Tripp Lite SUIOK Inverter Operationdip Switch Settings Suiokpm Shown, InDut Voltage Selection

Page 6

INVERTER OPERATIONDIP SWITCH

SETTINGS (SUIOKPM SHOWN)

Using a small tool, set the four Inverter Opera- tion DIP Switches (located on the rear panel of your UPS, see pg. 4-5for location) to match your input voltage, input frequency a n d desired operational mode.

InDut Voltage Selection

( D ~ Pswitch& # 1 ~r #2)

(Input Voltage Select Terminal Block)

These DIP switches and the Input Terminal Select Block must BOTH be set to match your input voltage. Your UPS WILL NOT CONVERT the voltage.

 

 

Input Voltage

J n ~ uVolt=

DIP Switch Position

Select Terminal Block

240V #1 DOWN & #2 DOWN

Invut Frequencv Selection

(DIP Switch #3)

Your Input Frequency setting MUST match your input frequency. Your UPS WILL NOT CONVERT the frequency.

Input Frequency DIP Switch Position

6 0 Hz

#3DOWN

Overational Mode Selection

(DIP Switch #4)

The "On-Line"Mode provides on-line operation with zero transfer time. The "Economy" Mode provides line-interactive operation for increased efficiencywhen on-line protection is unnecessary, thus reducing operating costs without affecting your UPS'S output reliability during a power outage.

Input Frequency

DIP Switch Position

On-Line

#4 UP

Economy

#4 DOWN

Image 6
Contents TRIPPaUTEPOWER PRorEcTloN UPS Connection Warnings Battery WarningsUPS Location Warnings Equipment Connection WarningsFront Panel UPS SystemSubp Rear Panels InDut Voltage Selection Inverter Operationdip Switch Settings Suiokpm ShownOverational Mode Selection Invut Frequencv SelectionUPS Location Inputand Output ConnectionCable Connection for 6kVA or lOkVA Output 6kVAshown External Battery Pack Connection SUBPSUlOKBPSUlOKPMTurning the UPS on BA77ERY Condition VerificationInitial Bavery Charging Optional Turning the UPS OFFSELF-TESTING Sltll~lOlllll~LCD Display Select Switch Operation on BYPASS-VOLTAGE OUT of RangeOperation on Overload Operation of Manual Bypass Switch Batery Charge WARNlNGSOperationundershutdown Hardware RS-232 InterfaceAS-400 Interface Pin assienmentPin assipnment Remote Emergency Power OFFDRY Contact Interface Pin assignment lSU6K ShownService DLs SU6K