IBM IBM UPS 10000XHV setup guide Storage, Replacing the Battery Modules, Shipping and Service

Page 20

4:STORAGE, MAINTENANCE, SHIPPING, AND SERVICE

Storage

Store the uninterruptible power supply covered in a cool, dry location, with the batteries fully charged.

At -15 to +30 °C (+5 to +86 °F), charge the uninterruptible power supply battery every six months.

At +30 to +45 °C (+86 to +113 °F), charge the uninterruptible power supply battery every three months.

Replacing the Battery Modules

Attention:

Upon battery disconnection, connected equipment is not protected from power outages.

Use caution when handling heavy battery modules.

The uninterruptible power supply battery life differs based on usage and environment.

This uninterruptible power supply has easy to replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. You can leave the uninterruptible power supply and connected equipment turned on for the replacement procedure.

Contact your IBM marketing representative or authorized reseller for information about replacement battery modules.

Refer to Removing the Battery Modules for removal instructions. For battery replacement, see Installing and Connecting the Batteries and Attaching the Front Battery Bezel.

This product contains sealed lead acid batteries. The battery modules must be recycled or disposed of properly. IBM has estab- lished a collection process for reuse, recycling, or proper disposal of used IBM sealed lead acid battery modules. For informa- tion on proper disposal of these modules, please contact IBM at 1-800-426-4333. Please have the model number listed on the uninterruptible power supply available before you call.

For information about the disposal of sealed lead acid batteries outside of the United States, contact your local IBM service or- ganization.

Replacing the Network Management Card

Refer to the Network Management Card CD for removal and replacement procedures.

Shipping and Service

Prepare the uninterruptible power supply for shipping:

Shut down and disconnect any equipment attached to the uninterruptible power supply. Shut down the uninterruptible power supply, and disconnect the uninterruptible power supply from the utility power outlet. Remove the front bezel and disconnect the batteries.

If the uninterruptible power supply requires service, do not return it to the dealer. Follow these steps:

1.Review the problems discussed in Troubleshooting to eliminate common problems.

2.If the problem persists, contact IBM.

$Note the model number of the uninterruptible power supply, the serial number, and the date purchased. If you call IBM Customer Service, a technician will ask you to describe the problem and attempt to solve it over the phone, if possible. If the uninterruptible power supply or one of its components is faulty, IBM will send you a replacement CRU for the un- interruptible power supply or the component.

$If the uninterruptible power supply or the component is under warranty, repairs are free. If not, there is a repair charge.

3.Pack the uninterruptible power supply or the faulty component in packaging sent by IBM, and use the return label to ship back to IBM. Pack the uninterruptible power supply properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.

Attention: Always disconnect the battery before shipping. The battery modules may remain in the uninterruptible power supply; they do not have to be removed.

16

Image 20
Contents IBM UPS 7500XHV IBM UPS 10000XHV Page Table of Contents Page Safety Page 18 kg 40 lb Kg 70-120 lb Kg 40-70 lb 55 kg 120 lb 10º Unpacking Removing the Battery ModulesIntroduction Positioning the Uninterruptible Power Supply Hardwiring the Uninterruptible Power SupplyAttach the mounting brackets # Secure the uninterruptible power supply in the rack Tower Configuration Startup Index DescriptionSelecting the Output Voltage via Terminal Mode Mode. See Troubleshooting Front Display PanelBattery Runtime Tables On Battery OperationDetermining On Battery Runtime UPS 7500XHV Model User Configurable Items Emergency Power Off EPO Option EPOReplacing the Battery Modules Shipping and ServiceStorage Replacing the Network Management CardHardware Maintenance Information Customer Replaceable Unit Part NumbersTroubleshooting Alarm Tone Before you call Replacement part handling Page Edition Notice Argentina Iram certification requirement

IBM UPS 7500XHV, IBM UPS 10000XHV specifications

IBM has always been at the forefront of technological advancements, and its line of uninterruptible power supplies (UPS) is no exception. Two noteworthy models in their UPS range are the IBM UPS 10000XHV and the IBM UPS 7500XHV. Both models are designed to provide reliable power protection for critical IT infrastructure, ensuring continuous operation even during power disturbances.

The IBM UPS 10000XHV is engineered for high-capacity applications, offering a robust power output of 10,000 VA. This model is particularly well-suited for data centers and enterprise environments that require dependable power support. One of the standout features of the 10000XHV is its advanced double-conversion technology. This technology ensures a consistent output voltage and frequency, effectively isolating connected equipment from any external power fluctuations. With an impressive battery runtime, this UPS allows organizations to maintain operational continuity, giving time for systems to transition to backup power sources or to shut down gracefully.

In addition to its impressive power output, the UPS 10000XHV incorporates real-time monitoring and management capabilities via its integrated LCD display. This feature allows users to easily track the UPS's performance metrics, battery status, and load levels, facilitating proactive maintenance and management. Furthermore, the UPS is designed with hot-swappable batteries, enabling replacement without interrupting the operation of connected devices.

On the other hand, the IBM UPS 7500XHV offers a slightly lower capacity at 7,500 VA, making it an ideal choice for moderately sized environments or less demanding applications. This model also leverages the same double-conversion technology, ensuring protection against power disruptions. The 7500XHV boasts an efficient design that minimizes energy consumption, a crucial factor for organizations looking to reduce operational costs while maintaining performance reliability.

Both models feature a range of connectivity options that facilitate seamless integration into various network environments. They support multiple communication protocols, enabling users to configure and manage UPS operations remotely through a centralized management system. In terms of safety, IBM has equipped these UPS units with advanced battery management technologies to extend battery life and optimize performance.

In conclusion, the IBM UPS 10000XHV and 7500XHV represent cutting-edge solutions for organizations seeking dependable power protection. With their advanced features and technologies, these UPS units are essential for safeguarding critical infrastructure against the unpredictable nature of power fluctuations, ultimately ensuring operational resilience in today’s digital landscape.