USB Interface Port
1. | Firmware | Version of Firmware |
2. | Rating VA | Rated Power Capacity of UPS |
3. | Rating Voltage | Rated Power Voltage of UPS |
4. | Rating Frequency | Connected Frequency Rating of UPS |
5. | Rating Battery | Rated Battery Voltage Used by UPS |
6. | Input Frequency | AC Utility Frequency |
7. | Input Voltage | AC Utility Voltage |
8. | Output Source | Indicating Bypass or On Battery |
9. | Alarm | To Set Situation for Alarm |
10. Voltage Sensitivity | To Improve Transfer Time and Avoid |
| | Effect of I/P Distortion |
11. Outlet Relay ON/OFF | Set Delay Time to Control Outlet Relay |
| | On/Off |
12. Next Shutdown | Time to Next Scheduled Shutdown |
13. Next Restart | Time to Next Restart |
14. AC Source | Input Power Source of UPS |
15. Battery | Condition of Battery |
16. Loading | Load Percentage of UPS |
17. Battery Level | Indicates the Remaining Power |
| | Percentage of Battery |
18. Selectable Transfer Voltage | Change Transfer Voltage |
19. Diagram | Input & Output Power Flow of UPS |
20. Picture | General Outlook of UPS |
RS232 Interface Port
RS232 Pin definition: | | | |
NC - - - - - - - - - - - - - - - | 1 | 6 - - - - - - - - - - - - - - - - | NC |
TXD - - - - - - - - - - - - - - | 2 | 7 - - - - - - - - - - - - - - - - | NC |
RXD - - - - - - - - - - - - - | 3 | 8 - - - - - - - - - - - - - - - - | NC |
NC - - - - - - - - - - - - - - - | 4 | 9 - - - - - - - - - - - - - - - - | NC |
Signal Ground - - - - - - - | 5 | | |
*pin2: PC receives line RS232 data from UPS.
*pin3: PC transmits line RS232 data to UPS.
*pin5: signal ground.
*other: not used.
The RS232 communication port provides the following features:
1. Monitoring charger status
2. Monitoring battery status and condition
3. Monitoring inverter status
4.Monitoring UPS status
5.Monitoring the utility status
6.Providing the power switch function for the computer to turn on/off the utility on schedule. To save power, UPS data will be provided at 2400 baud rate and is made up of 8-bit, 1-stop-bit, and no parity-bit. All the information is provided in ASCII format.
CABLING: | | |
| COMPUTER | | UPS |
RX | (pin2) | TX | (pin2) |
TX | (pin3) | RX | (pin3) |
GND | (pin5) | GND | (pin5) |
Battery Replacement
The average life of a battery is 3-5 years before ever needing to be replaced.
EcoPower Battery Replacement Program™
In the event that the UPS needs a battery replacement, Belkin offers its EcoPower Battery Replacement Program™. This program offers a battery replacement and full service check on your UPS to ensure it is working properly to protect your connected devices. It also ensures that the battery in the UPS is discarded properly in an effort to keep our environment clean. All participants in the program will receive a two-year extended product warranty. Please call Belkin Components for detailed information regarding the cost of the program and shipping procedures.
Battery Replacement
Battery replacement is a safe procedure. You may leave the UPS On and equipment connected during this procedure. Do not replace the battery when the UPS is “On Battery”. See page 15 for diagram illustrations.
1.Set the UPS at the edge of a table (Diagram A).
2.Slide the battery compartment cover down (Diagram B).
3.Grasp the tab attached to the battery and slide the battery partially out. Then grab the battery firmly and remove; the battery wires will disconnect as the battery is pulled out (Diagram C).
4.Carefully insert the new battery halfway into the UPS. Avoid pinching the wires (Diagram D).
5.Connect the wires to the new battery according to the following configuration:
Red wire to red terminal Black wire to black terminal
6.Carefully insert the battery terminals.
7.Slide the battery compartment cover back into place (Diagram E).
The old battery must be recycled. Deliver the battery to an appropriate recycling facility or return it to Belkin in the packing carton that came with your new battery. Additional recycling information is provided with your new battery.
Battery Replacement (continued)
| Refer Servicing to | Diagram A |
| qualified service |
| |
| personnel or contact | |
| Belkin Components. | |
Diagram B | Diagram C |
Slide the battery | Slide the battery |
compartment cover. | partially out. |
|
Diagram D | Diagram E |
Slide the battery back in. | Slide the battery |
Avoid pinching | cover into place. |
the wires. | |
Troubleshooting
| PROBLEM | POSSIBLE CAUSE | SOLUTION |
| | | |
| UPS not on | On/off/test/button not pushed or | Press the on/off/test button |
| LED not lit | pushed less than 3 seconds | more than 3 seconds |
| | | |
| | Battery voltage less than 10V | Recharge the UPS at least |
| | | 4 hours |
| | | |
| | UPS fault | Contact service personnel |
| | | |
| UPS always at | Power cord loose | Replug the power cord |
| battery mode | | |
| AC breaker is burned out | Replace the breaker |
| |
| | | |
| | Line voltage too high, too low, | Normal condition |
| | or black out | |
| | | |
| Back-up time too short | Battery not fully charged | Recharge the UPS at least |
| | | 4 hours |
| | | |
| | UPS is overloaded | Remove some unnecessary |
| | loads | |
| | | |
| | Charger fault or | Replace battery |
| | other reason | |
| | | |
| The UPS continuously | Overload | Remove the non-critical loads |
| beeps | | |
| | | |
| Red LED lit | Battery failure | Replace battery |
| | | |
Storage
11.0Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least 4 hours. Disconnect any cables connected to the computer interface port to avoid unnecessary drainage of the battery.
11.1Extended Storage
During extended storage in environments where the ambient temperature is -15°C to +30°C, charge the UPS battery every 6 months.
During extended storage in environments where the ambient temperature is +30°C to +45°C, charge the UPS battery every 3 months.
Specifications (USB Series)
CE Declaration of Conformity
We, Belkin Components, declare under our sole responsibility that the F6C325u- 220V, F6C425u-220V, F6C525u-220V, F6C625u-220V, to which this declaration relates, is in conformity with Generic Emissions Standard EN50081-1 and with Generic Immunity Standard EN50082-1 1992 to which this declaration relates, is in conformity with Generic Emissions Standard EN50081-1 and with Generic Immunity Standard EN50082-1 1992.
Belkin Components Two-Year Product Warranty
Belkin Components warrants this product against defects in materials and workmanship for two years. If a defect is discovered, Belkin will, at its option, repair or replace the product at no charge, provided it is returned during the warranty period, with transportation charges prepaid, to the authorized Belkin dealer from whom you purchased the product. Proof of purchase may be required.
This warranty does not apply if the product has been damaged by accident, abuse, misuse, or misapplication; if the product has been modified without the written permission of Belkin; or if any Belkin serial number has been removed or defaced.
THE WARRANTY AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE IN LIEU OF ALL OTHERS, WHETHER
ORAL OR WRITTEN, EXPRESSED OR IMPLIED. BELKIN SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
No Belkin dealer, agent, or employee is authorized to make any modification, extension, or addition to this warranty.
BELKIN IS NOT RESPONSIBLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY BREACH OF WARRANTY, OR UNDER ANY OTHER LEGAL THEORY, INCLUDING BUT NOT LIMITED TO LOST PROFITS, DOWNTIME, GOODWILL, DAMAGE TO OR REPROGRAMMING, OR REPRODUCING ANY PROGRAM OR DATA STORED IN OR USED WITH BELKIN PRODUCTS.