Emerson Remote Monitoring Panel user manual LED Mimic Power Flow, Audible Alarms-Buzzer

Page 15

Operation

3.2LED Mimic Power Flow

The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper- ational status.

Table 3

Rectifier indicator

 

 

Green

Rectifier in Normal Operation

 

 

Flashing

Input AC Normal, but rectifier not operating

Green

 

Red

Rectifier Failed

 

 

Off

Rectifier Not operating, Input AC Not Available or out of normal range

 

 

Table 4

Battery indicator

 

 

Green

Battery Normal, but discharging and powering the load

 

 

Flashing

Battery End of Discharge pre-warning

Green

 

 

Battery abnormal (Failed, Absent or Polarity Reversed) or Battery

Red

Converter abnormal

 

(Failed, overcurrent, overtemperature)

Off

Battery and Converter Normal, Battery charging

 

 

Table 5

Bypass indicator

Green

Load on Bypass power

 

 

Red

Bypass not available, out of normal range or Static bypass switch fault

 

 

Off

Bypass Normal, load not on bypass

 

 

Table 6

Inverter indicator

 

 

Green

Inverter Normal and powering the load

 

 

Flashing

Inverter ON, starting up, synchronizing, or standing by (ECO mode)

Green

 

Red

Inverter failed

 

 

Off

Inverter not operating

 

 

Table 7

Load indicator

Green

UPS output ON and Normal

 

 

Red

UPS output ON and Overloaded

 

 

Off

UPS output OFF.

 

 

Table 8

Status (Alarm) indicator

 

 

Green

Normal Operation

 

 

Yellow

UPS Warning e.g. AC Input Failure

 

 

Red

UPS fault (ex. Fuse or Hardware failure)

 

 

3.3Audible Alarms—Buzzer

UPS activity is accompanied by the following sounds

Table 9 Audible alarm key

Single beep

Direct Access key acknowledgement

 

 

One beep per second

UPS Warning, (ex. AC Input Failure)

 

 

Continuous beep

Fault, (ex. Fuse or Hardware Failure)

 

 

11

Image 15 Contents
Liebert Remote Monitoring Panel Page Table of Contents Figures Information for the Protection of the Environment Introduction RMP component location in Figure UPS Room Maintenance or Control RoomPreliminary checks Power Supply15.6mm 14mm Cable Specifications Communication cable specificationsUPSU2J24 Mounting the RMP on DrywallElectrical connections Power and communication cable routingCommunication connections On Remote Monitoring Panel board RS-485 cable connection to Liebert NXOpening screen Startup and ResetSilence On/Off screens UPS and RMP firmware are compatible screenCommunication with UPS failed Audible Alarms-Buzzer LED Mimic Power FlowLCD Monitor and Menu Keys Menu key Icons and their meaningKey Help Window Type Stop Freshening Charge Freshening ChargeMenu Type Item Type Explanation Detailed Description of Menu ItemsUPS system window Descriptions of RMP menus and data window itemsCurrent Record Window Status and Event Messages RMP messagesMessage Description / Suggested Action if any Condition is no longer true EPO RMP messages Prompt windows, meanings controlled at RMP Dynamic Energy Flow Chart and UPS Help ScreenPrompt Popup Windows Prompt windows, meanings controlled at UPS onlyHelp screen Default screen saverCable specifications Mechanical specificationsEnvironmental specifications Electrical specificationsAgency and Certifications Electromagnetic interference EMI-emission limitsElectromagnetic susceptibility EMS-immunity levels Er t Ne tIti Ti n