Basic Operation continued

Other UPS Features continued

Power Sensitivity/Lowline Adjustment: This dial is normally set fully counterclockwise, which enables the UPS to protect against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing PWM sinewave power from its battery reserves for as long as the distortion is present. In some areas with poor utility power or where the UPS's input power comes from a backup generator, frequent brownouts and/or chronic waveform distortion could cause the UPS to switch to battery too often, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to waveform distortion or brownouts by experimenting with different settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in its input power’s AC waveform and reduces the voltage point at which it switches to battery.

NOTE: The further the dial is adjusted clockwise, the greater the degree of waveform distortion and the lower the input voltage the UPS will allow to pass to connected equipment. When experimenting with different settings for this dial, operate connected equipment in a safe test mode so that the effect on the equipment of any waveform distortions in the UPS's output can be evaluated without disrupting critical operations. The experiment should last long enough to assure that all expected line conditions are encountered.

Storage & Service

Storage

All connected equipment should be turned off, then disconnected from the UPS to avoid battery drain. Unplug your UPS from its AC receptacle, then press and hold its ON/OFF button to deactivate it. Your UPS is now ready for storage. If you plan on storing your UPS for an extended period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.

Service

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the warranty period, enclose a copy of your sales receipt.

7

Image 7
Contents Internet Office BC Internet BC Personal UPS Location Warnings Important Safety InstructionsConnect your UPS to an electrical outlet Select UPS Operating Mode Buttons Quick Installation optionalIndicator Lights Other UPS Features Storage ServiceTwo symbols are used on the label ~ AC Voltage DC Voltage Manual del propietario Advertencias sobre la conexión de equipos Instrucciones de seguridad importantesAdvertencias sobre la ubicación del UPS Advertencias sobre la conexión del UPSSeleccione el modo de operación del UPS Conecte su UPS en un tomacorrienteComunicaciones USB Instalación rápida opcionalBotones Use el botón MUTE/TEST SILENCIO/PRUEBA para lo siguiente Operación básica continúaOtras funciones del UPS Luces indicadorasServicio AlmacenamientoNotas en el etiquetado Manuel de lutilisateur Conservez CES Instructions Consignes de sécurité importantesUSA, Canada & Europe de lOuest Boutons Installation rapide en optionSuite de Fonctionnement basique Voyants indicateurs Suite de Fonctionnement basique Entretien StockageModèle Page Page 200306152