APC AP8959NA3 manual How To Define Trap Receivers, Apc Apcmgmt Mconfig

Page 12

GUIDEBase

REFERENCEInformationManagement

®

How To Define Trap Receivers

You can define trap receivers as follows:

Each Management Card or other APC hardware device can send traps to up to six trap receivers, but you can define only four through the APC PowerNet MIB. You can define the other two through the user interface of the Management Card or device.

Each PowerNet agent can send traps to up to four trap receivers.

You can define only SNMPv1 trap receivers through the APC PowerNet MIB. To define SNMPv3 trap receivers, use the interface of the Management Card or device that will send the traps, if it supports SNMPv3.

In a MIB browser, select, in order, these OID categories to access the PowerNet MIB OIDs that you use to define a trap receiver:

[apc]

[apcmgmt]

[mconfig]

OID

Task

 

 

mconfigNumTrapReceivers

The number of NMSs to receive traps (always 4).

{mconfigTrapReceiverTable}

A tabled set of OIDs to define parameters for each trap

[mconfigTrapReceiverEntry]

receiver:

trapIndex

• The trap receiver’s number (i.e., the read-only index to

receiverAddr

the trap receiver entry).

• The NMS’s IP address. The default value, 0.0.0.0,

communityString

prevents all NMSs from receiving traps.

• The password (community name) that a trap must use

severity

to be sent to this trap receiver.

• This OID is obsolete and always returns zero.

acceptThisReceiver

• Enables or disables sending traps to this NMS.

 

yes (1): Enable

receiveTrapType

no (2): Disable

• The type of traps that this NMS will receive. You must

 

use powernet (1).

 

 

11

Image 12
Contents Contents About This Guide Purpose of the GuideRelated Documents and Files PowerNet MIB Structure Snmp access controlsTraps OIDsStructure of the OID hierarchy in the PowerNet MIB Structure of the OID hierarchy in the Snmp browserTabled OIDs Monitor a PowerNet Agent Manage Agents and Management CardsLocate the OIDs View Bootp value set trap receivers, date, and time Manage an Snmp Agent of a Hardware DeviceView information about an agent View information about an agent’s software modulesControl the agent’s rebooting behavior Enable APC traps to use a specific argument type MfiletransferConfigSettings subcategory has one OIDMfiletransferConfigFTP subcategory has these OIDs PowerNet MIB Traps OverviewHow To Define Trap Receivers Apc Apcmgmt MconfigMIB structure Monitoring a PowerNet agent OIDs IndexManagement Information Base APC Worldwide Customer Support USACopyright

AP8959NA3 specifications

The APC AP8959NA3 is a sophisticated and highly efficient power distribution unit (PDU) designed to optimize power management in data centers and IT environments. It is engineered to enhance reliability and effectiveness in delivering power to a variety of devices, ranging from servers to networking equipment.

One of the main features of the APC AP8959NA3 is its advanced layout, which includes multiple output receptacles for flexible connectivity. With 24 NEMA 5-20R outlets, this PDU is capable of accommodating various devices, allowing users to configure their power distribution according to specific requirements. The unit is designed to support high-density racks, making it an ideal choice for modern IT infrastructures.

In addition to its impressive outlet configuration, the APC AP8959NA3 offers 30A input capability, ensuring it can handle substantial power loads. This is particularly important in environments that require reliable power to critical equipment. The PDU is suitable for both standard and high power requirements, and it provides a robust solution for power distribution across a wide array of applications.

Another significant aspect of the APC AP8959NA3 is its intelligent monitoring features. It includes real-time monitoring capabilities, allowing users to track power consumption data. This feature helps in identifying power trends, enabling users to make informed decisions regarding their power usage. The unit's built-in network management capabilities allow for remote monitoring and control, streamlining management tasks and reducing response times to potential issues.

The construction of the APC AP8959NA3 is robust, ensuring durability and longevity. It is designed to withstand the rigors of a data center environment while maintaining optimal performance. Additionally, the PDU is made with safety in mind, featuring circuit breakers and power surge protection to safeguard connected devices against electrical anomalies.

Moreover, the APC AP8959NA3 is compatible with a range of mounting options, including rack-mount and vertical positioning, ensuring versatility in various environments. Its sleek and compact design helps in maximizing space efficiency without compromising accessibility.

In conclusion, the APC AP8959NA3 is a powerful and versatile PDU, equipped with essential features and advanced technologies suited for modern IT demands. Its capacity to support high loads, intelligent monitoring, and flexible mounting options make it an invaluable component of any data center, ensuring that critical equipment receives consistent and reliable power distribution.