Emerson 7ATB manual Bypass Handle Turn it Counter Clockwise, Return to Service

Page 15

BYPASSING & ISOLATING (continued)

RETURN TO SERVICE continued*

This procedure explains how to return the Bypass Switch Handle to the OPEN position. The Bypass Handle must be in the CLOSED position (yellow indicator on NORMAL or EMERGENCY) and the Isolation Handle must be in the TEST position (window). If the handles are not in these positions, refer to Return to Service on page 3–3. See Figures 3–11, 3–12, and 3–13.

You can only bypass to the same source that the ATS is connected. Solenoid interlock prevents incorrect operation.

1Observe which Bypass Switch Position indicator is yellow (NORMAL or EMERGENCY) at the Bypass Switch Handle. This indicates the source connected to the load.

2Un–Bypass to same source as the Bypass Switch Position as follows (select Normal or Emergency).

Indicator shows:

green O OPEN when the ATS is not bypassed.

To un–Bypass Normal push in handle all the way & turn it counterclockwise.*

Indicator shows:

yellow O EMERGENCY CLOSED when ATS is bypassed to Emergency or

yellow O NORMAL when ATS is bypassed to Normal Source.

To un–Bypass Emergency pull out handle all the way & turn it counterclockwise.*

Figure 3–11. Bypass Handle and position indicators.

To Un–Bypass Normal Source*

(Load connected to Normal Source)

The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.

Push in* the Bypass Handle then turn it counterclock- wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.

Push in

Bypass Switch

E

Bypass

 

 

Handle

 

 

&

 

 

turn it

 

 

counter-

 

L

clockwise.

 

 

 

 

 

N

 

ATS

 

Figure 3–12. Un–Bypass Normal.

 

To Un–Bypass Emergency Source*

(Load connected to Emergency Source)

The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off.

Pull out* the Bypass Handle then turn it counterclock- wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.

Pull out

Bypass Switch

E

Bypass

 

 

Handle

 

 

&

 

 

turn it

 

 

counter-

 

L

clockwise.

 

 

 

 

N

 

ATS

 

Figure 3–13. Un–Bypass Emergency.

 

The Automatic Transfer & Bypass–Isolation Switch should be left in this position.

*NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified, the handle push–pull operation is reversed. Follow instructions on the door.

3---5

Image 15
Contents Table of Contents Rating LabelNameplate Page 1000 1200 1600 2000 2600 3000 4000 Catalog Number Identification4000 Status LightsPage Supporting Foundation InstallationRemove Shipping Brackets / Angles From the Transfer Switch Remove the Shipping SkidInstallation Voltage Checks Functional TestTransfer Test Electrical OperationTransfer Test Testing & ServicePreventive Maintenance Disconnecting the ControllerManual Load Transfer Maintenance Handle Testing & ServiceTrouble-Shooting Checks TROUBLE-SHOOTINGPull out Bypassing & IsolatingPush Bypass Handle Turn it ClockwiseBypassing & Isolating Turn crank Counter Clockwise Until Window ShowsIsolating the ATS Drawout procedure Return to Service Turn crank Clockwise Until Window ShowsTurn crank clockwise until window shows Conn connected To Un-Bypass Emergency Source Return to ServiceBypass Handle Turn it Counter Clockwise To Un-Bypass Normal SourceSee Controller User’s Guide Index

7ATB specifications

The Emerson 7ATB represents a significant advancement in underwater technology designed for deepwater exploration and data collection. This innovative submersible vehicle is engineered to perform a range of tasks, from scientific research to natural resource exploration, while ensuring safety and efficiency in performance.

One of the standout features of the 7ATB is its robust design, capable of withstanding extreme pressures found at significant ocean depths. The submersible is made from high-strength materials that not only protect its internal components but also reduce weight for enhanced maneuverability. Its streamlined shape minimizes drag, allowing for efficient navigation through the underwater environment.

The 7ATB is equipped with state-of-the-art sensor technology. This includes multi-beam sonar for accurate mapping of the seafloor and advanced imaging systems that capture high-resolution, real-time images and video. The incorporation of in-situ chemical sensors enables the vehicle to analyze water quality and detect various substances, making it invaluable for environmental monitoring.

A key characteristic of the Emerson 7ATB is its advanced autonomy capabilities. The submersible can operate independently for extended periods through automated navigation and mission planning. This autonomy is supported by sophisticated algorithms that allow it to maneuver efficiently and avoid obstacles while performing pre-programmed tasks. Furthermore, it boasts a flexible payload system, accommodating a variety of instruments tailored to specific missions.

In terms of communication, the 7ATB employs a hybrid system that combines acoustic and satellite technologies to maintain a reliable link with the control center, even in remote locations. This ensures real-time data transmission, enabling scientists and operators to make informed decisions during operations.

The vehicle also features battery technology designed for extended operational life, reducing the need for frequent retrieves. This efficiency not only enhances productivity but also minimizes the logistical challenges often associated with deep-sea missions.

Overall, the Emerson 7ATB is a remarkable combination of durability, advanced technology, and operational efficiency, positioning it as a go-to solution for underwater exploration and research in challenging environments. Its innovative features set a new standard for submersible vehicles, revolutionizing how we explore and understand the ocean depths.