Tripp Lite PDUMH20HVNET owner manual Network Interface Parameters

Page 6

Installation continued

Networking the PDU continued

5-3Connect PDU to Computer: Use the mini- DIN to DB9 serial cable (part number 73-1025) included with the PDU to connect the PDU to the computer. The circular connector A at one end of the cable attaches to the 8-pin mini-DIN serial port B on the PDU. (Align the connector carefully to avoid damaging the pins.) The DB9 connector C at the other end of the cable connects to the computer's serial port D .

5-4Connect PDU to Network: While the PDU is powered, connect a standard Ethernet patch cable to the RJ-45 Ethernet port A on the PDU.

Note: This port is not compatible with PoE (Power over Ethernet) applications.

5-5Configure PDU in Terminal Mode: After a brief pause, an initialization page should appear in the terminal emulation program. Press any key on the keyboard within 10 seconds to change the PDU settings. (If the 10-second period has elapsed, you can reboot the PDU by powering down completely and then restoring power.)

Follow the sequence of responses below in order to assign an IP address to the PDU. The default terminal mode root password is TrippLite.

Sample IP settings are shown - supply your own IP information when you configure your PDU.

 

B

C

 

A

 

 

5-3

 

D

A

 

 

5-4

5-5

Press A to Accept the settings, or M to Modify? M

Enter the root password: *********

Reset configuration to default values (Y/N)? N

For each of the following questions, you can press <Return> to select the value shown in braces, or you can enter a new value.

NETWORK INTERFACE PARAMETERS:

Should this target obtain IP settings from the network?[N] N

Static IP address [192.168.1.19]? 192.168.0.123

Static IP address is 192.168.0.123

Subnet Mask IP address [255.255.0.0]? 255.255.255.0

Subnet Mask IP address is 255.255.255.0

Gateway address IP address [192.168.1.1]? 192.168.0.1

Gateway address IP address is 192.168.0.1

You can also change the root password, real-time clock and other settings. (Tripp Lite recommends against changing the default settings unless you are an advanced user with a specific purpose.) After you have finished entering settings, the PDU will save changes to memory and reboot (this may take several minutes). After the PDU reboots, the initialization page should display the new static IP settings.

5-6Remove Serial Cable: Remove the serial cable from the PDU and proceed to Step 6-1 .

6

Image 6
Contents PDUMH15HVNET PDUMH20HVNET Important Safety Instructions Mounting the PDUInstallation Connecting the PDU Networking the PDU Dynamic IP Address AssignmentStatic IP Address Assignment Network Interface Parameters Networking the PDU Testing Network Connection Features Network Operating Conditions Remote Monitoring and Control Limited Warranty

PDUMH20HVNET specifications

The Tripp Lite PDUMH20HVNET is a robust power distribution unit (PDU) designed to enhance the efficiency and reliability of data centers and IT environments. This PDU is particularly valuable for those needing remote management capabilities, as it combines advanced features with a versatile design to meet various power distribution needs.

One of the primary characteristics of the PDUMH20HVNET is its ability to support high voltage applications. With an input voltage range of 200-240V, it is compatible with various high-performance equipment. The unit provides a total of 20 amps of power, making it suitable for powering multiple devices while ensuring efficient load balancing across the outlets.

The PDUMH20HVNET features 20 NEMA 5-15R output receptacles, allowing for the connection of multiple devices without sacrificing performance. This distribution unit offers both horizontal and vertical mounting options, granting flexibility for any rack-mounted equipment. Its compact design enables it to fit easily into standard 19-inch racks, saving valuable space in crowded server rooms.

Another notable feature of the PDUMH20HVNET is its built-in network management capabilities. It comes equipped with an Ethernet port that allows for remote monitoring and management via a web interface. Users can track real-time data regarding current loads, voltage, and environmental conditions, enabling proactive management of power resources. This feature is essential for maintaining optimal performance and preventing overload situations.

The unit also includes advanced features like automatic alerts for power fluctuations, allowing for quick responses to any issues that may arise. Additionally, it supports SNMP for seamless integration with existing network management systems, simplifying the overall monitoring process.

Durability and safety are other key aspects of the PDUMH20HVNET. It is constructed with high-quality materials to withstand the rigors of daily use in demanding environments. The built-in surge protection safeguards connected devices from spikes and surges, ensuring the longevity of critical equipment.

In summary, the Tripp Lite PDUMH20HVNET is a feature-rich power distribution unit that delivers reliable performance and remote management capabilities. Its high voltage support, flexible mounting options, and advanced monitoring features make it an essential component for modern data centers and IT operations, contributing to efficient and safe power management.