Network interfaces support simultaneous communications via
UPS interface supports
NEMA
Dataline surge suppression protects dialup, DSL or network Ethernet connection
Front panel LEDs offer current monitoring, voltage regulation and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations; no
Specifications
SYSTEM OVERVIEW
Voltage compatibility | 120V (110, 100V user selectable) |
|
|
Frequency | 60 Hz |
compatibility |
|
|
|
OUTPUT |
|
Output VA | 750 |
|
|
Output watts | 500 |
|
|
Output nominal | 120, 110, 100V AC |
voltage |
|
|
|
Output voltage | LINE MODE: Sine wave line voltage 120V (+6%, |
regulation | Sine wave output 120V, 110V, 100V |
|
|
Output frequency | LINE MODE: Passes line frequency of |
regulation |
|
|
|
Outlet quantity / type | 8 NEMA |
|
|
INPUT |
|
Maximum input amps | 5.4A (120V), 5.8A (110V), 6.4A (100V) |
|
|
Input connection type | NEMA |
|
|
Input cord length | 6 ft. |
|
|
Recommended | 120V 15A |
Electrical Service |
|
|
|
BATTERY |
|
Full load runtime | 10 minutes (500w) expandable |
|
|
Half load runtime | 27 minutes (250w) expandable |
|
|
Expandable battery | Runtime is expandable with |
runtime |
|
|
|
DC system voltage | 24VDC |
|
|
Battery recharge rate | 4.5 hour recharge to 90% (max) |
|
|
Replacement Battery | |
Cartridge |
|
|
|
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 127 and 145V (120V), 116 and 133 (110V), 111 and 121 (100V) are reduced by 12%
Input voltages between 95 and 108 (120V), 87 and 99 (110V), 83 and 93 (100V) are boosted by 14%