Bosch Appliances FPE-1000-NW Terminal Specifications Class a Style, Network Connections Example

Page 14

14 en ConnectionNetworking Cards

Terminal

 

Specifications Class A Style 7

 

 

 

FPE-1000-NW

Wired OUT+/-

Terminals used for outgoing loop

 

 

 

 

Wired IN+/-

Terminals used for return loop

 

 

 

Table 5.2 Specifications SLC Terminals Class A Style 7

Additional notes regarding Class A Style 7:

1.No T-taps allowed on Class A Style 7 network wiring.

2.The return side of the loop must be routed separately from the outgoing loop.

3.The return side must not share the same conduit or cable as the outgoing side of the loop.

4.Refer to NFPA 72 for additional requirements of Class A circuits.

Figure 5.1 Network Connections Example

Legend

1

2

3

4

5

Wire to Wire connection

Wire to Ethernet connection

Ethernet to Fiber Optic connection

Fiber Optic to Fiber Optic connection

Class A connection (Ethernet to Ethernet in this example)

NOTICE!

The network does not require an EOL resistor.

F.01U.214.374 01 2012.08

Installation Manual

Bosch Security System, Inc.

Image 14
Contents Networking Cards Page Documentation Availability Note 01U.214.374 01 Bosch Security System, Inc Table of Contents Disclaimer SafetyGeneral Networking Cards Safety en System Overview Type Number Description Connection Mode Maximum DistanceWired Networking Card Ethernet Networking CardGeneral considerations Ground Fault DetectionPlanning Port supervisionOperation Guide Installation MountingNetworking Card Connectors and slot Snap-fit hook Class a connections Type of Fault Class B Style Class a StyleConnection Terminal Specifications Class a Style Network Connections ExampleCommon parameters of all three networking cards Technical DataFPE-1000-NW Wired Networking Card parameters FPE-1000-NE Ethernet Networking Card parametersPage Page Page Page Bosch Security System, Inc