Tripp Lite Audio/Video On-Line UPS System owner manual Check the utility line for wiring problems

Page 11

Troubleshooting

The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties.

Lights (On/Flashing) and Condition

Solution

On: REPLACE BATT

Let the UPS system charge for at least

Condition: Replace Battery

12 hours and perform a self test using

 

the "ON/Test Switch" as described on

 

page 7. If the light continues to stay on,

 

contact Tripp Lite for service.

 

 

On: BATT LOW, ON BATT

Prepare for imminent UPS shutdown.

Condition: Battery Low

 

 

 

On: BYPASS, LINE, LOAD, OVERLOAD

Reduce the load the UPS supports.

Condition: On Bypass due to Overload

 

 

 

Flashing: OVERLOAD

Remove the cause of the short circuit

Condition: Short Circuit

from the UPS output.

 

 

On: FAULT

Check the utility line for wiring problems

Condition: Wiring Fault

such as reversed line and neutral or a

 

missing ground.

 

 

On: FAULT, 100%

Restart the UPS. If the problem persists,

Condition: Battery Voltage too High

contact Tripp Lite for repairs.

 

 

On: FAULT, BYPASS, LINE, 50%

Restart the UPS. If the problem persists,

Condition: On Bypass due to

contact Tripp Lite for repairs.

High Output Voltage

 

 

 

On: FAULT, BYPASS, LINE

Restart the UPS. If the problem persists,

Flashing: 50%

contact Tripp Lite for repairs.

Condition: On Bypass due to

 

Low Output Voltage

 

 

 

On: FAULT, BYPASS, LINE, 25%

Condition: On Bypass due to High Bus Voltage

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

On: FAULT, BYPASS, LINE

Flashing: 25%

Condition: On Bypass due to Low Bus Voltage

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

11

Image 11
Contents Audio/Video Important Safety Instructions Post Mounting Post Mounting Tower Mounting InstallationImporant Safety Instructions USB and RS-232 Serial Communications Front Panel Switches Basic Operation Rear Panel Communications Check the utility line for wiring problems Condition Input Abnormal Procedure Storage Page 200507084