Liebert VM18000, VM12000 user manual Alarm Messages, Meanings, and Corrective Actions

Page 37

Alarm Messages, Meanings, and Corrective Actions

 

MESSAGE

MEANING

CORRECTIVE ACTION

 

Start-Up Sequence Aborted

The UPS detects a condition that prevents a

Review and record all alarm messages. Perform

 

 

complete start-up.

prescribed action for specified alarm. If Start up

-Up

 

 

still aborts, contact Liebert at 1-800-222-5877.

Site Wiring Error

Incorrect phasing sequence of power conductors

Disconnect power from the UPS and call a

Start

 

wired to UPS.

wiring.

 

 

qualified electrician to correct and verify the

 

Incorrect Input Frequency

Input power frequency outside acceptable range.

Select the correct frequency in the configuration

 

 

 

screen. Verify the utility frequency.

 

 

 

 

AC

Input Power Out of Tolerance

Input power frequency outside acceptable range.

No corrective action required.

 

UPS battery supplying power to load equipment.

 

 

 

 

 

 

Battery Failed Test

Automatic Battery Test detects a weak battery.

Repeat the battery test via the LCD “Test Options”

 

 

 

menu selection. If battery fails again, contact

 

 

 

Liebert at 1-800-222-5877.

 

Can’t execute battery test:

Battery discharged too recently to perform test.

No corrective action required. UPS will perform

 

not recharged

 

next scheduled battery test.

 

Battery Date Expired

Batteries are over 5 years old.

Contact Liebert at 1-800-222-5877 to replace

Battery

 

 

batteries.

XX Minutes

Battery discharging. UPS calculates and displays

equipment to extend battery time.

 

UPS On Battery Time

Perform and orderly shutdown of load equipment

 

Remaining:

remaining battery time.

before time expires or shut off unnecessary load

 

 

 

 

 

Low Battery Shutdown

UPS discharged battery to minimum allowable

Upon return of power, start up UPS. The UPS

 

 

voltage and automatically shut down. No power

starts up by itself if Auto-Restart is enabled.

 

 

supplied to load.

 

 

Charger Battery Voltage High

Battery voltage exceeds acceptable limits causing

Contact Liebert at 1-800-222-5877 if this condition

 

 

automatic charger shutdown. Charger

persists for more than 2 minutes.

 

 

automatically restarts when battery voltage return

 

 

 

to acceptable levels.

 

 

WARNING: Load On Bypass

Load currently powered through bypass line due

If automatic transfer to bypass, load returns to

 

 

to automatic or manual transfer to bypass. Load

UPS power control for most temporary conditions.

 

 

unprotected from power disturbances or outages.

Review and record any other alarm messages. If

 

 

 

manual transfer to bypass, return to UPS power

Bypass

 

 

control when possible.

Bypass power out of

Bypass power voltage or frequency outside

Manual transfer to bypass not recommended.

tolerance

acceptable limits. Automatic bypass transfer

Wait for bypass power to return.

Bypass out of Sync

prohibited.

 

 

Bypass Overload

At least one phase of bypass current overloaded.

Reduce the load.

 

Excessive Retransfer

UPS completed at least 15 attempts to retransfer

Check other messages for inverter failure.

 

Attempted

load from utility back to UPS in 20 minutes or

Determine cause of overload and reduce load.

 

 

less. UPS unable to sustain load due to overload

 

 

 

or inverter failure. Load remains on bypass.

 

 

System Shutdown

Power Factor Corrector detects temporary

Press ON button to restart system. If start-up

 

Press ON to Restart System

condition at input of UPS.

aborts, review and record alarm messages and

 

 

 

contact Liebert at 1-800-222-5877.

 

Output Undervoltage

UPS output voltage or current outside acceptable

If UPS is unable to correct either one of these

 

Output Overvoltage

limits. Load automatically transferred to bypass.

conditions, contact Liebert at 1-800-222-5877.

System

 

UPS attempts automatic retransfer when voltage

 

 

or current is within acceptable limits.

 

 

 

 

 

Overload Phase A

Overload. UPS automatically transfers load to

Determine cause of overload and reduce load.

UPS

Overload Phase B

bypass if overload exceeds UPS capacity.

 

Output Overload

 

 

 

 

 

 

Fault: SYSTEM SHUTDOWN

UPS detects and fault and shuts down resulting in

Review and record alarm messages and contact

 

 

loss of power to load.

Liebert at 1-800-327-4384

 

Logic Error

Automatic diagnostic testing detects a hardware

Contact Liebert at 1-800-222-5877

 

 

or software failure in UPS internal control system

 

 

External Shutdown

External contact shuts down UPS through REPO.

Start-up UPS after correcting cause of external

 

 

 

shut-down.

 

System Shutdown Impending

UPS cabinet temperature above acceptable limits.

Check for restricted air flow or fan failure. If none,

**

Due to Overtemp

UPS automatically shuts down in 2 minutes if

contact Liebert at 1-800-222-5877

 

 

over-temperature continues.

 

 

Dial-Out Attempt Failed

UPS unsuccessfully attempted to dial out due to

Usually, the dial-out phone line is simply busy.

*

 

an event.

Check for secure and correct modem connection.

 

 

 

 

37

Image 37
Contents UPStation S Page Page Remote Emergency Power Off Repo Cable Liebert UPStation S Site Planning Data Unloading the UPS IntroductionOptional System Components Output InstallationKVA Start-up Checklist UPS accepts two-phase or three-phase power KVA Start-Up Checklist 18kVA Single Line DiagramControl / Display Panel OperationControl Buttons LCD DisplayDisabled Configuration Setting Default ValueTable #2 Factory Default Settings See OptionsLCD Menu Tree Battery Recharge On BatteryManual Restart after Manual Off Auto-BypassManual Off Remote Emergency Power OffOptions Distribution Configurable Distribution CDHardwire Load Module Receptacle Voltage Circuit Configuration BreakerStandard Load Module Load ModulesWeights/Dimensions Maintenance Bypass 8 18kVAApproximate Weights in Pounds Model Number 125 175 On-Line Standard FeaturesTest MaintenanceMounting InstallationKVA UPS Connections KVA Maintenance Bypass Connections Initial System Start-up OperationTransfer to Test from Maintenance Bypass Transfer to Maintenance Bypass from On-LineTroubleshooting Transfer to On-Line from TestGetting Started Select a Time Delay∙ Programming ∙ Review ∙ Override ∙ Load Labels Select a Load Module∙ Utility Failed ∙ Utility Restored Power Management Programming Elements∙ Turn OFF load ∙ Turn on load ∙ Warning Delays LoadsStep #1A Define Parameters Start ClosureStep #1B Step #1CSiteNet 1 Shutdown Interface Kits SiteNet 2 Power SurveillanceCables RS-232 with User-Configurable Relays VCR232CVBD061 3.5-6 kVA Standard External Battery CabinetsVBS061 / VBS062 6 kVA VBD121 8 12 kVARoutine Maintenance Appendix NEC Wire Gauge ChartMins UPStation S 6 kVA Battery Run Times #1 UPStation S 10 kVA Battery Run Times #1 UPStation S 18 kVA Battery Run Times #1 Alarm Messages, Meanings, and Corrective Actions Company Behind The Products UPStation S

VM18000, VM12000 specifications

The Liebert VM12000 and VM18000 are advanced precision cooling systems designed to provide reliable temperature and humidity control in critical environments such as data centers, telecommunications facilities, and industrial applications. These systems are engineered to meet the diverse needs of modern infrastructures that demand optimal performance, energy efficiency, and robust reliability.

One of the key features of the Liebert VM series is its high cooling capacity. The VM12000 offers a cooling capacity of 12,000 BTU/h, while the VM18000 provides an impressive 18,000 BTU/h. This makes both models ideal for environments where heat load is significant, ensuring that critical equipment remains within operational limits. The systems employ variable speed technology, allowing them to dynamically adjust cooling output based on real-time conditions, which enhances energy efficiency and performance.

The Liebert VM series is equipped with advanced control systems, including microprocessor controls that enable precise monitoring and adjustments. Users can easily access real-time data through intuitive interfaces, allowing for seamless management of cooling settings. Additionally, the systems can be integrated into building management systems (BMS), offering centralized control that enhances operational efficiency.

Another notable characteristic of the VM series is its modular design. This allows for easy scalability, making it suitable for both small setups and large, complex installations. The flexibility offered by the modular design permits the addition of cooling units as cooling demands grow, ensuring that users can keep pace with their evolving requirements.

In terms of energy efficiency, the Liebert VM12000 and VM18000 meet and exceed the efficiency standards set by the industry. The systems utilize R-410A refrigerant, which is environmentally friendly and contributes to higher energy performance. This focus on sustainability not only reduces the carbon footprint but also lowers operating costs, providing significant savings over time.

Furthermore, the Liebert VM series is built with robust components designed for durability and longevity. The systems are engineered for high performance in demanding conditions, ensuring reliability even in the most challenging environments.

Overall, the Liebert VM12000 and VM18000 precision cooling units stand out for their high capacity, energy efficiency, advanced controls, and modularity. These features make them a top choice for businesses needing reliable cooling solutions to protect their critical infrastructure while also promoting energy sustainability.