Tripp Lite Extended-Run Single-Phase Battery Cabinet Specifications, Dimensions and Floor Loading

Page 14

7.Specifications

7.1Dimensions and Floor Loading

Battery Cabinet Model

Shelves

Dimensions

Weight

Floor Loading

(Width x Depth x Height)

 

 

 

 

BP240V557C-1PH

3

32.4 x 28.8 x 60 inches

1250 lb

193 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(567.5 kg)

(943 kg/m2)

 

 

BP240V787C-1PH

3

32.4 x 28.8 x 60 inches

1850 lb

285 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(840 kg)

(1395 kg/m2)

 

 

BP240V1037C-1PH

3

32.4 x 28.8 x 60 inches

1983 lb

306 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(900.3 kg)

(1496 kg/m2)

 

 

BP240V1407C-1PH

3

32.4 x 28.8 x 60 inches

2463 lb

380 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(1118.2 kg)

(1857 kg/m2)

 

 

BP192V557C-1PH

3

32.4 x 28.8 x 60 inches

1130 lb

174 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(513 kg)

(852 kg/m2)

 

 

BP192V787C-1PH

3

32.4 x 28.8 x 60 inches

1628 lb

251 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(739.1 kg)

(1228 kg/m2)

 

 

BP192V1037C-1PH

3

32.4 x 28.8 x 60 inches

1773 lb

274 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(804.9 kg)

(1337 kg/m2)

 

 

BP192V1407C-1PH

3

32.4 x 28.8 x 60 inches

2070 lb

319 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(939.8 kg)

(1561 kg/m2)

 

 

BP192V557C-16K

3

32.4 x 28.8 x 60 inches

1130 lb

174 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(513 kg)

(852 kg/m2)

 

 

BP192V787C-16K

3

32.4 x 28.8 x 60 inches

1628 lb

251 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(739.1 kg)

(1228 kg/m2)

 

 

BP192V1037C-16K

3

32.4 x 28.8 x 60 inches

1773 lb

274 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(804.9 kg)

(1337 kg/m2)

 

 

BP192V1407C-16K

3

32.4 x 28.8 x 60 inches

2070 lb

319 lb/ft2

(82.3 x 73.2 x 152.4 cm)

(939.8 kg)

(1561 kg/m2)

 

 

7.2 Recommended Torque

Battery Cabinet Model

Terminal Type

Torque

BP240V557C-1PH

10-32 Threaded Insert

25 in·lb (2.8 N·m)

 

 

 

BP240V787C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP240V1037C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP240V1407C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V557C-1PH

10-32 Threaded Insert

25 in·lb (2.8 N·m)

 

 

 

BP192V787C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V1037C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V1407C-1PH

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V557C-16K

10-32 Threaded Insert

25 in·lb (2.8 N·m)

 

 

 

BP192V787C-16K

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V1037C-16K

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

BP192V1407C-16K

1/4-20 Threaded Insert

110 in·lb (12.4 N·m)

 

 

 

14

Image 14
Contents Extended-Run Single-Phase Battery Cabinet Features IntroductionImportant Safety Instructions Installation and Location WarningsBattery Warnings Transportation Battery Cabinet InstallationPreparation Mechanical CheckPreliminary Electrical Check Internal Wiring TypicalBattery Cabinet Placement Final Electrical Check Battery Charger Electrical Connection Select ModelsElectrical Connection Daisy-Chaining Multiple Battery Cabinets 10aInitial Charge Operation and ChargingDetermine Charging Voltages Operational CheckFuse Replacement MaintenanceMaintenance Schedule Quarterly Check Semiannual CheckDiagrams Battery Cabinet Diagram 3 ShelvesDiagrams Battery and Breaker DiagramsIntegrated Battery Charger Select Models Recommended Torque SpecificationsDimensions and Floor Loading Service Storage and ServiceWarranty StorageTh Street, Chicago, IL 60609 USA

Extended-Run Single-Phase Battery Cabinet specifications

The Tripp Lite Extended-Run Single-Phase Battery Cabinet serves as an essential backup power solution, designed for environments where prolonged uptime is critical. This compact and efficient battery cabinet is tailored primarily for use with Tripp Lite's SmartPro line of UPS systems, delivering reliable power protection and extended runtime capabilities for critical equipment.

One of the main features of the Tripp Lite Extended-Run Battery Cabinet is its impressive scalability. This unit is designed to expand the runtime of UPS systems significantly, enabling users to keep their systems operational during extended power outages. With the ability to house additional batteries, it allows organizations to customize their backup power based on specific needs. The cabinet can accommodate multiple battery packs, providing flexibility and ease of use.

In terms of design, the battery cabinet is engineered for optimal performance. Its robust construction ensures durability and the ability to withstand the rigors of various industrial settings. The cabinet also features a compact footprint, enabling seamless integration into server rooms, data centers, and other critical environments without consuming excessive space.

Advanced technologies are evident in the cabinet's smart charging capabilities. The integrated management features enable precise monitoring and control, ensuring that batteries are efficiently charged and maintained. The intelligent battery management system maximizes battery life while minimizing maintenance requirements, making it suitable for organizations that rely on continuous operation.

Moreover, the Tripp Lite Extended-Run Battery Cabinet is equipped with a user-friendly interface, allowing for straightforward installation and configuration. Visual indicators provide clear status updates, ensuring users can monitor battery health and performance with ease. The seamless communication with the UPS systems further enhances the overall user experience, providing real-time updates and alerts.

In conclusion, the Tripp Lite Extended-Run Single-Phase Battery Cabinet represents a dependable and scalable power solution for businesses that demand lasting performance. Its combination of advanced technology, rugged design, and user-friendly features makes it an ideal choice for safeguarding critical equipment against power interruptions. This battery cabinet not only enhances the reliability of UPS systems but also provides peace of mind knowing that essential operations can continue uninterrupted during extended outages.