Tripp Lite SU6000XFMR, BP240V7RT3U, BP240V10RT3U, SU10KXFMR, SU10KRT3UPM AC Output Voltage Diagram

Page 10

Connection continued

Installation—With Isolation Transformer

1Hardwire your isolation transformer’s UPS connector to your UPS’s input and output.

Remove the tops of the boxes covering the UPS’s and transformer’s input and output terminals. Pass the free end of the isolation transformer’s UPS connector through the UPS’s cover box’s knockout, then connect it to the UPS’s input and output terminals according to the labels on the wires and the terminals. Replace the top of the box covering the UPS’s input and output terminals.

1

2Hardwire your equipment to your isolation transformer’s

equipment output.

Pass your equipment’s power cable(s) through one of the transformer cover box’s left knockouts, then connect them to the transformer’s equipment output terminals. See the Output Voltage Diagram to determine which terminal connections will provide which voltages.

2

3Select your input voltage. Hardwire your isolation

transformer’s utility input to your utility power source.

Place a jumper between the 208V or 240V voltage select terminals to set the transformer’s input voltage. Connect one end of a power cable to your utility power source. Pass the cable’s other end through one of the transformer cover box’s center knockouts, then connect the cable to the utility input terminals. Replace the top of the transformer cover box.

3

AC OUTPUT VOLTAGE DIAGRAM

208V

240V

120V120V

Continue with Installation—All Applications (pg. 10)

10

Image 10
Contents SmartOnline Important Safety Warnings Single Unit Installation MountingBack-to-Back Installation Post Telecom Installation Features UPS Front Panel ControlsUPS Rear Panel Battery Pack Rear PanelIsolation Transformer Rear Panel Features Hardwire your UPS’s output to your equipment ConnectionAC Output Voltage Diagram DRY Contact Interface Diagram Connect communication cables to your UPS optionalTurn UPS output on Configure your UPS’s outputTurn input to the UPS on To turn the UPS and transformer OFFStartup Self-Test OperationFailed Self-Test Normal Operation On Battery AlarmOverload Messages Bypass Messages Shutdown MessagesService Service/Warranty and InsuranceYear Limited Warranty Specifications SU10KRT3U