Step 5: Connect Ground and Power Cables

3.Verify that the switch on each power supply faceplate is in the OFF (O) position.

4.For each power supply:

a.Insert the appliance coupler end of a power cord into the appliance inlet on a power supply faceplate.

b.Insert the plug into an AC power source receptacle.

c.Verify that the power cord does not block access to router components or drape where people could trip on it.

Connect DC Power

CAUTION: You must ensure that power connections maintain the proper polarity. The power source cables might be labeled (+) and (–) to indicate their polarity. There is no standard color coding for DC power cables. The color coding used by the external DC power source at your site determines the color coding for the leads on the power cables that attach to the terminal studs on the power faceplate.

1.Make sure that there is no power flowing from the external power source, so that the voltage across the leads of the power cables is 0 V. Ensure that there is no chance that the cable leads might become active during the procedure.

2.For each power supply, verify that the power switch on the power supply faceplate is in the OFF (O) position.

3.Connect the grounding cable to a proper earth ground for each external DC power source, if it is not already connected.

4.Verify that a licensed electrician has attached the cable lug provided with the router to the grounding cable

5.Using a number 2 Phillips screwdriver, remove the screw next to the grounding symbol above the power supplies on the chassis rear. Secure the grounding cable lug to the grounding point by reinstalling and tightening the screw.

6.Verify that a licensed electrician has attached a listed power cable lug to each power source cable.

7.Loop the power cables through the hook located on the faceplate to the right of the field-wiring terminals.

8.Depending on the type of power cable lugs used, loosen or remove the screws on the field-wiring terminals.

9.Insert each power cable lug into the appropriate field-wiring terminal. Use a number 1 Phillips screwdriver to secure the power cable lug. Turn the screw on each field-wiring terminal clockwise, and apply between 8 lb-in. (0.9 Nm) and 9 lb-in. (1.02 Nm) of torque to each screw.

a.Insert the positive (+) source cable into the return terminal (labeled RTN).

b.Insert the negative (–) source cable into the input terminal (labeled –48).

10.Verify that the DC source power cabling and the grounding cabling are correct,

Step 5: Connect Ground and Power Cables 11

Image 11
Contents M7i Internet Router Quick Start European Union Declaration of Conformity Rack-Mounting Requirements Quick Start DescriptionPrepare the Site Prepare the Site Tools Required Rack Clearances and Router DimensionsMounting Bracket in Front-Mounting Position Prepare for Front or Center MountingInstall the Router Lift the Router into the Rack Connect External Devices and PIC CablesConnect FIC and PIC Cables Connect a Management Console or Auxiliary DeviceConnect to a Network for Out-of-Band Management Connect AC Power Connect Ground and Power CablesConnect DC Power Connect the Power Cables to a DC Router Power On the RouterCli configure edit root@# Perform Initial Software ConfigurationName-server address Interfaces fxp0 Unit 0 family inet Safety Warnings M7i Internet Router Quick Start European Union Compliance Statements for NebsCompliance Statements for EMC Requirements CanadaDeclaration of Conformity Junos Internet Software for Supported Routing Platforms List of Technical PublicationsWeb User Guide Junos ReferencesJUNOScope Documentation Junos API and Scripting DocumentationHardware Documentation Release Notes Junos Internet Software Network Operations GuidesRequesting Support Revision History