Tripp Lite 200310080 AC Input/Output Connection, Connection for Models with Cords and Receptacles

Page 11
Dual-Source Input/Output*
• AC IN 1 will only provide line power to AC OUT 1.
• AC IN 2 will only provide line power to AC OUT 2.
• Inverted battery power is supplied to bothAC OUT 1 andAC OUT 2.
AC IN 1
AC IN 2
AC OUT 2
AC OUT 1

AC Input/Output Connection

To avoid overloading your Inverter/Charger, match the power requirements of the equipment you plan to run at any one time (add their total watts) with the output wattage capacity of your Inverter/Charger model (see Specifications). Do not confuse “continuous” wattage with “peak” wattage ratings. Most electric motors require extra power at start-up (“peak wattage”) than required to run continuously after start- up, sometimes over 100% more. Some motors, such as in refrigerators and pumps, start and stop intermittently according to demand, requir- ing “peak wattage” at multiple, unpredictable times during operation. DoubleBoostFeature: Tripp Lite Inverter/Chargers deliver up to twice their nameplate rated wattage for up to 10 seconds,* providing the extra power needed to cold start heavy-duty tools and equipment. OverPowerFeature: Tripp Lite Inverter/Chargers deliver up to 150% of their name-plate rated wattage for up to 1 hour,* providing plenty of reserve power to reliably support tools and equipment longer.

* Actual duration depends on model, battery age, battery charge level and ambient temperature.

Connection for Models with Cords and Receptacles

Plug the Inverter/Charger’s AC input cord into an outlet providing 120V AC, 60Hz. power. Make sure that the circuit you connect your Inverter/Charger to has adequate overload protection, such as a circuit breaker or a fuse. Plug your equipment into the Inverter/Charger’s AC receptacles. Any equipment you connect to it will benefit from your Inverter/Charger’s built-in ISOBAR® surge protection!

Warning! Consult a qualified electrician and follow all applicable electrical codes and requirements for hardwire connection. Disconnect both DC input and AC utility supply before attempting hardwiring. Use wire type THHN or equivalent with minimum temperature rating of 90°C.

Connection for Models with Hardwire Terminals

Output Connection Requirement: UL requires that the output terminals of all hard- wire Inverter/Charger models must be connected to UL-listed GFCI receptacles (required receptacle manufacturer/model series: Hubbell GF8300HGW or Leviton 6598).

Single Input/Output Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: Connect incoming wires to the hot (brown)

2

 

, neutral (blue)

3

 

and ground* (green) terminals

1

.

 

 

 

 

 

 

 

 

 

 

 

 

Output: Connect outgoing wires to the hot (black)

 

4

, neutral (white)

5

and ground* (green) terminals

 

 

 

 

 

 

 

1

.

 

 

 

 

 

 

“FOR USE WITH COPPER WIRE ONLY” HOT IN

2

NEUTRAL

IN

3

GROUND

IN

GROUND

OUT

 

1

HOT OUT

 

4

NEUTRAL

OUT

5

Note: Ground Bond Connection, Supplied

Replace cover plate and tighten screws.* If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must be bonded to the main ground lug on the unit. In any case, the incoming conduit must be bonded to earth or vehicle ground, and the incoming conduit must be bonded to the outgoing conduit.

Dual Input/Output Models

Select models provide higher bypass power capacity by enabling connection of two separate AC input sources. These two sources can be either two 120V legs split from a single 240V service (with opposite phase on each 120V leg) or two different 120V sources. The Inverter/Charger will only supply 120V output power and WILL NOT provide 240V output even if it is connected to inputs from a split 240V service when in inverter mode. When the Inverter/Charger is receiving AC power, it can supply connected loads with up to 20 amps of power on each circuit**. When the Inverter/Charger is not receiving AC power, and has switched to inverting DC battery power, it can supply connected loads with various amper- age levels (see “Maximum Output AC Current” in Specifications section) on BOTH circuits. Dual input/output models provide for either: a) dual-source inputs and outputs; b) single- source input and output; or c) single-source input and dual-source outputs (with AC OUT 2 power only available in invert mode). Connect user-supplied wire and conduit to the con- nections as follows:

Input: Connect incoming wires to hot (black for AC IN 1, black for AC IN 2), neutral (white for AC IN 1, white for AC IN 2) and ground (green/yellow) wires.

Output: Connect outgoing wires to hot (black for AC OUT 1, black for AC OUT 2), neutral (white for AC OUT 1, white for AC OUT 2) and ground (green/yellow) wires.

Single-Source Input/Output*

• If you only have a single 120V AC input source, you must connect it to AC IN 1.

• If you only have a single output circuit, you must connect it to

AC OUT 1

*Single-Source or Dual-Source Input/Output Connection: As well as supplying power to connected loads, AC IN 1 also provides power to the battery charger. If you connect a large load to AC OUT 1, you should select a more limiting battery charger setting (see “Select Battery Charger-Limiting Points”) or you may experience continual nuisance tripping of the electrical service (source) circuit breaker which supplies AC IN 1. The Inverter/Charger will only measure the current at AC OUT 1 to automatically limit the charger rate. AC IN 2 input current is passed through to AC OUT 2 with- out measurement. Single-Source Input/Dual-Source Output Connection: You may connect AC IN 1 and AC IN 2 to a single source to provide power to AC OUT 1 and AC OUT 2. However, the loads connected to AC OUT 2 will not be measured for the purpose of automatic charger limitation. This could result in occasional tripping of the electrical service (source) circuit breaker. If this occurs, reduce the load on AC OUT 2 until nuisance tripping stops.

** Load circuit breaker limited

11R

Image 11
Contents RV Series v DC-to-AC Inverter/Chargers ContentsLimited Warranty SpecificationsEquipment Connection Warnings Important Safety InstructionsBattery Connection Warnings Location Warnings16 † Feature IdentificationOperation Switch ModesIndicator Lights Resetting Your Inverter/Charger to Restore AC PowerGroup B DIP Switches Not on 612 Models ConfigurationSet Configuration DIP Switches Group a DIP Switches All ModelsAll Models, except RV612UL & RV612ULH Select Auxiliary Battery Type if any Battery SelectionVehicular and Non-Vehicular Horizontal Mount MountingVehicular Battery ConnectionConnection for Models with Cords and Receptacles AC Input/Output ConnectionTroubleshooting ServiceMaintenance

200310080, 93-2182 specifications

Tripp Lite, a renowned leader in power protection and connectivity solutions, designs high-quality products tailored to meet the demands of businesses and individuals alike. Among their extensive catalog is the Tripp Lite 93-2182,200310080 model, a powerhouse of technological innovation and pragmatic design.

The Tripp Lite 93-2182 is a versatile power distribution unit (PDU) that is engineered to provide efficient and reliable power to multiple devices. With a rack-mountable design, it is ideal for data centers, server rooms, and any setup where space is at a premium. Its sleek form factor allows it to blend seamlessly into existing infrastructure while maximizing power delivery and minimizing clutter.

One of the standout features of this PDU is its combination of multiple output options, including various NEMA outlets to accommodate a wide range of devices. This makes it an excellent solution for environments with diverse equipment requirements. Users can connect servers, networking equipment, and other critical devices without the need for additional power strips, promoting a cleaner workspace and reduced risk of tripping hazards.

In terms of technology, the Tripp Lite 93-2182 is equipped with surge protection capabilities that shield connected equipment from voltage spikes. This protection is crucial in safeguarding sensitive electronics from potential damage. Additionally, the PDU features built-in circuit breakers which provide over-current protection, ensuring the safe operation of connected devices.

Another significant characteristic of this model is its robust monitoring capabilities. Some versions come with options to monitor power consumption, which can help users make informed decisions regarding load balancing and energy efficiency. Furthermore, comprehensive management features allow for efficient remote monitoring, enhancing control over power distribution across the network.

The durability of the Tripp Lite 93-2182 is also noteworthy. Constructed with high-quality materials, it is designed to withstand the rigors of a dynamic data environment. The attention to detail in its design ensures that it operates under various conditions while maintaining optimal performance.

In summary, the Tripp Lite 93-2182,200310080 represents a culmination of advanced engineering and practical design. With its versatile output options, surge protection features, and robust monitoring capabilities, it is a reliable choice for anyone looking to optimize their power distribution needs, particularly in tight spaces where efficiency is paramount.