SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS

These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without load transfer, or they can be completely disabled. The engine-generator should be exercised under load once a week for a minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.

BUILT–IN ENGINE EXERCISER

The engine exerciser included in ASCO Series 300 Automatic Transfer Switches provides a once a week 20–minute exercise period. It occurs immediately when the SET ENGINE EXERCISER push button is pressed (and held for at least 5 seconds), and then at the same time weekly thereafter. A 9 volt alkaline battery (DuracellR MN1604, EverreadyR 522, or PanasonicR 6AM6) is furnished and installed in the controller to maintain the setting. The battery jumper block must be shifted to the ON position. See Figure 4–2 on page 4–2.

Fill in day and time set. Week Day ______ Time _______.

DIP Switch Settings

FUNCTION

S1 DIP

 

 

 

S2 DIP

 

 

 

SWITCH

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

Std. Timer

Actuator

 

 

 

 

 

 

 

7

 

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Enabled

7 on

 

 

 

 

 

 

 

 

5 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std. Timer

Actuator

 

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

 

 

 

 

7

 

 

 

5

 

Disabled

7 off

 

 

 

 

 

 

5 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

without

 

 

 

8

 

 

 

 

 

 

 

8 off

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with Load

8 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

Press to cancel an active exercise period (stops generator).

If Exercise with Load is set, retransfers load to Normal, then stops generator after 5 min. cooldown.

 

status light

 

 

Press and hold for 5 sec. or until status

 

light blinks rapidly to set exercise period

Press until light FLASHES

immediately and every week hereafter

 

(generator starts).

Figure 5-1. Operator panel pushbuttons and light.

If Exerciser with Load is set,

transfers load to Emergency.

Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1, actuator 8. The load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.

Exercise without Load, DIP Switch S1, Actuator 8 off

8

How to Set Built–In Timer

Step

 

 

 

Function

Explanation

 

Push Button

 

Status Light

 

 

 

 

 

 

 

SET ENGINE

 

blinks rapidly

 

Exercise the generator now and

1

EXERCISER

 

set exercise period

 

FfFfFf

every week at this time hereafter.

 

hold 5 sec.

 

 

 

 

 

 

 

2

release

 

blinks slowly

exercise period now active

Generator starts and runs.

 

FffFff

 

 

 

 

 

3

press BYPASS

 

F stays on

cancel active exercise period

Generator stops.

TIME DELAY

 

 

 

 

 

 

4

 

F stays on

generator off

Exerciser enabled; repeats every 7 days.

Exercise with Load, DIP Switch S1, Actuator 8 on

8

How to Set Built–In Timer

Step

 

 

 

Function

Explanation

 

Push Button

 

Status Light

 

 

 

 

 

 

 

SET ENGINE

 

blinks rapidly

 

Exercise the generator now and

1

EXERCISER

 

set exercise period

 

FfFfFf

every week at this time hereafter.

 

hold 5 sec.

 

 

 

 

 

 

 

2

release

 

blinks slowly

exercise period now active

Generator starts and runs;

 

FffFff

the load transfers to Emergency.

 

 

 

 

 

press BYPASS

 

blinks slowly

 

The load retransfers to Normal; then

3

 

cancel active exercise period

generator runs for 5 minute cooldown

TIME DELAY

 

FffFff

 

 

 

 

 

( light blinks slowly during cooldown ).

4

 

F stays on

generator off

Exerciser enabled; repeats every 7 days.

NOTE: Every time SET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.

5--1

Image 13
Contents Operator’s Manual 1000 1200 1600 2000 2600 3000 Nameplate Catalog Number IndentificationInstallation Controller Ground Source fails Transfer switchEngine Starting Contacts Auxiliary CircuitsATS Position Indicators Installation Functional TestManual Operation Test Use a phase rotation meter to InstallationVoltage Checks Black circle means light is onElectrical Operation Transfer To Emergency Sequence of OperationPreventive Maintenance Testing & ServiceTROUBLE-SHOOTING Testing & ServiceProceed with care Automatic transfer switch is energized Manual Load TransferTime Delay Adjustment AdjustmentsSensor Adjustments Time Delay SettingsHow to Change a Setting AdjustmentsClose the enclosure door How to Set Built-In Timer DIP Switch SettingsBUILT-IN Engine Exerciser Step Function Explanation Push Button Status LightOptional Programmable Engine Exerciser Accessory 11CD Control FeaturesCanceling Time Programs Setting the Clock Time and DayChanging or Checking Time Programs Programming Engine On-Off PeriodsLoad Disconnect Feature Inphase Monitor For Motor Load TransferControls Strip Heater AccessoryIndex

Series 300 specifications

TRENDnet Series 300 is a powerful lineup of networking devices designed to deliver robust performance and high-speed connectivity for various applications. With its focus on both home and small office environments, the Series 300 incorporates advanced technologies to ensure seamless connectivity and enhanced network management.

One of the primary features of the TRENDnet Series 300 is its support for the latest wireless standards. Equipped with 802.11ac technology, these devices provide significant improvements in speed and range compared to previous generations. Users can experience wireless speeds up to 1300Mbps, making it ideal for streaming high-definition content, online gaming, and large file transfers.

Additionally, the Series 300 boasts dual-band capabilities, allowing users to connect to both 2.4GHz and 5GHz frequency bands. This flexibility helps to reduce interference and ensures stable connections for multiple devices simultaneously. The dual-band feature is particularly beneficial in crowded environments, where numerous devices compete for bandwidth.

Security is paramount in any networking solution, and TRENDnet Series 300 devices offer robust security protocols to safeguard users' data. With support for WPA/WPA2 encryption, users can ensure their wireless networks are protected against unauthorized access. Furthermore, many models in this series integrate advanced security features such as a built-in firewall and guest network options, providing an extra layer of protection.

Another notable characteristic is the intuitive user interface, which simplifies the setup and management of network configurations. Users can easily access and modify settings through a user-friendly web interface or a mobile application. This ease of management makes it accessible even for users with limited technical expertise.

The Series 300 is also designed with versatility in mind, featuring multiple Ethernet ports for wired connections. This is beneficial for devices that require a stable network connection, such as gaming consoles and smart TVs. Additionally, Power over Ethernet (PoE) capabilities allow the devices to power compatible network devices, reducing cable clutter.

Finally, TRENDnet's commitment to reliability is evident in the build quality of the Series 300. These devices are engineered for long-lasting performance and efficiency, making them a trustworthy choice for both personal and professional networking needs. Overall, the TRENDnet Series 300 series stands out as a comprehensive networking solution, incorporating speed, security, and ease of use into its design.