RuggedCom RS500 Type Test Specifications, Electrical Safety Levels Comments, Test Bd 16 hrs @ 85C

Page 14

3.6 Type Test Specifications

 

Electrical Safety

Levels

 

 

Comments

 

Dielectric Withstand

2 kV rms for 1 minute

 

 

ANSI/IEEE C37.90 (1989)

 

 

 

 

 

 

IEC 60255-5 (Section 6)

 

High Voltage Impulse

5 kV peak

 

 

IEC 60255-5 (Section 8)

 

Insulation Resistance

500 VDC for 1 minute

 

 

IEC 60255-5 (Section 6

 

 

 

 

 

 

 

 

Electrical Environment

Levels

 

 

Comments

 

High Frequency Disturbance

2.5 kV @ 1MHz for 2s

 

 

ANSI/IEEE C37.90.1

 

(Oscillatory)

 

 

 

 

IEC 60255-22-1

 

IEC Surge

4 kV / 2 kV

 

 

IEC 61000-4-5

 

 

 

 

 

 

(Level 4)

 

IEC Fast Transient

2 kV / 1 kV

 

 

IEC 61000-4-4

 

 

 

 

 

 

(Level 4)

 

ANSI/IEEE Fast Transient

4 kV

 

 

ANSI/IEEE C37.90.1

 

IEC Radiated RFI Immunity

10 V/m

 

 

IEC 61000-4-3

 

ANSI/IEEE Radiated RFI

35 V/m

 

 

ANSI/IEEE C37.90.2

 

Immunity

 

 

 

 

 

 

 

 

 

 

 

ESD

15 kV (air discharge)

 

 

IEC 61000-4-2

 

(Electrostatic Discharge)

8 kV (contact)

 

 

(Level 4)

 

 

 

 

 

 

 

 

Atmospheric Environment

Levels

 

 

 

Comments

 

Temperature (Dry Cold)

-40°C

 

 

 

IEC 60068-2-1

 

 

 

 

Test Ad: 16 hrs @ -40°C

 

Temperature (Dry Heat)

85°C

 

 

 

IEC 60068-2-2

 

 

 

 

Test Bd: 16 hrs @ 85°C

 

Humidity

95%

 

 

 

IEC 60068-2-30

 

 

Non-condensing

 

Test Db: 6 cycles, 55°C, 95%

 

 

 

 

 

 

Humidity

 

14

2008 RuggedCom Inc. All rights reserved

Rev101

Image 14
Contents RuggedSwitch RS500  2008 RuggedCom Inc. All rights reserved Rev101 Table of Contents Functional Overview Feature HighlightsProduct Overview Tx LED Red Power LED RedRS500 Front Panel Description Rx LED GreenRS500 Top and Bottom View 1 RS500 Top and Bottom ViewRS500 DIN Rail Mounting & Release Side View InstallationDIN Rail Mounting  2008 RuggedCom Inc. All rights reserved Rev101 Power Supply DC Input Hipot Dielectric Strength Testing Failsafe Output Wiring and Specifications RS500 Failsafe Relay OutputsFailsafe Relay Specifications Technical SpecificationsPower Supply Specifications Networking Standards SupportedFiber Optical Specifications Networking Performance SpecificationsTest Ad 16 hrs @ -40C Type Test SpecificationsElectrical Safety Levels Comments Test Bd 16 hrs @ 85CPhysical Dimensions Operating EnvironmentParameter Value Comments WarrantyAgency Approvals Agency Standards