Tripp Lite SU6K, SUIOK manual

Page 17

(Notc:Excludingisolation transformer)

 

Model

SU6K

SUlOK

&&

 

 

Inputvoltage

156V-280VSlngle Phase

156V-280VSinglePhase

Input Frequency

50/60 Hz t 3 Hz

50/60 Hz 2 3 Hz

 

(selectable, pg. 7)

(selectable. pg. 7)

Input Current

32A

50A

Inrush Current

<150A

<200A

Power Factor (Full Load)

~ 0 . 9 9

>0.99

Emciency (Full Load/On-Line)

>87Oh

>88%

Circuit Breaker

40A

63A

O U ~ D U ~

 

 

VA

6000

10000

Watts (Power Factor: 0.7)

4200

7000

Waveform (On-Line)

Slnewave

Slnewave

Waveform (On-Battery)

Sinewave

Slnewave

Output Voltage (RMS)

120/208/240V

120/208/240V

Output Frequency

50/60 Hz

50/60 Hz

 

(20.2 HZon battery)

(20.2 Hz on battery)

Voltage Regulation

k3Oh

23Oh

Max. Harmonic Distortion

 

 

(Llnear Full Load)

~ 3 %

<3%

(Non-Linear N l Load)

<6%

<6%

Overload Capabilttfes

102% (continuous)

102% (continuous)

 

102%-125Oh (1 min.)

102Y0-125~h(1 min.)

 

125%-150°h (30 sec.)

125%-150% (30 sec.)

 

>150% (2 sec.)

> 150% (2 sec.)

Short Clrcuit Capability

90AD

160A'

Circuit Breakers

3 x 32A

3 x 63A

Crest Factor

3:1

3: 1

Ih e short clrcult capability of 10 2W l2OVfor the6kVA lsgreater than ISOA,andfor the 1OkVA Ls .greater Lhnn 320A.

Battery & Charger

Battery-

12V/7AH

12V/7AH

Battery Quantity

20

40

Protection

3OA/600Vfuse

30A/600Vfuse

RechargeVoltage

274VDC

274VDC

Recharge Rate (to90%)

8hrs.

4 hrs.

Low Battery Shutdown

2OOVDC

2OOVDC

TyplcalBackupTime

 

 

(Full Load)

8 mln.

10 min.

(Half Load)

2 5 min.

31 min.

Operation

 

 

On-Line Transfer Ttme

 

 

(Une to Battery. Battery to Line)

0 ms

0 ms

AudIble Nolse (Full Load @ 1 meter)

<50 dBA

c55 dBA

Indicator#

 

 

Both models Include an LCD Display and LEDs (AC Line In. AC to DC. DC to AC. AC Output. Battery Back-Up. Bypass).

Communications

Both models lnclude an RS-232 DB9 female connector. an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

~mectlons

InputTe~minalBlock

40A

60A

OutputTerminalBlock

4OA

60A

Extended Battery Input Socket

40A

40A

phwical SpeciBcntiom

 

 

Dimensions of UPS and Battery Cabinet

 

( H x D x W J

22-1/5x24-4/5x 11in.

22-1/5x24-4/5x 11in.

 

(56.5 x 6 3 x 28 cm.)

(56.5 x 6 3 x 28 cm.)

Net Weight (UPS)

286 Ib. (130 kg)

242 Ib. (110 kg)

Net Weight (Battery Cabinet)

 

278 Ib. (126 kg)

Image 17
Contents TRIPPaUTEPOWER PRorEcTloN UPS Location Warnings Battery WarningsUPS Connection Warnings Equipment Connection WarningsUPS System Front PanelSubp Rear Panels Overational Mode Selection Inverter Operationdip Switch Settings Suiokpm ShownInDut Voltage Selection Invut Frequencv SelectionCable Connection for 6kVA or lOkVA Output 6kVAshown UPS LocationInputand Output Connection SUBPSUlOKBPSUlOKPM External Battery Pack ConnectionInitial Bavery Charging Optional BA77ERY Condition VerificationTurning the UPS on Turning the UPS OFFSltll~lOlllll~ SELF-TESTINGOperation on Overload LCD Display Select SwitchOperation on BYPASS-VOLTAGE OUT of Range Operationundershutdown Operation of Manual Bypass SwitchBatery Charge WARNlNGS AS-400 Interface RS-232 InterfaceHardware Pin assienmentDRY Contact Interface Remote Emergency Power OFFPin assipnment Pin assignment lSU6K ShownService DLs SU6K