Brocade Communications Systems 6720 quick start Standalone installation for a Brocade VDX

Page 5

Recommendations for cable management

The minimum bend radius for a 50 micron cable is 2 inches under full tensile load and 1.2 inches with no tensile load.

Cables can be organized and managed in a variety of ways, for example, using cable channels on the sides of the cabinet or patch panels to minimize cable management. Following is a list of recommendations:

NOTE

You should not use tie wraps with optical cables because they are easily overtightened and can damage the optic fibers. Velcro-like wraps are recommended.

Plan for rack space required for cable management before installing the switch.

Leave at least 1 m (3.28 ft) of slack for each port cable. This provides room to remove and replace the switch, allows for inadvertent movement of the rack, and helps prevent the cables from being bent to less than the minimum bend radius.

For easier maintenance, label the cables and record the devices to which they are connected.

Keep LEDs visible by routing port cables and other cables away from the LEDs.

Items required for installation

The following items are required for installing, configuring, and connecting the Brocade VDX 6720 for use in a network and fabric:

Workstation with an installed terminal emulator, such as HyperTerminal

Unused IP address and corresponding subnet mask and gateway address

Serial cable (provided)

Ethernet cable

Brocade-branded SFP (1GbE) or SFP+s (10GbE) and compatible cables and/or direct-attach copper and optical cables

Access to an FTP server or Brocade-branded USB device for backing up the switch configuration (optional)

Standalone installation for a Brocade VDX 6720

Perform this task to install the Brocade VDX 6720 as a standalone unit.

1.Unpack the Brocade VDX 6720 and verify the items listed on “Items included with the Brocade VDX 6720.” Verify the items are present and undamaged.

2.Apply the adhesive rubber feet. Applying the rubber feet onto the switch helps prevent the switch from sliding off the supporting surface.

a.Clean the indentations at each corner of the bottom of the switch to ensure that they are free of dust or other debris that might lessen the adhesion of the feet.

b.With the adhesive side against the chassis, place one rubber foot in each indentation and press into place.

3.Place the switch on a flat, sturdy surface.

4.Provide power to the switch as described in “Providing power to the switch.”

Brocade VDX 6720 QuickStart Guide

5 of 12

Publication Number: 53-1002085-02

 

Image 5
Contents Brocade VDX Brocade Communications Systems, Incorporated Overview Installation and safety considerationsItems included with the Brocade VDX Electrical considerationsCabinet considerations Environmental considerationsRecommendations for cable management Standalone installation for a Brocade VDXItems required for installation Providing power to the switch Rack installation for a Brocade VDXVerifying operation Creating a serial connectionChanging the default account passwords Assigning permanent passwordsEnabling and disabling Brocade VCS mode Setting the switch IP addressUsing Dhcp to set the IP address Enabling VCS modeConnecting network devices Configuring switch portsDisabling VCS mode Installing and connecting an SFP+ transceiverBrocade VDX 6720 QuickStart Guide Connecting a network device to a fiber port Connecting to Ethernet or fast Ethernet hubsConnecting to workstations, servers, or routers Brocade VDX 6720 QuickStart Guide