Tripp Lite SU50K3/3PM, SU80K3/3PM, SU80K3/3INTPM, SU50K3/3INTPM Other Information Sub-Menu

Page 19

LCD Display Navigation (continued)

“Other Information” Sub-Menu

This sub-menu allows managers to view a variety of additional UPS System information.

Note: a UPS Status Code is displayed in the upper-right corner of the screen in the following display. Use the chart below to determine what the UPS Status Code indicates.

UPS

Status

Code

Code Displayed

UPS Status

 

 

0

Bypass Output Inhibited

2

Load on Reserve

10

Rectifier AC Soft-Start

18

Performing Inverter Test

20

Load on Inverter

22

Load on Inverter at Backup Mode

24

Low Battery

26

Low Battery Shutdown

28

Short-Circuit Shutdown

30, 58

Manual Bypass On

32

P.L.L. Abnormal

34

Inverter Fault Shutdown

36

Inverter Overload Shutdown

38

Remote Shutdown

40, 42, 44

Inverter Output Voltage Abnormal

46

EPO Event Shutdown

50

DC BUS Overvoltage Protection Shutdown

52, 54, 56

Inverter Fuse Open

60, 62, 64

Inverter Over-temperature Shutdown

66

Output Transformer Over-temperature Shutdown

 

 

LCD Navigation Key

Action

Buttons to Push

Scroll Up Through Menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scroll Down Through Menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter or Select a Menu Choice

 

 

 

 

 

 

 

 

 

 

 

 

Exit Current Menu and Return to Previous Menu

 

 

 

and

 

simultaneously

 

 

 

 

 

 

 

 

 

19

Image 19
Contents SmartOnline Phase 50kVA & Above Equipment Connection Warnings Battery WarningsUPS Location Warnings UPS Connection WarningsRegulatory Compliance Identification Numbers LED Panel Breakers, Switches & FusesButtons LCD DisplayCommunication Interface Installation ChecklistConnection Checklist Floor Weight Loading TableTorque Specifications Are removed Normal Mode Single UPS Operation Turn off open the Reserve Input Breaker Multiple UPS Operation Parallel Multiple UPS Operation Parallel Multiple UPS Operation Parallel Start-Up Procedure Shutdown Procedure Main Menu Parameter Setting Sub-Menu Event Log Sub-Menu System Control Sub-MenuOther Information Sub-Menu Dry-Contacts Remote Emergency Power Off EPO RS-232 Port/Ethernet Port/SNMP Card Slot Ethernet PowerGenerator Contact UPS Parallel Communication Ports RS-485 PortsLimited Warranty 200503068