |
| |||||
|
| VS375C |
|
| 50/60 |
| 100 / 110 / 120 | 375VA / 225W |
| ||||||
|
|
|
|
| 220 / 230 / 240 |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| VS575C |
|
| 50/60 |
| 100 / 110 / 120 | 575VA / 345W |
| ||||||
|
|
|
|
| 220 / 230 / 240 |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Input/Output Voltage |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| AC Line Voltage |
|
|
|
| ||||
|
| Version |
|
| Lower Limit |
|
| Upper Limit |
| ||||||
|
| 100 / 110 / 120V |
|
| 85/ 94/ 102V |
|
| 120 / 134 / 138V |
| ||||||
|
| 220 / 230 / 240V |
| 165/ 184/ 192V |
|
| 275 / 276 / 276V |
| |||||||
|
| Input/Output Frequency Range |
|
|
|
|
|
|
| ||||||
|
| Input |
| 50 Hz / 60 Hz ± 10% |
|
|
|
| |||||||
|
| Output (Inverter mode) | 50 Hz / 60 Hz ± 0.3 Hz |
|
|
|
| ||||||||
|
| Wave Form : |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| AC Mode |
|
| Sine wave |
|
|
|
|
|
| ||||
|
|
|
| Step wave |
|
|
|
|
|
| |||||
|
| Transfer Time: |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| Power failure | AC ⇒ inverter |
|
| 4 ms (typical) |
|
| |||||||
|
| Spike/Surge Protection: |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Version |
|
| Continuous |
|
| Single pulse 8/20us |
|
| |||||
|
|
|
| Voltage Vrms |
| Imax |
| Joules |
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
| 100/110/120 |
|
|
| 175V |
|
| 6500A |
| 1050 |
|
| ||
|
| 220/230/240 |
|
|
| 300V |
|
| 6500A |
| 1050 |
|
| ||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Telephone Line Surge Protection |
|
|
| +/- 6KV Peak |
|
| |||||||
|
|
|
|
| (1.2∝S/50 Waveform) |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| 10/100 | Protection Let |
|
|
|
| <1% |
|
|
| ||||
|
| Through Rating |
|
|
|
| (From 6KV/125A Normal Mode Surge) |
|
|