Page 5

INSTALLATION (continued)

handle

shafts

handle

 

handle

 

Figure 1-2.

Figure 1-3.

Figure 1-4

150 – 400 A (3 pole)

600 & 800 A (& 4 pole 400 A)

3000 & 4000 A

E–design switches

F–design switches

F–design transfer switches

1 – Manual Operation

A detachable manual operator handle is provided on the Transfer Switches for maintenance purposes only. Manual operation of both CN and CE transfer switches must be checked before they are operated electrically.

Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.

1.Select the appropriate switch amperage size above and follow the directions for installing the handle:

150 through 400 amp. E–design See Figure 1-2. Insert the manual handle into the hole in the shaft, left side of the operator.

600 and 800 amp. F–design See Figure 1-3.

Attach the manual handle onto the pivot shaft extension, left side of the operator.

1000 through 4000 amp. G–design See Figure 1-5.

Install the hub (with pin) onto the shaft and insert the manual firmly into the side hole in the hub. Push in or pull out hub to engage opposite source contacts.

3000 and 4000 amp. F–design See Figure 1-4.

Insert the manual handle into the hole in the weight.

2.Move the handle as shown to manually operate the Transfer Switch. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris. Repeat the manual operation check on the other Transfer Switch.

3.Return the CN Transfer Switch to the C (closed) position. Return the CE Transfer Switch to the O (open) position. Remove manual operator handle and store it on the Transfer Switch in the place provided.

Verify that the maintenance handle has been removed and stored properly before proceeding!

Now continue to 2 – Voltage Checks on next page.

Emergency contacts

window

indicators

OPEN or

CLOSED

Grasp handle firmly with both hands

Slide the hub onto the shaft and insert the pin.

Turn counterclockwise

Insert handle

into hole

to OPEN contacts.

(spring fully

Turn clockwise to

compressed)

CLOSE contacts.

 

Normal contacts

contact position

indicators (left side)

counterclockwise DOWN

clockwise DOWN

OPENS the contacts

OPENS the contacts

Pull out shaft to open Emergency

Pull out shaft to close Emergency

source contacts (upper)

source contacts (upper)

Push in shaft to open Normal

Push in shaft to close Normal

source contacts (lower)

source contacts (lower)

Figure 1-5. 1000 – 4000 ampere G–design transfer switches.

1---3

Image 5
Contents Nameplate Rating LabelCatalog Number Identification Installation Auxiliary Circuits Engine Starting Contacts Controller GroundHarnesses Normal contacts Contact position Indicators left side Emergency contacts Window IndicatorsManual Operation HandleVoltage Checks Standard controls and indicatorsTransfer Test Electrical OperationUnited States call 1 800 800 Asco Testing & ServiceTesting & Service See Controller User’s Guide Index