DeviceNet Communication Adapter

1.2.1Exec. V. 1.10 vs. V. 1.20

Exec. V. 1.20 changed the behavior of certain I/O bases if a field side fault occurred. This change affects the following bases.

H170 ADM 350 10

H170 ADM 350 11

H170 ADM 390 10

H170 ADM 370 10

The following table describes the differences between the two versions in more detail. Refer to the TSX Momentum I/O Base User Guide (870 USE 002 00) for module specifications.

Table 3 Exec. V. 1.10 vs. V. 1.20

Firmware

Module

Action

 

 

 

 

170 ADM 350 10

If one of the field side outputs faults

 

(shorts out), the host will read all inputs

 

170 ADM 350 11

 

as zeros, regardless of the input signal

 

170 ADM 370 10

 

state.

 

 

 

 

 

 

 

If one of the field side outputs faults

Version 1.10

 

(shorts out), the host will read all inputs

 

as zeros, regardless of the input signal

 

 

 

170 ADM 390 10

state.

 

If an open condition exists (unconnected)

 

 

 

 

on any of the input points, the host will

 

 

read all inputs as zeros, regardless of the

 

 

input signal state.

 

 

 

 

170 ADM 350 10

If one of the field side outputs faults

 

170 ADM 350 11

(shorts out), the host will continue to read

 

170 ADM 370 10

the inputs normally.

 

 

 

 

 

If one of the field side outputs faults

Version 1.20

 

(shorts out), the host will continue to read

 

the inputs normally.

 

170 ADM 390 10

If an open condition exists (unconnected)

 

on any of the input points, the host will

 

 

 

 

read

 

 

H open inputs as zero (fault) and

 

 

H remaining non–faulted inputs normally.

 

 

 

4

Image 6
Contents Page Data, Illustrations, Alterations Training Hotline TrademarksCopyright Modicon TSX Momentum DeviceNet Communication Adapter LNT 710 Function Operating Voltages and Error ControlProduct Overview Physical StructureSpecifications General Specifications DescriptionEnvironmental Specifications Description Reference Exec. V .10 vs. V Firmware Module ActionExec. V .10 vs. V Status Indicators Indicator State StatusModule/Network Status Indicator Indicator State Network Terminator Jumper Connecting to the NetworkNetwork Connector 3 4Setting the Network Node Address Default AddressHow to Set the Address Node Upper Lower Address Switch Switch LNT 710Electronic Data Sheet EDS Disk EDS File UpdatesREADME.TXT File