RuggedCom RS500 manual Product Overview, Functional Overview, Feature Highlights

Page 4

1 Product Overview

1.1 Functional Overview

The RuggedSwitchRS500 is a substation hardened, fiber optical Ethernet switch specifically designed to operate in harsh environments such as those found in electric utility substations and harsh industrial environments. The RS500 provides 4 10BaseFL fiber optical ports and one 100BaseFX port.

Specifically tested to the same standards as mission critical protective relaying equipment (i.e. ANSI/IEEE C37.90 and IEC 60255) the RS500 is ideally suited to form the Ethernet network in a UCA2 (Utility Communications Architecture 2.0) based substation automation network. Because the RS500 was designed to meet the demands of the substation environment it is also ideally suited for industrial automation networks based on Industrial Ethernet. The reliability of the RS500 exceeds that of commercial Ethernet switches by having no rotating mechanical parts such as cooling fans and by utilizing high-temperature solid-state components.

1.2 Feature Highlights

￿Utility Grade (i.e. substation hardened) per ANSI/IEEE C37.90, IEC 60255, and the new IEC 61850-3 (2002), IEC 61000-6-5 standards

￿Operating temperature: -40°to 85°C (no fan)

￿Radiated RF Immunity: 35V/m per ANSI/IEEE C37.90.2

￿Power supply options: 24VDC, 48VDC or 110VDC

￿Failsafe output relay for critical failure or error alarming

￿4 – 10BaseFL (10Mbps) multimode

￿1 – 100BaseFX fiber optical port

￿Full-duplex operation (no collisions)

 

4

2008 RuggedCom Inc. All rights reserved

Rev101

Image 4
Contents RuggedSwitch RS500  2008 RuggedCom Inc. All rights reserved Rev101 Table of Contents Product Overview Feature HighlightsFunctional Overview Power LED Red RS500 Front Panel DescriptionTx LED Red Rx LED GreenRS500 Top and Bottom View 1 RS500 Top and Bottom ViewDIN Rail Mounting InstallationRS500 DIN Rail Mounting & Release Side View  2008 RuggedCom Inc. All rights reserved Rev101 Power Supply DC Input Hipot Dielectric Strength Testing Failsafe Output Wiring and Specifications RS500 Failsafe Relay OutputsTechnical Specifications Power Supply SpecificationsFailsafe Relay Specifications Networking Standards SupportedFiber Optical Specifications Networking Performance SpecificationsType Test Specifications Electrical Safety Levels CommentsTest Ad 16 hrs @ -40C Test Bd 16 hrs @ 85CPhysical Dimensions Operating EnvironmentWarranty Agency ApprovalsParameter Value Comments Agency Standards