Emerson Remote Monitoring Panel user manual Current Record Window

Page 19

Operation

Table 12 Descriptions of RMP menus and data window items (continued)

Menu

 

 

Type

Item Type

Explanation

 

Battery voltage (V)

Battery bus voltage

 

Battery current (A)

Battery bus current

 

Battery temperature (°C)

Battery temperature °C

Battery

Remain Time Min.

Battery run time remaining

 

Battery boost charging

Battery is boost charging

 

Battery float charging

Battery is float charging

 

Battery disconnected

Battery is not connected

Records

(history log)

Displays all records in the history log

Language

(choices for text displayed)

User may select any of 12 languages for LCD text.

 

Display contrast

Adjust the LCD display contrast

 

Date format set *

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

 

Date & time *

Set the date and time

 

Comm1 baud rate *

Communication baud rate setting for IntelliSlot 1

 

Comm2 baud rate *

Communication baud rate setting for IntelliSlot 2

 

Comm3 baud rate *

Communication baud rate setting for IntelliSlot 3

 

Communication address *

This setting is applicable to RS485 communication mode

Settings

Communication mode *

Communication Mode Setting

Callback times *

When IntelliSlot 1 Communication mode is Modem, this parameter sets

 

 

the number of times a number is redialed to send an alarm notification.

 

 

 

 

 

 

Phone No.1 *

When IntelliSlot 1 Communication mode is Modem, this is the first phone

 

number to be dialed (to send an alarm notification).

 

 

 

Phone No.2 *

When IntelliSlot 1 Communication mode is Modem, this is the second

 

phone number to be dialed (to send an alarm notification).

 

 

 

Phone No.3 *

When IntelliSlot 1 Communication mode is Modem, this is the third phone

 

number to be dialed (to send an alarm notification).

 

 

 

Command password *

User can modify the command password.

 

Battery maintenance test *

This test performs a partial discharge of the battery to obtain a rough

 

 

estimate of the battery capacity. Load must be between 20% and 100%.

 

Battery capacity test *

This test performs a full discharge of the battery to obtain a precise

 

measure of the battery capacity. Load must be between 20% and 100%.

 

 

Command

System test *

This is a self-test of the UPS. When the user activates this function, a

popup window appears about 5 seconds later to show the results.

(start/stop

 

battery &

Stop testing *

Manually stops a battery maintenance test, battery capacity test or system

system

test.

 

tests)

 

 

Freshening Charge *

This command will allow a temporary Equalize charge for the batteries.

 

 

This charge is configurable for 1 to 36 hours

 

 

 

Stop Freshening Charge *

Manually stop a Freshening Charge

 

Modem Auto-answer

Manually enable the auto-answer function of modem.

 

enable *

 

 

 

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and

Version

software display board.

 

 

UPS model

Provides UPS model information—for example, 400V-50Hz.

* Visible from the RMP, but the control is available at UPS only.

Current Record Window

Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions that have been resolved. Use “page” (F1) and up / down arrow to read the events.

For a complete history log, refer to the Records tab of the Menu and Data Window. Refer to Table 13 for a complete list of supported status messages.

15

Image 19 Contents
Liebert Remote Monitoring Panel Page Table of Contents Figures Information for the Protection of the Environment Introduction RMP component location in Figure UPS Room Maintenance or Control RoomPreliminary checks Power Supply15.6mm 14mm Cable Specifications Communication cable specificationsUPSU2J24 Mounting the RMP on DrywallElectrical connections Power and communication cable routingCommunication connections On Remote Monitoring Panel board RS-485 cable connection to Liebert NXOpening screen Startup and ResetSilence On/Off screens UPS and RMP firmware are compatible screenCommunication with UPS failed Audible Alarms-Buzzer LED Mimic Power FlowMenu key Icons and their meaning LCD Monitor and Menu KeysKey Help Window Type Stop Freshening Charge Freshening ChargeMenu Type Item Type Explanation Detailed Description of Menu ItemsUPS system window Descriptions of RMP menus and data window itemsCurrent Record Window RMP messages Status and Event MessagesMessage Description / Suggested Action if any Condition is no longer true EPO RMP messages Prompt windows, meanings controlled at RMP Dynamic Energy Flow Chart and UPS Help ScreenPrompt Popup Windows Prompt windows, meanings controlled at UPS onlyHelp screen Default screen saverCable specifications Mechanical specificationsEnvironmental specifications Electrical specificationsElectromagnetic interference EMI-emission limits Agency and CertificationsElectromagnetic susceptibility EMS-immunity levels Er t Ne tIti Ti n