RuggedCom RX5000 manual Test Description Test Levels

Page 33

5. EMI And Environmental Type Tests

Test

 

Description

Test Levels

IEEE C37.90.3

ESD

 

Enclosure Contact

+/-2kV, +/-4kV, +/- 8kV

 

 

 

 

Enclosure Air

+/-4kV, +/-8kV, +/-15kV

 

 

 

 

 

 

 

 

IEEE C37.90.2

Radiated RFI

 

Enclosure ports

35 V/m

 

 

 

 

 

 

 

 

Signal ports

+/- 4kV @ 2.5kHz

 

 

 

 

 

IEEE C37.90.1

Fast Transient

 

D.C. Power ports

+/- 4kV

 

 

 

 

A.C. Power ports

+/- 4kV

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

+/- 4kV

 

 

 

 

 

 

 

 

Signal ports

2.5kV common mode @1MHz

 

 

 

 

 

IEEE C37.90.1

Oscillatory

 

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

 

 

 

 

 

 

 

 

A.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

 

 

 

 

 

 

 

 

Signal ports

5kV (Fail-Safe Relay output)

 

 

 

 

 

IEEE C37.90

H.V. Impulse

 

D.C. Power ports

5kV

 

 

 

 

 

 

 

 

A.C. Power ports

5kV

 

 

 

 

 

 

 

 

Signal ports

2kVAC

 

 

 

 

 

IEEE C37.90

Dielectric Strength

 

D.C. Power ports

2kVDC

 

 

 

 

 

 

 

 

A.C. Power ports

2kVAC

 

 

 

 

Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Testsa

 

Test

Description

 

Test Levels

IEC 60068-2-1

Cold Temperature

Test Ad

-40°C, 16 Hours

 

 

 

 

IEC 60068-2-2

Dry Heat

Test Bd

+85°C, 16 Hours

 

 

 

 

IEC 60068-2-30

Humidity (Damp Heat, Cyclic)

Test Db

95% (non-condensing), 55°C , 6 cycles

 

 

 

 

IEC 60255-21-1

Vibration

 

2g @ (10 - 150) Hz

 

 

 

 

IEC 60255-21-2

Shock

 

30g @ 11mS

 

 

 

 

Table 5.3. Environmental Type Tests

RuggedCom® RuggedBackbone™

33

RX5000 Installation Guide Rev106

Image 33 Contents
RuggedBackbone RX5000 All Rights Reserved Warranty Contacting RuggedComDisclaimer Of Liability Registered TrademarksTable of Contents List of Figures List of Tables FCC Statement And Cautions Feature Highlights Product OverviewFunctional Overview Netconf RuggedBackbone Modules Installing a Module In The ChassisControl Module Control ModuleSwitch Switch ModuleTX01 Line ModulesPower Supply Module Power ModuleInstallation MountingRack Mounting Rack Front Mounting Rack Front Mount Top View Rack Front Mounting with Front-Mounted Power Supplies Rack Front Mount with Front-Mount Power Supplies Top View Rack Rear Mounting 10. Rack Rear Mount Top View 11. Panel Mount Side View Panel MountingPin Function Power Supply Wiring And GroundingAC Power Supply Wiring DC Power Supply Wiring15. AC Power Separate Earth Connection 16. Critical Alarm Relay Connection Critical Alarm Relay17. Serial Console Port Serial Console Ports1. RJ45 Twisted-Pair Copper Ports Copper Ethernet PortsGigabit Ethernet 1000Base-TX Cabling Recommendations RJ45 Pin 10/100Base-Tx 10/100/1000Base-TxTransient Suppression Fiber Ethernet PortsPower Supply Specifications Technical SpecificationsCritical Alarm Relay Specifications Copper Ethernet Port SpecificationsFiber Ethernet Port Specifications Fast Ethernet 100Mbps Optical SpecificationsGigabit Ethernet 1Gbps Optical Specifications Operating Environment Mechanical SpecificationsParameter Range Comments Parameter Value CommentsTest Description Test Levels Severity EMI And Environmental Type TestsTest Test Description Test LevelsAgency Standards Comments Agency ApprovalsRuggedCom Inc Warranty
Related manuals
Manual 35 pages 63.66 Kb