Omron F7 Type designation, PLC inverter, Specifications by product, General specifications

Page 2

Type designation

PLC inverter

3G3RV-P10ST8-DRT-E

Inverter series

Number of I/O's

 

 

 

 

 

 

 

 

 

 

 

 

 

DeviceNet slave

Options

 

-

No

 

 

 

 

 

 

 

 

DRT

Yes

 

 

 

 

 

 

 

 

Output

RTC

RS422

Remarks

-

NPN

NO

NO

 

1

NPN

NO

YES

 

2

NPN

YES

NO

 

 

 

 

 

 

3

NPN

YES

YES

 

5

PNP

NO

NO

 

6

PNP

NO

YES

 

 

 

 

 

 

7

PNP

YES

NO

 

8

PNP

YES

YES

Standard

Specifications

Specifications by product

Item

3G3RV-P10ST8-E

3G3RV-P10ST8-DRT-E

PLC core

CPM2C-S

CPM2C-S

 

 

 

Inputs

6 24 VDC inputs

6 24 VDC inputs

Outputs

4 sourcing/PNP transistor outputs

4 sourcing/PNP transistor outputs

 

 

 

Peripheral port

Yes

Yes

 

 

 

RS-232C port

Yes

Yes

RS-422 port

No

Yes

 

 

 

Calendar/clock

Yes

Yes

 

 

 

Memory backup

Flash memory and battery

Flash memory and battery

Compobus/S master interface

Yes

Yes

 

 

 

Encoder interface

Yes

Yes

 

 

 

DeviceNet Slave interface

No

Yes

General specifications

Item

 

Specifications

 

 

 

3G3RV-P10ST8-E

3G3RV-P10ST8-DRT-E

Rated power supply voltage

24 VDC +10%/-15%(external power supply for I/O)

 

Communications power supply voltage

---

11 to 25 VDC (supplied by communications connector)

Power consumption

Internal power

2 W (supplied internally) (see note)

3 W (supplied internally) (see note)

supply

 

 

 

Communications power supply

---

30 mA max.

 

 

 

 

Vibration resistance

 

10 to 20 Hz, 9.8 m/s2 max.

 

 

 

20 to 50 Hz, 2 m/s2 max

 

 

 

 

Ambient operating temperature

-10 to 45 °C

 

 

 

 

Ambient operating relative humidity

10% to 90% (no condensation)

 

Ambient storage temperature

-20 to 70 °C

 

 

 

 

 

Atmosphere

 

Must be free from corrosive gas

 

 

 

 

 

Control method

 

Store program method

 

I/O control method

 

Cyclic scan method

 

 

 

 

Programming language

Ladder chart method

 

 

 

 

 

Instruction length

 

1 step/1 instruction; 1 to 5 words/1 instruction

 

Instruction types

Basic

14 types (same as for programmable slaves)

 

 

 

 

 

Special

105 types, 185 instructions (same as for programmable slaves)

 

 

 

 

Processing speed

Basic instructions

0.64 µs (LD)

 

 

Special instructions

7.8 µs (MOV)

 

 

 

 

 

Program capacity

 

4,096 words

 

 

 

 

Maximum number of I/O points

10

 

Input bits

 

00000 to 00015 (6 physical inputs)

 

 

 

 

 

Output bits

 

01000 to 01003 (4 physical outputs)

 

 

 

CompoBus/S input bits

128 bits: IR 02000 to IR 02715 (bits not used for CompoBus/S input bits can be used for work bits.)

CompoBus/S output bits

128 bits: IR 03000 to IR 03715 (bits not used for CompoBus/S output bits can be used for work bits.)

 

 

 

 

Inverter interface

 

Direct interface with inverter through

 

 

 

IR-memory

 

 

 

DM-memory

 

 

 

• Transfer command

 

 

 

 

 

Inverter interface bits

 

176 bits: IR 20000 to IR 21015

 

Encoder interface bits

 

48 bits: IR 02900 to IR 02915 and IR 04800 to IR 04915

 

 

 

Work bits

 

448 bits: IR 02800 to IR 02815, IR 03800 to IR 04715, and IR 21100 to IR 22715

 

 

 

Special bits (SR area)

 

448 bits: SR 22800 to SR 25507 (words SR 228 to SR 255)

Temporary bits (TR area)

8 bits (TR 0 to TR 7)

 

 

 

 

 

Holding bits (HR area)

 

320 bits: HR 0000 to HR 1915 (words HR 00 to 19)

 

 

 

 

Auxiliary bits (AR area)

384 bits: AR 0000 AR 2315 (words AR 00 to AR 23)

 

366

3G3RV-P10ST@-E

Image 2
Contents System configuration G7/F7/L7/E7 inverter PLC 365General specifications SpecificationsSpecifications by product Type designationG7/F7/L7/E7 inverter PLC 367 Inputs Specification SpecificationsInput specifications High-speed counter inputsInterrupt inputs Output specificationsEncoder input specifications Transistor outputs sourcing/PNPOperation CPU unit component descriptionsTerminal arrangement Switch to select port 1 type of connected deviceG7/F7/L7/E7 inverter PLC 371 To be connected the earth connection inside the inverterG7 + PLC in a water treatment application example Dimensions Application examplesG7 + PLC 372 3G3RV-P10ST@-EF7 + PLC E7 + PLC374 3G3RV-P10ST@-E L7 + PLCL7 + PLC in lift application example Ordering information 376 3G3RV-P10ST@-E Product Appearance Specifications ModelCompobus/S slaves