Tripp Lite SU6000RT3UPM, BP240V7RT3U, BP240V10RT3U, SU10KXFMR, SU10KRT3UPM Specifications

Page 17

Specifications

Specifications are for UPS, Isolation Transformer, and one battery pack.

Model

SU6000RT3U

SU10KRT3U

Input

 

 

UPS Input Voltage

156V~276V Single Phase

156V~276V Single Phase

Transformer Input Voltage

200/208/220/230/240V

200/208/220/230/240V

Input Frequency

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

Input Current

22.6A

40A

Inrush Current

<150A

<200A

Power Factor (Full Load)

>0.97

>0.97

Efficiency (Full Load/On-Line)

>87%

>88%

UPS Circuit Breaker

40A

63A

Transformer Circuit Breaker

40A (2 pole)

63A (2 pole)

Output

 

 

VA

6000

10000

Watts (Power Factor: 0.7)

4200

7000

Waveform (On-Line)

Sinewave

Sinewave

Waveform (On-Battery)

Sinewave

Sinewave

Output Voltage (RMS)

120/200/208/220/230/240V

120/200/208/220/230/240V

Output Frequency

50/60 Hz

50/60 Hz

 

 

(± 0.2 Hz on battery)

(± 0.2 Hz on battery)

Voltage Regulation

±3%

±3%

Max. Harmonic Distortion

 

 

 

(Linear Full Load)

<3%

<3%

 

(Non-Linear Full Load)

<6%

<6%

Overload Capabilities

102% (continuous)

102% (continuous)

 

 

102%~125% (1 min.)

102%~125% (1 min.)

 

 

125%~150% (30 sec.)

125%~150% (30 sec.)

 

 

>150% (Immediate)

>150% (Immediate)

Short Circuit Capability

90A*

160A*

UPS Circuit Breaker

40A

63A

Transformer Circuit Breaker

30A (3 pole)

63A (3 pole)

Crest Factor

3:1

3:1

*The short circuit capability at 1ø 2W 120V for the SU6000RT3U is greater than 180A, and for the SU10KRT3U is greater than 320A.

Operation

 

 

On-Line Transfer Time

 

 

(Line to Battery, Battery to Line)

0 ms

0 ms

Audible Noise (Full Load @ 1 m)

<50 dBA

<55 dBA

Typical Backup Time (Single Battery Pack)

 

 

(Full Load)

10 min.

6 min.

(Half Load)

25 min.

15 min.

Indicators

Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).

Communications

Includes an RS-232 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Physical Specifications

 

 

(H × D × W)

51/8 × 17½ × 22½ in.

51/8 × 17½ × 22½ in.

 

(13 × 45 × 58 cm.)

(13 × 45 × 58 cm.)

Net Weight (UPS)

42 lb. (19.1 kg)

53 lb. (24.1 kg)

Net Weight (Transformer)

120 lb. (54.5 kg)

120 lb. (54.5 kg)

Net Weight (Battery Pack)

170 lb. (77.3 kg)

170 lb. (77.3 kg)

17

93-1979 (200207103)

Image 17
Contents SmartOnline Important Safety Warnings Mounting Single Unit InstallationBack-to-Back Installation Post Telecom Installation UPS Front Panel Controls FeaturesIsolation Transformer Rear Panel Battery Pack Rear PanelUPS Rear Panel Features Connection Hardwire your UPS’s output to your equipmentAC Output Voltage Diagram Connect communication cables to your UPS optional DRY Contact Interface DiagramTurn input to the UPS on Configure your UPS’s outputTurn UPS output on To turn the UPS and transformer OFFFailed Self-Test OperationStartup Self-Test Overload Messages On Battery AlarmNormal Operation Shutdown Messages Bypass MessagesYear Limited Warranty Service/Warranty and InsuranceService SU10KRT3U Specifications