Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline
Service personnel should familiarize themselves with symbols marked on the UPS:
This symbol indicates a protective grounding terminal (a terminal which must be connected to earth ground prior to making any other connection to the equipment).
This symbol indicates a terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicates the word “phase”.
UPS Location Warnings
•Install your UPS indoors, away from heat, direct sunlight, dust, and excess moisture or other conductive contaminants.
•Install your UPS away from flammable liquids and gases. Do not let the unit come in contact with water or other liquids.
•Install your UPS in a structurally sound area. Your UPS is extremely heavy. Flooring must be able to support the weight of all UPS modules. Take care when moving and lifting the unit.
•Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C) with humidity within a range of 0 to 95%
•Leave adequate space around all sides of the UPS for proper ventilation: at least 40 inches (100 cm) from front panel and 20 inches (50 cm) from top, rear and side panels. Do not cover ventilation openings on the unit.
•Do not install the UPS near magnetic storage media, as this may result in data corruption.
UPS Connection Warnings
•The power supply for this unit must be
•The UPS must be isolated prior to any connection or maintenance. A
•Due to high leakage current, a ground connection is essential.
Equipment Connection Warnings
•Do not use Tripp Lite UPS Systems in life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device.
•The UPS is designed to power computer equipment. Do not use the UPS with purely inductive or capacitive loads.
•The UPS System includes its own energy source (external battery). The output terminals may be live even when the UPS is not connected to an AC supply.
Battery Warnings
•Your UPS does not require routine maintenance. Do not open your UPS for any reason. There are no
•Risk of electrocution is possible when battery module is connected to the power module. Qualified service personnel must disconnect the batteries prior to maintenance.
•Because the batteries present a risk of electrical shock and burn from high
•Do not dispose of the batteries in a fire. The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in the USA only, refer to these sources for recycling information:
2