6. Communications port

Connects the PLC to a programming device (including programming consoles), host computer, or standard external device. Use a proper connecting cable (CPM2C-CN111, CS1W-CN114, CS1W-CN118, or CS1W-CN226).

Note: 1. A CQM1H-PRO01-E programming console can be connect- ed directly to the PLC.

2.A C200H-PRO27-E programming console can be connected directly to the PLC with a CS1W-CN224/CN624 connecting cable.

3.Use a CPM2C-CN111 or CS1W-CN114 connecting cable to connect to the communications port as a peripheral port. The communications port can be used simultaneously as both a peripheral port and RS-232C port by using the CPM2C- CN111 connecting cable.

4.Use a CPM2C-CN111, CS1W-CN118 or CS1W-CN226 con- necting cable to connect to the communications port as a RS- 232C port. The communications port can be used simulta- neously as both a peripheral port and RS-232C port by using the CPM2C-CN111 connecting cable

Note: The peripheral port and RS-422/485 port cannot be used simul-

taneously. When using the peripheral port disconnect any devices connected to the RS-422/485 port.

7. Communications switch

Switch to select port 1 type of connected device

Position

Communication port 1

OFF (up) (default)

Programming console

ON (down)

RS-422/485 communication

8. DeviceNet port (-DRT versions only)

Terminal arrangement

V-

CAN-L

Shield

CAN-H

V+

 

 

 

 

 

9. RS-422/485 port

Used to connect to host computers, or standard external devices. Terminal arrangement

Send Receive

data data

(output) (input)

6 SDB+ RDB+

5 SDA- RDA-

Note: The maximum line length is 500 m.

The peripheral port and RS-422/485 port cannot be used simul- taneously. When using the peripheral port disconnect any devices connected to the RS-422/485 port.

When using RS-485 communication, connect RDA- to SDA- and RDB+ to SDB+.

10. Terminating resistance switch

 

 

 

 

 

 

Position

Termination

 

 

 

 

 

 

OFF (right)

Disabled

 

ON

 

 

1

 

(default)

 

 

 

 

 

ON (left)

Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set this switch to ON only for double-ended connection to a host link network.

11. CompoBus/S port

Terminal arrangement

BDH

 

4

 

2

 

 

 

 

 

 

 

 

 

 

 

BDL

 

3

 

1

 

 

 

 

 

 

 

 

 

Use special flat cable or VCTF cable for the transmission lines that con- nect the nodes in the CompoBus/S I/O Link. (Special flat cables and VCTF cables cannot be combined in the same system.)

Name

Model number

Specifications

Flat cable

XB1T-W10

4-core flat cable, 0.75 mm²

VCTF cable

---

2-core VCTF, 0.75 x 20

12. Digital inputs and outputs and encoder interface

Connects the CPU unit to external input and output devices. Sourcing outputs

Z-

B-

A-

OUT3

OUT1

COM(+)

IN5

 

IN3

IN1(B)

Z+

B+

A+

OUT2

OUT0

COM

 

IN4

IN2(Z)

IN0(A)

13. Functional earth-wire

To be connected the earth connection inside the inverter.

14.Battery

15.Low battery detection switch

This switch enables or disables the detection of a low-battery error.

 

 

 

 

 

 

Position

Low-battery detection

 

 

 

 

 

 

OFF (right)

Error detection enabled

 

ON

 

 

1

 

(default)

 

 

 

 

 

ON (left)

Error detection disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16. DeviceNet node-number (-DRT versions only)

Please refer to the DeviceNet section

17. DeviceNet indicators (-DRT versions only)

Please refer to the DeviceNet section

18. CompoBus/S indicators

 

 

 

Indicator

Status

Meaning

 

 

 

SD

Flashing

Data is being transmitted via

 

 

SD

(yellow)

 

CompoBus/S

 

 

RD

 

 

 

 

OFF

Data isn't being transmitted via

 

 

ERC

 

 

 

 

 

CompoBus/S

 

 

 

 

 

 

 

 

RD

Flashing

Data is being received via

 

 

 

(yellow)

 

CompoBus/S

 

 

 

 

OFF

Data isn't being received via

 

 

 

 

 

CompoBus/S

 

 

 

 

 

 

 

 

 

ERC

Flashing

A CompoBus/S communications

 

 

 

(red)

 

error occurred.

 

 

 

 

OFF

A CompoBus/S communications

 

 

 

 

 

error hasn't occurred.

G7/F7/L7/E7 inverter PLC

371

Image 7
Contents G7/F7/L7/E7 inverter PLC 365 System configurationType designation SpecificationsSpecifications by product General specificationsG7/F7/L7/E7 inverter PLC 367 High-speed counter inputs SpecificationsInput specifications Inputs SpecificationTransistor outputs sourcing/PNP Output specificationsEncoder input specifications Interrupt inputsCPU unit component descriptions OperationTo be connected the earth connection inside the inverter Switch to select port 1 type of connected deviceG7/F7/L7/E7 inverter PLC 371 Terminal arrangement372 3G3RV-P10ST@-E Dimensions Application examplesG7 + PLC G7 + PLC in a water treatment application exampleE7 + PLC F7 + PLCL7 + PLC in lift application example L7 + PLC374 3G3RV-P10ST@-E Ordering information Compobus/S slaves Product Appearance Specifications Model376 3G3RV-P10ST@-E