Tripp Lite Extended-Run Single-Phase Battery Cabinet owner manual Important Safety Instructions

Page 3

2. Important Safety Instructions

SAVE THESE INSTRUCTIONS

All sections of this manual contain instructions and warnings that must be followed during the installation and operation of the battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to move, install or connect your battery cabinet. Failure to comply may invalidate the warranty and cause serious property damage and/or personal injury.

DANGER! LETHAL HIGH VOLTAGE HAZARD!

All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage.

Installation and Location Warnings

Install the battery cabinet in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses, conductive contaminants, dust and direct sunlight.

Install the battery cabinet in a level, structurally sound location.

The battery cabinet is extremely heavy; be extremely careful when moving or lifting the unit.

Operate the battery cabinet at indoor temperatures between 32° F and 104° F (0° C and 40° C) only. For best results, maintain an indoor temperature of 77° F (25° C).

Leave adequate space around all sides of the battery cabinet for proper ventilation. Do not block, cover or insert objects into the external ventilation openings of the battery cabinet.

Do not place any object on the battery cabinet, especially containers of liquid.

Do not attempt to stack the battery cabinet. Attempting to stack the battery cabinet may cause permanent damage and create a potential for serious personal injury.

Do not attempt to unpack or move the battery cabinet without assistance. Use appropriate handling equipment rated to bear the weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.)

For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact equivalent, with a non-conductive extinguishing agent) near the battery cabinet.

Connection Warnings

The battery cabinet contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.

The battery cabinet has its own energy source. The output terminals may be live even when the battery cabinet is not connected to a UPS system.

The battery cabinet must be suitably grounded according to all applicable electrical wiring regulations.

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.

De-energize all input and output power sources before installing cables or making electrical connections.

Use flexible cable of sufficient length to permit battery cabinet servicing.

Use ferrule caps to cover termination cables and prevent frayed ends from shorting on terminal blocks. Use cabling rated VW-1, FT-1 or better. Use cable sleeves and connector clamps.

Confirm that all cables are marked correctly according to their purpose, polarity and diameter.

Observe proper polarity by connecting negative to negative and positive to positive. Failure to observe proper polarity may damage the batteries and create a serious risk of personal injury and property damage.

Wiring should be performed by trained, qualified electricians only.

If the battery cabinet does not include the shunt trip option, the final installation must include an easy-access disconnect device between the battery and the load. The disconnect device must be suitably rated in accordance with applicable electrical codes and the battery cabinet rating.

Do not connect the integrated battery charger (included with “C” models only) to the UPS system output. The integrated battery charger requires a separate AC supply circuit.

3

Image 3
Contents Extended-Run Single-Phase Battery Cabinet Introduction FeaturesInstallation and Location Warnings Important Safety InstructionsBattery Warnings Mechanical Check Battery Cabinet InstallationPreparation TransportationInternal Wiring Typical Battery Cabinet PlacementPreliminary Electrical Check Battery Charger Electrical Connection Select Models Electrical ConnectionFinal Electrical Check 10a Daisy-Chaining Multiple Battery CabinetsOperational Check Operation and ChargingDetermine Charging Voltages Initial ChargeSemiannual Check MaintenanceMaintenance Schedule Quarterly Check Fuse ReplacementBattery Cabinet Diagram 3 Shelves DiagramsBattery and Breaker Diagrams DiagramsIntegrated Battery Charger Select Models Specifications Dimensions and Floor LoadingRecommended Torque Storage Storage and ServiceWarranty ServiceTh Street, Chicago, IL 60609 USA

Extended-Run Single-Phase Battery Cabinet specifications

The Tripp Lite Extended-Run Single-Phase Battery Cabinet serves as an essential backup power solution, designed for environments where prolonged uptime is critical. This compact and efficient battery cabinet is tailored primarily for use with Tripp Lite's SmartPro line of UPS systems, delivering reliable power protection and extended runtime capabilities for critical equipment.

One of the main features of the Tripp Lite Extended-Run Battery Cabinet is its impressive scalability. This unit is designed to expand the runtime of UPS systems significantly, enabling users to keep their systems operational during extended power outages. With the ability to house additional batteries, it allows organizations to customize their backup power based on specific needs. The cabinet can accommodate multiple battery packs, providing flexibility and ease of use.

In terms of design, the battery cabinet is engineered for optimal performance. Its robust construction ensures durability and the ability to withstand the rigors of various industrial settings. The cabinet also features a compact footprint, enabling seamless integration into server rooms, data centers, and other critical environments without consuming excessive space.

Advanced technologies are evident in the cabinet's smart charging capabilities. The integrated management features enable precise monitoring and control, ensuring that batteries are efficiently charged and maintained. The intelligent battery management system maximizes battery life while minimizing maintenance requirements, making it suitable for organizations that rely on continuous operation.

Moreover, the Tripp Lite Extended-Run Battery Cabinet is equipped with a user-friendly interface, allowing for straightforward installation and configuration. Visual indicators provide clear status updates, ensuring users can monitor battery health and performance with ease. The seamless communication with the UPS systems further enhances the overall user experience, providing real-time updates and alerts.

In conclusion, the Tripp Lite Extended-Run Single-Phase Battery Cabinet represents a dependable and scalable power solution for businesses that demand lasting performance. Its combination of advanced technology, rugged design, and user-friendly features makes it an ideal choice for safeguarding critical equipment against power interruptions. This battery cabinet not only enhances the reliability of UPS systems but also provides peace of mind knowing that essential operations can continue uninterrupted during extended outages.