Tripp Lite SU10000RT3U2TF warranty Battery, Voltage Regulation, Leds Alarms & Switches, Physical

Page 3

BATTERY

Full load runtime

4 min. (10,000VA/8000W)

 

 

Half load runtime

10 min. (5000VA/4000W)

 

 

Connects to UPS via

Included 3-wire DC cable

 

 

DC system voltage

240VDC

 

 

Typical battery

4-6 years

lifespan

 

 

 

Battery recharge rate

Less than 8 hours to 90% (included battery set only)

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected nominal voltage at all times

Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within 2% of selected nominal

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC, regulating output within 2% of selected nominal

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily rotates for better viewing in rackmount or tower configurations.

Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete

Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions

SURGE / NOISE SUPPRESSION

AC suppression response time

EMI / RFI AC noise suppression

PHYSICAL

Instantaneous

Yes

Shipping weight (lbs)

402

 

 

Shipping weight (kg)

181

 

 

Shipping Dimensions

49.3 x 23 x 31.5

(HWD/in)

 

 

 

Shipping Dimensions

125.1 x 58.4 x 80

(HWD/cm)

 

 

 

Unit weight (lbs)

Power Module (54.8), Step-down Transformers (60), Battery Pack (158.7)

 

 

Unit weight (kg)

Power Module (24.7), Step-down Transformers (27), Battery Pack (71.4)

 

 

Unit Dimensions

Power Module 5.14 x 17.5 x 25, Step down transformers 3.5 x 17.5 x 20.8, Battery Pack 5.16 x 17.5 x 25 (Installed

(HWD/in)

depth of power module extends to 32.5 inches once detachable PDU backplate is installed)

 

 

Unit Dimensions

Power Module 13.3 x 44.4 x 63.5, Step down transformers 8.9 x 44.5 x 52.7, Battery Pack 13.4 x 40.6 x 63.5 (Installed

(HWD/cm)

depth of power module extends to 82.6 cm once detachable PDU backplate is installed)

 

 

Material of

Steel

construction

 

 

 

Form factors

Rack (10U)

supported

 

 

 

Cooling method

Fan

 

 

Battery Access

User replaceable, hot swappable external battery pack

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage Temperature

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Image 3