Tripp Lite SU80K3/3INTPM, SU80K3/3PM, SU50K3/3INTPM, SU50K3/3PM Multiple UPS Operation Parallel

Page 13

Multiple UPS Operation (Parallel) (continued)

Maintenance Bypass Mode

In this mode, the Manual Maintenance Procedure (On Bypass) has been performed in order to pass-through filtered AC input power (from a reserve AC input source) to connected equipment loads while allowing maintenance on the UPS power module. (Note: since the power module's inverter is bypassed in this mode, the UPS will not be able to switch to Back-Up Mode in the event of a power failure.) After the Manual Maintenance Procedure (Off Bypass) has been performed, the power module automatically reactivates the inverter and switches back to the mains AC input source to support connected equipment loads.

Optional Parallel Configuration (Hot Standby Redundancy and Common Battery)

Hot Standby Redundancy

In this configuration, one or more UPS power modules serve in a “hot standby” role in order to increase the availability of connected equipment by reducing the chances that a failure of one UPS will impact output power. During normal conditions, the UPS in a “hot standby” role does not support the connected equipment load; however, during a UPS failure, the UPS in a “hot standby” role automatically supports (through activation of the static switch) the connected equipment load. The output of the UPS in a “hot standby” role is connected to the reserve power input of another UPS power module. In order to reduce installation costs, users can use one UPS power module in a “hot standby” role for up to seven additional UPS power modules within a parallel configuration.

13

Image 13
Contents SmartOnline Phase 50kVA & Above UPS Location Warnings Battery WarningsUPS Connection Warnings Equipment Connection WarningsRegulatory Compliance Identification Numbers Buttons Breakers, Switches & FusesLCD Display LED PanelCommunication Interface Installation ChecklistConnection Checklist Floor Weight Loading TableTorque Specifications Are removed Normal Mode Single UPS Operation Turn off open the Reserve Input Breaker Multiple UPS Operation Parallel Multiple UPS Operation Parallel Multiple UPS Operation Parallel Start-Up Procedure Shutdown Procedure Main Menu Parameter Setting Sub-Menu Event Log Sub-Menu System Control Sub-MenuOther Information Sub-Menu Dry-Contacts Remote Emergency Power Off EPO RS-232 Port/Ethernet Port/SNMP Card Slot Ethernet PowerGenerator Contact UPS Parallel Communication Ports RS-485 PortsLimited Warranty 200503068