Emerson 3U MP2-220N user manual Troubleshooting, Utility

Page 14

Troubleshooting

7.0TROUBLESHOOTING

Problem

UTILITY lamp (amber) not Illuminated.

UPS Available lamp (green) not illuminated.

3U POD will not start some / all connected loads.

Utility or UPS circuit protectors trip after resetting.

Cause

Utility not present.

Utility Branch Circuit Breaker may be open.

3U POD input power not connected to

UTILITY.

UPS output power not present.

UPS input and/or output cord not connected to 3U POD.

Input power cannot support load.

Overcurrent on 3U POD connected load.

Solution

Call qualified service personnel to restore power. Verify that the branch circuit breaker is closed.

Refer to the 3U POD installation instructions in this manual:

2.0 - Rack Mount Installation

3.0- Installation and Electrical Connections

4.0- Alternate Hardwire Installation

Turn on the UPS. Refer to the UPS user manual.

Refer to the 3U POD installation instructions in this manual:

2.0 - Rack Mount Installation

3.0- Installation and Electrical Connections

4.0- Alternate Hardwire Installation

Verify that utility and UPS are on, all circuit protectors are closed and the load is within the rating of the power source.

Recalculate load requirements.

10

Image 14
Contents Power Availability 3U MP2-220N PODPage Figures Page Important Safety Instructions Glossary of Symbols System Description Introduction and System DescriptionRack Mount Installation Side view of 3U POD with mounting bracketInstallation and Electrical Connections Power Connection OptionsCord-Receptacle Installation and Start-Up Electrical Connections Electrical Installation ConsiderationsAlternate Hardwire Installation Conversion From Cord-Receptacle to Hardwire Screws Used for Internal WiringIndicator Lamps Utility Indicator LampUPS Indicator Lamp Operation Transfer to Maintenance BypassTransfer to UPS Troubleshooting UtilityProduct Warranty Registration SpecificationsSpecifications Page Locations Technical Support/ServiceCompany Behind the Products