S L C S e r i e s X e n o n C o n s o l e
4 . 2 . 2 . D O O R P A N E L S
All three door panels are removable for easier access to the interior of the console during installation and maintenance.
To remove door panel:
1.Unlock
2.Open door.
3.Push down on
4.Remove panel.
To install door panel, reverse the above procedure.
4 . 2 . 3 . V E N T I N G
It is necessary to vent hot exhaust air from console to the outside of the building.
1.Connect a
2.Ensure that there are no obstructions in ducting, and that air intake openings of console are unobstructed.
If
External exhaust air extraction is required. Minimum and maximum exhaust airflow requirements for all SLC series models are shown in Figure
Model | Minimum Exhaust (ft3/min) | Maximum Exhaust (ft3/min) |
SLC 20 | 300 | 400 |
SLC 30 | 350 | 450 |
SLC 40 | 450 | 550 |
|
|
|
SLC 45, SLC 45R | 550 | 750 |
|
|
|
SLC 70 | 750 | 900 |
|
|
|
Figure 4-3: Minimum and Maximum Exhaust Airflow Requirements for SLC Consoles