Input connection type
Input cord length
Recommended Electrical Service
Maximum input amps / watts
BATTERY
DC INPUT: Set of 2 DC
DC INPUT: User supplies cabling. 0 gauge or larger (see manual). AC INPUT: hardwire
DC INPUT: Requires 12V DC input source capable of delivering 145A for the required duration (when used at full continuous capacity - DC requirements increase during
DC INPUT: Full continuous load - 145A at 12V DC. AC INPUT: 35 amps at 120V AC with full inverter and charger load (15A max
Expandable battery runtime
DC system voltage
Battery recharge rate
Runtime is expandable with any number of user supplied wet or gel type batteries
12V
19A / 75A (selectable)
LEDS ALARMS & SWITCHES
Front panel LEDs
Switches
Set of 6 LEDs offer continuous status information on load percentage (6 levels reported) and battery charge level (7 levels reported). See manual for sequences.
SURGE / NOISE SUPPRESSION
AC surge | 450 joules AC surge suppression included |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 44.6 |
|
|
Shipping weight (kg) | 20.2 |
|
|
Shipping | 13.5 x 15 x 21.5 |
Dimensions (HWD/in) |
|
|
|
Shipping | 34.3 x 38.1 x 54.6 |
Dimensions |
|
(HWD/cm) |
|
|
|
Unit weight (lbs) | 40.2 |
|
|
Unit weight (kg) | 18.3 |
|
|
Unit Dimensions | 7.25 x 8.5 x 17 |
(HWD/in) |
|
|
|
Unit Dimensions | 43.8 x 21.6 x 41.3 |
(HWD/cm) |
|
|
|
Material of | Polycarbonate |
construction |
|
|
|
Form factors | Mounting slots enable permanent placement of inverter on any horizontal surface (see manual for additional mounting |
supported | information) |
|
|
Cooling method | |
|
|
Style | |
|
|
ENVIRONMENTAL |
|
Relative Humidity | |
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer to battery power
16.6milliseconds (typical - compatible with many computers - verify transfer time compatibility of loads for UPS applications)
In AC "auto" mode, inverter/charger switches to battery mode as line voltage drops to 75V (user adjustable to 85, 95, 105V - see manual)