RATE

DPS3300 series tracks the rate of process change/minute for each channel. This rate is displayed by first pushing the CH. SEL key to select the channel whose rate is desired. Once the channel has been selected, push DATA key. The display will briefly read 'cx-rate' (x=channel #), and then the monitored rate for that channel.

LIMITS

DPS3300 series units support limit alarms on all the channels. These limits can be programmed over the entire range of selected thermocouple or scale. Thus, not only can these units be used as monitors but they can also provide control capability on

each channel. Limit values are programmed during CH Setup. Also programmed during CH Setup is the dead-band (hysteresis) value. This keeps the relays from chattering when the process is hovering just around the limit.

OUTPUTS

DPS3300 Series units can be ordered with either open collector outputs or electro-mechanical relays. Check model number printed on the unit.

Open Collector Option

Whenever a limit is reached an open collector output provides a 5 Vdc signal at 50ma. on the output connector, eg.. Limit #4 provides its 5 volt output signal between pins 7 & 8 of the card edge.

Figure 1. Open Collector Hookup Example

Instrument

+5VDC

+ OUTPUT

7

8

LOAD

- OUTPUT

Solid Sate Relay

LED, Buzzer, ETC.

Electro-Mechanical Relay Option

These relays are programmed during CH Setup to operate as either Normally Open (NO) or Normally Closed (NC). The default setting is Normally Open. Each of these limit relays provides a switched output whenever a limit is reached. The maximum rating for a 120Vac unit is 120Vac @ 0.5 amp or 28 Vdc @ 1.0 amp. A 240Vac unit is rated at 240Vac @ 0.25 amp. or 28Vdc @ 1.0 amp.

Figure 2. Electro-mechanical Relays Hookup Example

Limit # 4

Limit # 3

Instrument

Limit # 2

Limit # 1

8

7

6

5

4

3

2

1

PLUG-IN CONNECTOR

Switched Outputs

120 VAC @ 0.5 AMPS

120 VAC @ 0.5 AMPS

120 VAC @ 0.5 AMPS

120 VAC @ 0.5 AMPS

Page 22

Image 23
Contents Wall mount Multi-Channel Process Scanner Display Modes SetupChannel Configuration System ConfigurationError Messages and Solutions Mounting Table of ContentsPower Input Connector PIN Assignment Direct Interface to Universal Relay Module Trouble ShootingSpecifications Page Model no Description DescriptionTo Display Perform Following Steps How to Display ParametersDisplaying Parameters Display Modes Elapsed Time ModeMode Function Performed High/Low Channel Mode Scan ModeTypes of Deviation Displays SetupDeviation Mode Difference ModeSYS Parameter List CH Parameter ListSetup For Channel ON/OFF Channel ConfigurationSetup for Voltage or Current Input Setup For Input TypeSetup For Tare Setup For High ScaleSetup For Low Scale Setup For OffsetSetup For Deadband Setup For SetpointSetup for Universal Relay Channel 1 Relay Setup For LimitsTurning Channels ON/OFF Setup for Thermocouple/ Thermistor/ RTD InputsSetup For Engineering Units Temperature unitsSetup For Display Options System ConfigurationSetup Examples Setup For Cold Junction Calibration Setup For Display TimeSetup For Relay Latch/Non-Latch Setup for BuzzerThermocouple Calibration Procedure Setup For Channel CalibrationInput Range Setup for current and voltage Peaks Saving ParameterPage Channel Diff Enter PasscodeSYS CH Select ChannelCR.AL T/C K Current Elapsed Time IP Type Scan High ChannelLOW Channel Display Devn Channel Diff ThermistorOpen Collector Option RateLimits OutputsInput Connector Output Connector Input Connector PIN Assignment PowerDirect Serial Interface to Direct Interface to Universal Relay ModuleFactory Channel settings Trouble ShootingError Messages and Solutions Slots in Terminal Compartment For Mounting Screws MountingWarranty Page M4302/0306