Watlow Electric Gateway & DeviceNet Configuring the DeviceNetTM Scanner 1769-SDN Using RSLogix

Page 11

RUI/Gateway & DeviceNetTM

Configuration & Ladder Logic Example

Using an Allen-Bradley CompactLogix PLC

19.The gateway instance represents the EZ-ZONE®control, in this case, PM 1-4. The enable

gateway instance simply turns on that particular gateway where there is a direct correlation between gateway instance 1 and EZ-ZONE®PM controller 1. Likewise, that relationship continues through gateway instance 16 and EZ-ZONE®PM controller 16. The gateway instance will always equate to the Standard Bus controller with the same address 1-16.

The CIP offset allows for the PLC or any master on the DeviceNetTM side to read or write the same member from any of the four controllers on the Standard Bus network via an explicit message.

Configuring the DeviceNetTM Scanner (1769-SDN) Using RSLogix 5000

20.In the examples that follow please note that the PLC being used is a CompactLogix L32E. If using other PLCs the steps will vary slightly but the overall concepts will be the same. As you might guess some configuration is required on the PLC side prior to getting started with the programming.

21.Insert a DeviceNetTM scanner into the I/O structure of the PLC. Notice below the input and output size correlates directly to what was configured in RSNetWorx (step 15).

Watlow

 

 

1241 Bundy Blvd

 

 

Winona, MN 55987

 

 

Telephone: 507-494-5656

 

 

© 2007 Watlow Electric Mfg Co

11

4/08

Image 11
Contents Page Page Page Page Page Page Page Page Configuration of the RUI/Gateway CIP Configuring the DeviceNetTM Scanner 1769-SDN Using RSLogix EZ-ZONEEEPROM Page Page Page Custom T to O Data Type Custom O to T Data Type Controller Tag T to O Controller Tag O to T Assembly RUI/Gateway Addressing Communications Card