RuggedCom RS416 warranty EMI and Environmental Type Tests

Page 5

RuggedServerRS416

Modular 16-Port Serial Device Server with Integrated Managed Ethernet Switch

EMI and Environmental Type Tests

IEC 61850-3 EMI TYPE TESTS

TEST

Description

 

Test Levels

Severity Levels

IEC 61000-4-2

ESD

 

Enclosure Contact

+/- 8kV

4

 

 

 

 

 

Enclosure Air

+/- 15kV

4

 

 

 

IEC 61000-4-3

Radiated RFI

 

Enclosure ports

20 V/m

x

 

 

 

 

 

 

 

 

 

Signal ports

+/- 4kV @ 2.5kHz

x

 

 

 

 

 

 

 

 

 

D.C. Power ports

+/- 4kV

4

IEC 61000-4-4

Burst (Fast Transient)

 

 

 

 

 

A.C. Power ports

+/- 4kV

4

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports 3

+/- 4kV

4

 

 

 

Signal ports

+/- 4kV line-to-earth, +/- 2kV line-to-line

4

 

 

 

 

 

 

IEC 61000-4-5

Surge

 

D.C. Power ports

+/- 2kV line-to-earth, +/- 1kV line-to-line

3

 

 

 

A.C. Power ports

+/- 4kV line-to-earth, +/- 2kV line-to-line

4

 

 

 

 

 

 

 

 

 

Signal ports

10V

3

 

 

 

 

 

 

 

 

 

D.C Power ports

10V

3

IEC 61000-4-6

Induced (Conducted) RFI

 

 

 

 

 

A.C. Power ports

10V

3

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports 3

10V

3

IEC 61000-4-8

Magnetic Field

 

Enclosure ports

40 A/m continuous, 1000 A/m for 1 s

N/A

 

 

 

 

 

 

 

 

 

D.C. Power ports

30% for 0.1s, 60% for 0.1s, 100% for 0.05s

N/A

IEC 61000-4-29

 

 

 

 

 

Voltage Dips & Interrupts

 

 

30% for 1 period, 60% for 50 periods

N/A

 

 

 

 

 

 

A.C. Power ports

 

 

IEC 61000-4-11

 

 

100% for 5 periods, 100% for 50 periods 2

N/A

 

 

 

 

 

 

Signal ports

2.5kV common, 1kV diff. mode@1MHz

3

IEC 61000-4-12

Damped Oscillatory

 

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

3

 

 

 

 

 

 

 

 

 

A.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

3

IEC 61000-4-16

Mains Frequency Voltage

 

Signal ports

30V Continuous, 300V for 1s

4

 

 

 

 

 

D.C. Power ports

30V Continuous, 300V for 1s

4

 

 

 

 

 

 

 

 

 

IEC 61000-4-17

Ripple on D.C. Power Supply

 

D.C. Power ports

10%

3

 

 

 

Signal ports

2kVac (Fail-Safe Relay output)

N/A

 

 

 

 

 

 

IEC 60255-5

Dielectric Strength

 

D.C. Power ports

2kVac

N/A

 

 

 

A.C. Power ports

2kVac

N/A

 

 

 

 

 

 

 

 

 

Signal ports

5kV (Fail-Safe Relay output)

N/A

 

 

 

 

 

 

IEC 60255-5

H.V. Impulse

 

D.C. Power ports

5kV

N/A

 

 

 

A.C. Power ports

5kV

N/A

 

 

 

 

 

 

IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS

Test

Description

 

Test Levels

Severity Levels

IEEE C37.90.3

ESD

 

Enclosure Contact

+/- 8kV

N/A

 

 

 

 

 

Enclosure Air

+/- 15kV

N/A

 

 

 

 

 

 

 

 

 

IEEE C37.90.2

Radiated RFI

 

Enclosure ports

35 V/m

N/A

 

 

 

 

 

 

 

 

 

Signal ports

+/- 4kV @ 2.5kHz

N/A

 

 

 

 

 

 

IEEE C37.90.1

Fast Transient

 

D.C. Power ports

+/- 4kV

N/A

 

 

 

 

 

A.C. Power ports

+/- 4kV

N/A

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports3

+/- 4kV

N/A

 

 

 

 

 

 

 

 

 

Signal ports

2.5kV common mode @1MHz

N/A

 

 

 

 

 

 

IEEE C37.90.1

Oscillatory

 

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

N/A

 

 

 

 

 

 

 

 

 

A.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

N/A

 

 

 

 

 

 

 

 

 

Signal ports

2kVac

N/A

 

 

 

 

 

 

IEEE C37.90

Dielectric Strength

 

D.C. Power ports

2kVac

N/A

 

 

 

 

 

 

 

 

 

A.C. Power ports

2kVac

N/A

 

 

 

 

 

 

Environmental Type Tests

Test

Description

 

Test Levels

Severity Levels

IEC 60068-2-1

Cold Temperature

 

Test Ad

-40°C, 16 Hours

N/A

 

 

 

 

 

 

IEC 60068-2-2

Dry Heat

 

Test Bd

+85°C, 16 Hours

N/A

 

 

 

 

 

 

IEC 60068-2-30

Humidity (Damp Heat, Cyclic)

 

Test Db

95% (non-condensing), 55°C , 6

N/A

 

cycles

 

 

 

 

 

 

 

 

 

 

 

IEC 60255-21-1

Vibration

 

Tests Fc

2g @ (10 - 150) Hz

Class 2

 

 

 

 

 

 

IEC 60255-21-2

Shock

 

Tests Ea

30g @ 11mS

Class 2

 

 

 

 

 

 

Notes: 1. Only applicable to functional earth connections separated from the safety earth connection.

2.Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high,

5.( e.g. shipboard application and for severe transportation conditions")

www.RuggedCom.com

RuggedServer™ RS416

5

 

 

 

 

 

Image 5
Contents Rugged Operating System Rostm Features Universal Power Supply OptionsSerial Device Server Ethernet PortsSerial Port Types RuggedServer RS416Rostm Features Port Configuration and Status Port Based Network Access ControlEvent Logging and Alarms Configuration via Ascii Text FileTest EMI and Environmental Type TestsTechnical Specifications Mtrj / ST / SC Fiber Specifications and DimensionsMounting Options Order Codes For additional information on our products